ABB 1SDA065780R1 Moulded Case Circuit Breaker - Icu 130 kA
Part Number: 1SDA065780R1
Quick Summary
ABB 1SDA065780R1 Moulded Case Circuit Breaker protects industrial power distribution by interrupting fault currents. This 3P fixed device helps address nuisance trips and space constraints in control panels, delivering reliable protection without expanding panel depth. The Tmax T8 family features robust materials and precise release technology, with CE conformity, RoHS and REACH declarations plus TSCA reporting to support global compliance. By combining high current capacity with streamlined installation, this MCCB reduces wiring complexity and accelerates panel commissioning, delivering improved uptime and lower total cost of ownership for large manufacturing sites and utility-scale equipment installations.
Product Information
Extended Description
1SDA065780R1 ABB: C.BREAKER TMAX T8V 2500 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR331/P-LSI R 2500
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T8 | Breakers - Packaging disposal information
Order Code US and Canada
T8VFE3HC000000XX
EAN
8015644686918
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
427 mm
Product Net Height
382 mm
Product Net Depth / Length
282 mm
Product Net Weight
9.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
525 mm
Package Level 1 Height
475 mm
Package Level 1 Depth / Length
695 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644686918
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
4000 cycle | 20 cycles per hour
Mechanical Durability
15000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 73 W
Rated Current (In)
2500 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (380 V AC) 100 kA | (400 V AC) 100 kA | (415 V AC) 100 kA | (440 V AC) 100 kA | (500 V AC) 75 kA | (690 V AC) 60 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 40 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 1.3 kA | (230 V AC) 1.3 kA | (380 V AC) 130 kA | (400 V AC) 130 kA | (415 V AC) 130 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
2500 A
Release
PR232/P-LSI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T8
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T8
Wiring Diagram
Wiring diagram T8
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3-pole fixed circuit-breaker with front terminals → Business Impact: Simplified installation and reduced enclosure depth, enabling more compact switchgear layouts in existing rooms without sacrificing protection → Application: Main distribution panels and transformer feed sections that require reliable 3P protection. Feature: Rated current up to 2500 A and Rated Operational Voltage of 690 V AC → Business Impact: Supports high-demand loads and scalable plant protection with ample headroom, reducing upstream upgrades and downtime → Application: Large motors, transformers and heavy-duty feeders in industrial plants. Feature: High short-circuit/impulse ratings including Icu up to 130 kA and Uimp 8 kV → Business Impact: Superior fault tolerance and selective coordination, lowering risk of cascading trips and equipment damage → Application: Critical power rails and protection zones near high-energy equipment. Feature: Release PR232/P-LSI and Front-terminal, fixed design → Business Impact: Precise tripping and straightforward maintenance with accessible diagnostics, improving maintenance efficiency and safety → Application: Control cabinets and switchgear assemblies requiring deterministic protection. Feature: Compliance and environmental declarations (CE, RoHS, REACH, CMRT, TSCA) → Business Impact: Simplifies regulatory reporting and global procurement with a single, traceable MCCB → Application: Global manufacturing operations and multi-site projects needing consistent compliance.
Get a Quick Quote for a ABB 1SDA065780R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA065780R1?
Enquire Now
FAQs
The ABB 1SDA065780R1 uses fixed front-terminal connections designed for straightforward panel mount. Confirm enclosure cutouts match the 427 mm width, 382 mm height, and 282 mm depth, then secure the device with the included mounting provisions. Verify conductor sizing, torque specs, and ensure alignment with the PR232/P-LSI release for proper actuation and coordination with downstream protection devices.
The unit provides an Icu rating up to 130 kA, enabling rapid interruption of high-energy fault currents. For transformer protection, this supports selective coordination by isolating only the affected section, minimizing downstream disruption while safeguarding windings and switchgear against catastrophic faults.
Yes. The model carries RoHS declarations and REACH compliance. Additional documentation includes CMRT for conflict minerals reporting and TSCA declarations, along with the EC Declaration of Conformity for CE compliance, supporting global regulatory requirements.
Product net width is 427 mm, height is 382 mm, and depth is 282 mm. The unit weighs 9.7 kg, with package dimensions shown in the related container data. Use these values to plan mounting clearances, wiring, and service access in new or retrofit enclosures.
This 3P MCCB from the Tmax T family is intended for large-power distribution, including transformer and motor feeder protections. It adheres to IEC standards, supports front-termination installation, and aligns with ETIM classification and other external standards to ensure compatibility across ABB SACE Tmax T protection schemes.