ABB 1SDA066818R1 Moulded Case Circuit Breaker - XT1B 4P Front Terminals TM Release IEC60947-2
Part Number: 1SDA066818R1
Quick Summary
ABB 1SDA066818R1 is a moulded case circuit breaker for protecting 690 V distributions in industrial controls. For engineers facing panel space constraints and wiring complexity, this XT1B with front terminals and a TM release simplifies installation and improves selective protection. It carries CE conformity (EC DoC), an LR certificate, and an environmental profile including an EPD and recyclable content, aligning with sustainability programs. The 4P design delivers a compact footprint without compromising protection, while the 100 A rating and 690 V capability support robust, safe operation across demanding manufacturing environments. This combination delivers faster commissioning, easier maintenance, and clear cost-of-ownership advantages for panel builders and system integrators.
Product Information
Extended Description
1SDA066818R1 ABB: C.BREAKER TMAX XT1B 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
688e96d7-2d1c-4e22-b59c-50ff06516bf8 Italy (IT)
Simplified SCIP
b081d9e5-0266-467a-8f8f-906a85a12afa Germany (DE) | 4be3f089-aca5-4fb8-8ca5-ca75d8b5d067 Sweden (SE) | 27550f41-4161-4b3a-8225-f1e246ce2a09 Germany (DE) | 6c03d9fa-a586-4041-bf40-cd77812ad7f8 Germany (DE) | 90c62ad0-99e2-4cfb-a4b3-7a1d2b822175 Czech Republic (CZ) | 70f88417-6d1f-4419-b8ca-cd081ff4976a Poland (PL) | 9f1ba41e-13c8-4949-8f02-c3e198ca3ccb Netherlands (NL) | 7f066c37-7fb1-47df-b33d-5f27effe988d Netherlands (NL) | ba2a17d0-ebc2-40ef-8670-1145eb519351 Estonia (EE) | 72d61050-bae5-4d72-b9f9-bd391a4a830e Greece (GR) | d9334c91-3248-4e66-9b4c-3919e09712e4 Portugal (PT) | dd27b78a-c66a-4eb0-b691-907a2e33f930 Norway (NO) | 6bfbb959-ec01-495a-a4a0-08ac8e4e3667 Finland (FI) | 8186f6da-48cd-49d8-a4ec-d7d71c32770c Netherlands (NL) | b3c31785-12c6-4630-83f1-b2d78d65bea1 Germany (DE) | 9607cf14-ae26-4495-a29e-67cdeff195c1 Denmark (DK) | b7deb7c4-4af4-4932-8db3-8f1bd014dce3 Germany (DE) | d1429ebb-e55d-4293-a755-dff56a49be68 Croatia (HR) | 6d10ed05-32eb-48f2-88a8-1b46926daf87 Poland (PL) | 13935ad8-46e8-49d7-9e27-360bd0cbc6a4 France (FR) | d9a62902-39ce-4272-bc64-dbb65a1b0e6f Netherlands (NL) | c2927a9e-50d1-4415-82df-df6998b70511 Spain (ES) | fea510e3-600e-4a0a-9c52-8483df25f240 Netherlands (NL) | b55767a9-8b5d-4dce-b7f7-413e4c989aec Bulgaria (BG) | ed811c7e-4d71-472c-8176-6c42e3067f7e Sweden (SE) | 4cd65b04-2f4a-4fe8-8d5a-cb5ddd0c309d Poland (PL) | 458cef3b-a92d-4b27-894c-1c5125dd37d5 France (FR)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1BE4100AFF000XXX
E-Number (Finland)
3640500
E-Number (Norway)
4309708
EAN
8015644007256
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.44 kg
Package Level 1 EAN
8015644007256
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 7 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.25 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
B
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
4P front-terminal design with a thermomagnetic release (TM) reduces wiring errors and speeds installation, improving panel build times and field servicing in dense control cabinets. The 70–100 A setting range provides precise protection coordination near the 100 A load, minimizing nuisance trips in multi-circuit panels and supporting reliable motor feeder protection. With a rated voltage of 690 V and an 8 kV impulse withstand, the device is compatible with European and global low-voltage networks, reducing substitute requirements during expansion. Short-circuit ratings (Ics/Icu) up to 25 kA at lower voltages and down to 3 kA at higher voltages ensure fast, safe fault interruption for transformers and heavy machinery. Power loss of 7 W per pole helps manage thermal rise, while 25,000-cycle mechanical durability supports frequent switching in process environments. EcoSolutions data and a recyclability rating of 55.9% assist sustainability goals, while standard busbar connections (45.5–80 mm²) simplify retrofits and new builds in existing panels.
Get a Quick Quote for a ABB 1SDA066818R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA066818R1?
Enquire Now
FAQs
Install the 4P fixed front-terminal XT1B directly into the panel busbar with 45.5–80 mm² conductors. Use the recommended 6 N·m tightening torque on the bolt terminals, ensure front-access wiring for easy future maintenance, and align the device with IEC 60947-2 guidelines. The unit engages with 690 V systems and supports rapid commissioning in MCCs and distribution boards.
Key specs include 100 A rated current, 690 V rated operational voltage, 8 kV rated impulse withstand, 4 poles, and a 70–100 A setting range. The device provides Ics up to 25 kA at lower voltages and 3–18 kA across higher voltages, with Icu values appropriate to system voltage. Front terminals and TM release are standard features for coordination and safety.
Yes. The XT1B with TMD release and 4P configuration is well-suited for motor feeders and protect-disconnect scenarios in production lines. The 70–100 A setting supports selective tripping, while the 690 V rating accommodates drive systems and heavy machinery. Its compact footprint helps maximize panel density without compromising protection.
This model includes CE conformity (EC Declaration of Conformity) and an LR certificate, with an Environmental Product Declaration (EPD) and a recyclability rating of 55.9%. WEEE considerations and packaging-disposal guidance are also documented, supporting sustainability commitments in modern plants.
The device offers 7 W per pole power loss under rated conditions, aiding thermal management in cabinets. A robust 25,000-cycle mechanical durability reduces replacement frequency in high-switching environments. Front-terminal access simplifies wiring and servicing, reducing maintenance time and total cost of ownership in panel upgrades or retrofits.