ABB 1SDA065776R1 Moulded Case Circuit Breaker - 8 kV Uimp
Part Number: 1SDA065776R1
Quick Summary
ABB 1SDA065776R1 Moulded Case Circuit Breaker provides high-capacity protection for industrial power distribution panels. Engineers often struggle with crowded switchgear, complex wiring, and the need for reliable fault isolation during peak loads. This device carries CE conformity (EC Declaration of Conformity Tmax T8), RoHS and REACH compliance, and CMRT/TSCA declarations, ensuring regulatory alignment and supply chain transparency. By combining a front-terminal, fixed 4P design with the PR331/P LSIG electronic release, it delivers fast, selective protection while simplifying installation and maintenance in harsh manufacturing environments.
Product Information
Extended Description
1SDA065776R1 ABB: C.BREAKER TMAX T8V 2000 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 2000
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T8 | Breakers - Packaging disposal information
Order Code US and Canada
T8VFD4GE000000XX
EAN
8015644686871
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
553 mm
Product Net Height
382 mm
Product Net Depth / Length
282 mm
Product Net Weight
12.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
650 mm
Package Level 1 Height
475 mm
Package Level 1 Depth / Length
695 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8015644686871
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
4500 cycle | 20 cycles per hour
Mechanical Durability
15000 cycle | 60 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 46 W
Rated Current (In)
2000 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (380 V AC) 100 kA | (400 V AC) 100 kA | (415 V AC) 100 kA | (440 V AC) 100 kA | (500 V AC) 75 kA | (690 V AC) 60 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 40 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 1.3 kA | (230 V AC) 1.3 kA | (380 V AC) 130 kA | (400 V AC) 130 kA | (415 V AC) 130 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
2000 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T8
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T8
Wiring Diagram
Wiring diagram T8
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4934 >> 4 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
4P front-terminal design reduces wiring time and simplifies wiring harness routing, enabling quicker panel builds and safer maintenance. The business impact is faster commissioning and reduced field errors in dense switchgear, making it ideal for transformer feeders and high‑density panels. This configuration supports reliable, front-access servicing in tight installations where space is at a premium. High current rating and fault capability provide protection up to 2000 A with Ics up to 100 kA and Icu up to 130 kA depending on voltage, delivering robust grid protection and enabling selective coordination in manufacturing and data center environments. Applications include large electrical feeders, critical plant sections, and utility substations where uptime matters. The lifecycle efficiency reduces wear on upstream devices and minimizes downtime during fault events.
Get a Quick Quote for a ABB 1SDA065776R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA065776R1?
Enquire Now
FAQs
Plan for front-terminal wiring access to minimize top-entry clearance and facilitate safe maintenance. Ensure 553 mm width, 382 mm height, and 282 mm depth fit within your enclosure, and verify 12.5 kg unit weight for mounting hardware and rack support. Use front-access terminals to simplify wiring and reduce service time.
The PR331/P LSIG electronic release provides precise tripping guidance and fast response under fault conditions, improving coordination with downstream devices. This enhances selective tripping in complex feeder configurations, reducing nuisance trips and protecting critical loads in manufacturing lines and transformer feeders.
Yes. With 4 poles, 2000 A rated current, front-terminal design, and Ics/Icu values up to 100/130 kA (depending on voltage), it supports transformer and generator protection where high fault current and reliable interruption are essential. Compatibility with Tmax T architecture helps ensure consistent protection and coordination in power distribution schemes.
The device carries CE conformity (EC Declaration of Conformity Tmax T8), RoHS and REACH declarations, CMRT, and TSCA declarations. These ensure regulatory compliance, safe material usage, and transparent supply-chain reporting, aiding audit readiness and customer qualification processes.
Electrical durability is rated at 4500 cycles (20 cycles per hour) and mechanical durability at 15000 cycles (60 cycles per hour), with 46 W power loss per pole. This translates to longer intervals between maintenance, lower operating costs, and improved equipment uptime in continuous production environments.