ABB 1SDA065792R1 Moulded Case Circuit Breaker - PR331/P LSIG

Part Number: 1SDA065792R1
Manufacturer
ABB
Part number
1SDA065792R1

Quick Summary

ABB 1SDA065792R1 Moulded Case Circuit Breaker is designed to protect electrical distribution panels in industrial settings by interrupting fault currents quickly. Operators often battle nuisance trips and costly downtime, especially in high-load MCCs where fast, reliable protection is essential. This device carries CE conformity for Tmax T8, REACH and RoHS declarations, and TSCA support to help meet global regulatory requirements. Beyond protection, the unit offers fixed 3-pole reliability with rear-vertical terminals and a solid-state PR331/P LSIG release, delivering safe switching in 690 V systems. For buyers, this translates to reduced maintenance costs and simpler supplier qualification while maintaining safety standards.

Product Information

Extended Description

1SDA065792R1 ABB: C.BREAKER TMAX T8V 3200 FIXED THREE-POLE WITH TERMINALS REAR VERTICAL AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 3200
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T8 | Breakers - Packaging disposal information
Order Code US and Canada
T8VFF3JE000000XX
EAN
8015644687038
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
427 mm
Product Net Height
382 mm
Product Net Depth / Length
282 mm
Product Net Weight
11.7 kg
Package Level 1 Units
1 piece
Package Level 1 Width
525 mm
Package Level 1 Height
665 mm
Package Level 1 Depth / Length
695 mm
Package Level 1 Gross Weight
13.2 kg
Package Level 1 EAN
8015644687038
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
3000 cycle | 20 cycles per hour
Mechanical Durability
15000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 117 W
Rated Current (In)
3200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (380 V AC) 100 kA | (400 V AC) 100 kA | (415 V AC) 100 kA | (440 V AC) 100 kA | (500 V AC) 75 kA | (690 V AC) 60 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 40 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 1.3 kA | (230 V AC) 1.3 kA | (380 V AC) 130 kA | (400 V AC) 130 kA | (415 V AC) 130 kA | (440 V AC) 130 kA | (500 V AC) 100 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
3200 A
Release
PR331/P LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T8
Terminal Connection Type
Fixed Circuit-Breakers | Rear flat Vertical
Data Sheet, Technical Information
Tmax. T Generation - Low voltage molded case circuit breakers up to 1200 A - UL 489 and CSA C22.2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T8
Wiring Diagram
Wiring diagram T8
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: High current rating and 3P design. Business Impact: Supports 3200 A per pole and up to 130 kA Icu (voltage dependent), enabling safe interruption of large fault currents. Application: transformer feeders and heavy-duty MCCs in industrial plants. Feature: PR331/P LSIG solid-state release. Business Impact: Faster, more reliable tripping with improved selectivity and reduced fault duration. Application: critical protection in switchgear and distribution panels. Feature: Rear vertical terminals for fixed mounting. Business Impact: Simplified wiring and clean panel integration with a compact footprint. Application: retrofits and new builds in Tmax T installations. Feature: 690 V AC rated, Ui 1000 V and 8 kV rating. Business Impact: Safe operation across medium-voltage distributions with enhanced insulation and surge tolerance. Application: feeder protection in energy and manufacturing facilities. Feature: Long mechanical and electrical durability. Business Impact: 15000 mechanical cycles and 3000 electrical cycles reduce maintenance and replacement costs. Application: continuous operation environments with high duty cycles. Feature: Compliance and environmental declarations. Business Impact: RoHS, REACH, CMRT, TSCA and WEEE support streamline procurement and regulatory reporting. Application: regulated projects and global deployments across facilities.

Get a Quick Quote for a ABB 1SDA065792R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA065792R1? Enquire Now

FAQs

The unit is a fixed circuit-breaker with rear flat vertical terminals. It is designed for straightforward installation in standard panels and Tmax T layouts, supporting reliable wiring in compact MCCBs with a 427 mm wide footprint and 282 mm depth. This enables efficient wiring and back-to-back mounting where space is at a premium.
This 3P MCCB is rated for 3200 A per pole with an Icu up to 130 kA depending on voltage. It also supports 40 A short-time withstand (Icw) for 1 second, and up to 100 kA short-circuit breaking capacity at common low voltages, ensuring robust protection across transformer feeders and distribution panels.
Yes. The device carries a CE Declaration of Conformity for Tmax T8, with RoHS and REACH declarations for ABB Sace circuit breakers, a TSCA declaration, CMRT for conflict minerals, and WEEE classification. These ensure regulatory compliance in multiple markets and simplify procurement documentation.
Best suited for transformer and generator protection within the Tmax T family, and general electrical protection in medium-voltage distribution panels. Its 690 V AC rating, PR331/P LSIG release, and fixed rear-vertical terminals make it ideal for high-demand MCCs, switchgear, and protective feeder blocks in industrial facilities.
With 15000 mechanical cycles and 3000 electrical cycles, this MCCB offers long service life and reduced maintenance frequency. The reliable LSIG release, low per-pole power loss (117 W), and robust environmental compliance minimize downtime, spare-part consumption, and regulatory risk, contributing to lower total cost of ownership over the system life.