ABB 1SDA066760R1 Moulded Case Circuit Breaker - TMF Front 4P
Part Number: 1SDA066760R1
Quick Summary
ABB 1SDA066760R1 Moulded Case Circuit Breaker is a TMF four-pole protector for industrial power distribution. It simplifies wiring with front-terminal connections while delivering predictable, time-coordinated tripping. Many engineers struggle with inconsistent trip behavior and documentation gaps; this unit provides robust protection and clear labelling for audits. CE conformity, RoHS and REACH declarations, along with CMRT and TSCA disclosures, help meet global supplier requirements and customer audits. As part of the ABB SACE FORMULA family, it offers compact dimensions and reliable performance, enabling you to consolidate devices in tighter panels while maintaining service continuity and safety compliance for machines and processes.
Product Information
Extended Description
1SDA066760R1 ABB: C.BREAKER FORMULA A1N 125 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 30-400 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Environmental Information - Formula A1-A2 | Breakers - Packaging disposal information
Order Code US and Canada
AAN030TW-4
EAN
8015644694265
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
136.5 mm
Package Level 1 Height
124 mm
Package Level 1 Depth / Length
110.5 mm
Package Level 1 Gross Weight
1.05 kg
Package Level 1 EAN
8015644694265
Product Main Type
SACE FORMULA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms | CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 4 W
Rated Current (In)
Main Circuit 30 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 18 kA | (415 V AC) 7.5 kA | (440 V AC) 6.25 kA | (480 V AC) 4.5 kA | (500 V AC) 2.5 kA | (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 25 kA | (480 V AC) 18 kA | (500 V AC) 10 kA | (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
TMF
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
Data Sheet, Technical Information
1SDC210032D0204
Declaration of Conformity - CE
EC Declaration of Conformity Formula DSA A1
Wiring Diagram
Wiring diagram FORMULA A1-A2
Instructions and Manuals
Installation Instructions Formula A1/III-IV
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The four-pole front-terminal design enables straightforward wiring during panel assembly, reducing installation time and wiring errors, which translates to lower labor costs on site and faster commissioning. In practice, this means more predictable project timelines and fewer retrofit calls after energization. Rated for 30 A with Ui 690 V and Uimp 6 kV, it delivers robust overcurrent and transient protection across typical distribution and motor feeder circuits, supporting reliable uptime in manufacturing cells and process lines. With Ics and Icu values tailored for common industrial voltages, engineers gain confidence in safe interruption of faults without compromising downstream equipment. Power loss of 4 W per pole under rated conditions helps manage heat in crowded control cabinets, supporting longer device life and reduced cooling costs. At a compact 101.6 mm width, 130 mm height, and 60 mm depth, the unit fits tighter panels and retrofits more easily than larger feeders. The 1 kg mass contributes to lighter installation without sacrificing rigidity or mounting stability. Documentation and identifiers such as EAN 8015644694265 and Order Code AAN030TW-4 streamline procurement and traceability, while the product is aligned with IEC standards and WEEE disposal guidelines. Compatibility with front-terminal configurations simplifies field wiring, reduces torque requirements on terminal screws, and accelerates safe, durable connections in demanding environments. The integration with the ABB SACE FORMULA family also ensures consistent maintenance practices, spare parts availability, and unified diagnostic labeling across devices in your line.
Get a Quick Quote for a ABB 1SDA066760R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA066760R1?
Enquire Now
FAQs
This unit features a front-terminal connection design, which simplifies wiring inside electrical cabinets, reduces terminal torque variability, and speeds up commissioning. Its compact footprint fits dense panels, while the four-pole configuration provides synchronized protection for multi-line feeders. For best results, ensure compatible mounting rails and proper strain relief on cables to maintain secure connections and long-term reliability.
Key ratings include rated current In of 30 A, rated insulation voltage Ui of 690 V, rated impulse withstand voltage Uimp of 6 kV, and rated operational voltage of 550 V AC / 250 V DC. The device provides Ics up to 50 kA and Icu up to 100 kA, ensuring safe interruption of faults across typical distribution systems. These specs translate to strong protection for main feeders and motor circuits while meeting standard IEC requirements.
Yes. The unit carries CE conformity, RoHS and REACH declarations, along with documentation such as CMRT for conflict minerals and a TSCA declaration. WEEE guidance and EC Declaration of Conformity are available, ensuring regulatory alignment across markets. Wiring diagrams and installation instructions are included to support compliant installation and maintenance procedures.
Yes, with its TMF release and 4P configuration, the device is well-suited for motor protection and power distribution in control panels, drives, and HVAC systems. Its high short-circuit withstand capacities (Ics and Icu) and front-terminal wiring facilitate reliable protection of motor feeders and transformer interfaces, while the compact form factor eases retrofit into existing panels.
The product ships with and is compatible with a data sheet (1SDC210032D0204), wiring diagram (FORMULA A1-A2), and installation instructions (Formula A1/III-IV). EAN 8015644694265 and order code AAN030TW-4 simplify procurement. Being part of the ABB SACE FORMULA family, spare parts and diagnostics remain consistent across the product line, aiding maintenance planning and lifecycle management.