ABB 1SDA067391R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067391R1
Quick Summary
ABB 1SDA067391R1 Moulded Case Circuit Breaker is a three-pole XT1 device designed to protect and control low-voltage power distribution. Engineers often struggle with reliable trip settings, compact installation, and front-terminal accessibility in dense cabinets. This product carries CE conformity under the EC Declaration of Conformity, as well as GL and LR certificates, reinforcing global compliance and traceability. It integrates seamlessly with SACE Tmax XT systems, offering precise protection and plug‑and‑play installation advantages. For manufacturers seeking safer, standards-aligned protection with predictable maintenance, this MCCB delivers robust performance, lifecycle efficiency, and scalable protection strategies for modern electrical plants.
Product Information
Extended Description
1SDA067391R1 ABB: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 25-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
db866913-fe89-4d27-9e19-1544af8a4f02 Italy (IT)
Simplified SCIP
f202abe0-12ec-4179-97cf-89b315c6c305 Belgium (BE) | 3d1fa375-8d2c-4fb5-beca-a263dfdbb827 Hungary (HU) | 54b75992-3367-4791-b554-6dcbff2ab3cf Spain (ES) | a27280a8-bca2-4b6a-b682-ae8b015e303e Greece (GR) | f8cb45b8-f33d-4e6b-82a8-09008d3d5c87 France (FR) | 575dd2dc-8960-4074-82bf-3f3a454ae5eb Germany (DE) | 271e4ada-c178-46d8-aed4-cf3761368d48 Denmark (DK) | 5fe60ea6-1acd-43a3-b6c0-21244ea6a92b Sweden (SE) | 8ef0202e-998e-43d7-98b7-7e3bd879e073 Germany (DE) | 79ff2322-f3e6-4a8d-b239-076d37b54fd2 France (FR) | b27a41fe-5e2e-48d4-b833-8334bc466293 Germany (DE) | e273ae3b-0922-414e-93c0-80847d9fdda3 Czech Republic (CZ) | e963bee8-abc4-4c15-96b0-94965f6da5b1 Croatia (HR) | 8d05a666-8814-4069-9dee-84b22f24a159 Germany (DE) | 40ef665a-3599-439a-92b4-b97e5b6085cc Poland (PL) | 7cae70a8-4172-4379-98ce-ff8f11f1c36f Poland (PL) | 49d6c5fa-246b-46e4-b329-4b165daac59c Germany (DE) | fa51e80d-bef3-49a2-af40-09ec71becb56 Portugal (PT) | 29ebdc46-1142-4461-96f6-db3e960849ff Belgium (BE) | ad417ab4-6c41-4c97-9ddd-ae123597879c Estonia (EE) | f9c06e0e-932a-4471-a853-26b1015c0454 Poland (PL) | fa1d5045-f5f1-4b1d-9ae6-a0a3df0c2bad Hungary (HU) | daaa0f9a-041f-4888-be09-84b146fb9d05 Finland (FI) | e790b803-9f89-4861-aafb-77ff28a18a26 Bulgaria (BG) | a0187f54-10d1-4941-b25f-e7d1c73d8684 Norway (NO) | 6ce47805-01dc-43b0-b9d7-a5185f82de42 Netherlands (NL) | 85b2530f-01c1-49b5-b154-f7549e299333 Sweden (SE)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE3025AFF000XXX
E-Number (Finland)
3638773
E-Number (Norway)
4309611
EAN
8015644012151
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.124 kg
Package Level 1 EAN
8015644012151
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
25 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
17.5...25 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: 3P XT1 fixed front-terminal design simplifies wiring and reduces installation time in panel boards and distribution cabinets, with a front-terminal bolt connection and a tightening torque of 6 N·m for secure, durable terminations. Benefit: Faster commissioning, reliable connections, and lower field maintenance costs. Application: Main distribution boards in industrial facilities where space is at a premium. Feature → Business Impact → Application: Rated current of 25 A with a setting range of 17.5–25 A enables accurate protection tailored to load profiles, reducing nuisance trips and enabling precise coordination with upstream devices. Benefit: Improved uptime and optimized protection coordination for motors and transformers. Application: Motor control centers and transformer feeders. Feature → Business Impact → Application: TM release with a Tmax XT1 mechanical and thermal protection scheme, including a 30 ms opening time, ensures fast fault isolation while minimizing arc energy and stress on conductors. Benefit: Enhanced personnel safety and reduced thermal stress on downstream equipment. Application: Critical protection points in high-density switchgear. Feature → Business Impact → Application: High short‑circuit capabilities with Ics and Icu ratings up to 40 kA (AC) and 25 kA (DC variants), plus an 8 kV impulse withstand voltage, support reliable fault clearance across voltage ranges. Benefit: Superior fault tolerance and system resilience in industrial plants. Application: Substations, data centers, and heavy machinery lines requiring strong short‑circuit protection. Feature → Business Impact → Application: Rated insulation voltage 800 V and rated operational voltage up to 690 V AC / 500 V DC align with common European and international electrical standards, enabling broad compatibility. Benefit: Reduced component footprint and streamlined procurement. Application: Mixed-voltage distribution networks. Feature → Business Impact → Application: Front terminal design with bolt-type terminals and 45.5–80 mm² busbar capacity supports easy retrofit and upgrade in existing switchgear without extensive rewiring. Benefit: Lower installation costs and quicker system modernization. Application: Refurbishment projects and modular plant expansions. Feature → Business Impact → Application: Comprehensive documentation and standards conformance, including IEC60947-2 and a suite of certificates, facilitate compliance audits and plant certification processes. Benefit: Smoother regulatory approvals and reduced compliance risk. Application: Automotive, process, and energy facilities seeking verifiable conformance. Feature → Business Impact → Application: Low power loss of 2 W per pole under rated conditions reduces heat generation and energy waste while extending device life. Benefit: Energy efficiency and cooler switchgear enclosures. Application: Continuous operation environments with tight thermal budgets.
Get a Quick Quote for a ABB 1SDA067391R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067391R1?
Enquire Now
FAQs
This MCCB uses front bolt terminals and supports busbars from 45.5 to 80 mm². Tightening torque is 6 N·m, and the unit is designed for quick, secure mounting in standard 3‑phase switchgear. Verify clearance for 130 mm height and 76.2 mm width per net dimensions, then follow the XT1 installation instructions to ensure correct orientation and wiring.
Key specs include 25 A rated current with a 17.5–25 A setting range, 690 V rated operational voltage, 800 V rated insulation voltage, 8 kV impulse withstand, Icu up to 40 kA, and Ics up to 25–40 kA depending on voltage. It also features a 30 ms opening time and a power loss of 2 W per pole, supporting efficient protection with predictable response.
Yes. The 1SDA067391R1 is designed for low‑voltage transformer protection and general power distribution in industrial settings. Its XT1 family architecture, front-terminal design, and 690 V capability make it suitable for feeders to transformers, switchgear sections, and IT/comms rooms requiring reliable fault isolation and short‑circuit protection with documented installation practices.
The Tmax XT1 MCCB carries EC Declaration of Conformity (CE), GL certificate, and LR certificate, supporting regulatory compliance and cross-border use. Additional compliance is reflected in RoHS and REACH declarations, along with SCIP-related documentation for material and end-of-life considerations in line with industry standards.
The device offers predictable mechanical durability (up to 25,000 cycles) and electrical durability (up to 8,000 cycles at 120 cycles/hour), combined with efficient 2 W per pole loss. Front-terminal wiring reduces field labor, while standardized documentation and compatibility with Tmax XT ecosystems simplify maintenance, training, and lifecycle planning, delivering lower total cost of ownership.