ABB 1SDA066765R1 Moulded Case Breaker - 4P TMF A1N CE

Part Number: 1SDA066765R1
Manufacturer
ABB
Part number
1SDA066765R1

Quick Summary

Moulded Case Breaker is a protective device that interrupts fault current in industrial power circuits. This ABB model delivers reliable short-circuit protection for 4-pole systems with front-terminal access, streamlining installation in control panels and switchgear. It complies with IEC standards and is CE-conformant, supporting RoHS and REACH requirements for safer, more sustainable equipment. The A1N 125 rated main circuit and TMF release are designed to minimize downtime while simplifying maintenance planning. For engineers and procurement teams, this means predictable performance, long service life, and a documented conformity trail that supports auditing, compliance, and efficient project execution.

Product Information

Extended Description

1SDA066765R1 ABB: C.BREAKER FORMULA A1N 125 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 80-800 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Environmental Information - Formula A1-A2 | Breakers - Packaging disposal information
Order Code US and Canada
AAN080TW-4
EAN
8015644006754
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
136.5 mm
Package Level 1 Height
124 mm
Package Level 1 Depth / Length
110.5 mm
Package Level 1 Gross Weight
1.05 kg
Package Level 1 EAN
8015644006754
Product Main Type
SACE FORMULA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms | CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 9 W
Rated Current (In)
Main Circuit 80 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 18 kA | (415 V AC) 7.5 kA | (440 V AC) 6.25 kA | (480 V AC) 4.5 kA | (500 V AC) 2.5 kA | (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 25 kA | (480 V AC) 18 kA | (500 V AC) 10 kA | (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
TMF
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
Data Sheet, Technical Information
1SDC210032D0204
Declaration of Conformity - CE
EC Declaration of Conformity Formula DSA A1
Wiring Diagram
Wiring diagram FORMULA A1-A2
Instructions and Manuals
Installation Instructions Formula A1/III-IV
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: 4P front-terminal design enables quick panel integration and reduced wiring complexity, cutting installation time and potential contact resistance issues in high-current environments. This leads to measurable improvements in assembly efficiency and reliability in electrical rooms and distribution panels. Application: transformer/generator protection and distribution boards in industrial facilities benefit from the TMF release, delivering fast opening times (SOR 15 ms; UVR 15 ms) that minimize fault energy delivery and downstream equipment stress. Feature → Business Impact → Application: 80 A nominal current (In main circuit) paired with IEC-compliant insulation (Ui 690 V) supports compact, safe, and compliant busbar configurations in compact switchgear. Application: new builds and retrofits where space, safety, and regulatory compliance are critical considerations. Feature → Business Impact → Application: high short-circuit withstand (Ics up to 50 kA at 240 V AC and Icu up to 100 kA at 240 V AC) provides robust protection for critical loads such as motors, transformers, and power distribution networks, reducing risk of cascading faults. Application: data centers, manufacturing lines, and process industries seeking reliable fault-clearing performance. Feature → Business Impact → Application: RoHS and REACH declarations, CMRT reporting, and TSCA compliance give procurement teams confidence in regulatory readiness and supply chain transparency, supporting easier supplier audits and global deployments. Application: multinational projects with strict sustainability and compliance requirements. Feature → Business Impact → Application: compact weight (1 kg) and defined packaging (1 piece per outer box) simplify logistics, reduce handling risks, and streamline warehouse stock management. Application: spare parts planning and after-sales service for ABB SACE Formula products. Feature → Business Impact → Application: extensive documentation (Data Sheet, Wiring Diagram, installation manuals) accelerates commissioning, troubleshooting, and training for field technicians. Application: service contracts and technician onboarding in industrial environments.

Get a Quick Quote for a ABB 1SDA066765R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA066765R1? Enquire Now

FAQs

This 4P Moulded Case Breaker uses front-terminal connections that simplify wiring access and reduce panel depth. Ensure panel cutouts accommodate the 60 mm depth and verify torque specs for terminals to maintain secure electrical connections and maintain UL/IEC compliance.
Main circuit current IN is 80 A, Ui is 690 V, Upropylene: 550 V AC / 250 V DC, Ics up to 50 kA at 240 V AC, Icu up to 100 kA at 240 V AC. The device uses a TMF release with fast opening times, ensuring rapid fault clearing and reduced fault energy.
Yes. The product is categorized as a SACE Formula power circuit-breaker designed for trafo/generator/installation protection, with appropriate short-circuit withstand ratings and a 4P configuration to cover multi-pole transformer and generator protection schemes.
The unit ships with CE conformity (EC Declaration of Conformity Formula DSA A1), RoHS and REACH declarations, TSCA compliance, and CMRT reporting, ensuring regulatory readiness and supply-chain traceability for global deployments.
With a rated electrical durability of 1500 cycles and mechanical durability of about 8500 cycles, the device offers extended service life under typical industrial cycling. This reduces maintenance frequency, lowers spare-part costs, and improves system uptime in critical power distribution schemes.