ABB 1SDA067392R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067392R1
Quick Summary
ABB 1SDA067392R1 Moulded Case Circuit Breaker protects electrical distribution networks at 690 V in industrial plants. Engineers often battle nuisance trips and wiring complexity, and this XT1 3P unit delivers precise thermal-magnetic protection with front-terminal access for quick, reliable installation. Certified to CE, GL, and LR requirements, it supports regulatory compliance across global sites and customer audits. Designed for lifecycle efficiency, it reduces maintenance downtime and helps lower total cost of ownership while integrating with SACE Tmax XT systems. Its setting range and fault-current capabilities provide selective protection for transformers and medium-sized distribution panels, delivering measurable ROI through reliability and reduced maintenance.
Product Information
Extended Description
1SDA067392R1 ABB: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
4e599235-d926-4615-a71c-1de7040d6726 Italy (IT)
Simplified SCIP
77fcc699-7c06-40f6-9ee3-735c153c6dcd Germany (DE) | 3fa2a954-0ff2-424c-8c38-69cffccb7e71 Poland (PL) | 016eb8d1-70d2-428e-8610-6b17e417e722 Bulgaria (BG) | 0515a311-cda7-4cb2-a92b-07e795ccb927 Sweden (SE) | c41feba3-dcbe-4ff6-aa7d-3c65f17f6527 Spain (ES) | e4a49827-b15d-4bf7-b12a-d07f41d3c670 Belgium (BE) | 375df1ca-6156-42c0-8276-cf8d061e29e5 Germany (DE) | 7de2ae1c-0dc5-4e4d-afbf-4dc18e4510dd Poland (PL) | 8af8e392-4e25-48bf-a038-1c261e0fdbfe Norway (NO) | 02595f39-f557-4a1a-869d-d447af948a58 Finland (FI) | 7eade347-a4c7-4ae5-8109-1427d50ed287 Belgium (BE) | 2fe2bc3e-fc12-446b-b7fe-318b44a1054a Denmark (DK) | 87a04bcd-f6f5-4ded-86b8-93f3056d19e6 Greece (GR) | 29ad1ea9-b920-490a-b737-100152dc7a18 Estonia (EE) | 71d6aef1-f628-456a-a211-3e53829c15c8 Portugal (PT) | 738ae6df-0753-4c0c-b1ed-075d6de5b990 Germany (DE) | 8a780108-c8dd-441d-ae51-4bef2592234b Croatia (HR) | 90390158-17bd-4b8b-b09e-df85907f43c6 Czech Republic (CZ) | 2ae1704b-4034-423f-af47-5dc82d06826d Germany (DE) | cb447a4b-0808-4c35-96bd-9c0adb63c697 Hungary (HU) | fe90101c-9836-42b3-97a7-974d84e65396 Germany (DE) | 611f72f5-49de-432e-ad9c-2760a05032de France (FR) | 8d2b95c3-158d-4a08-a7f9-296f71ae1a45 Sweden (SE) | 8087afeb-1934-4ed7-be66-48018a2e3f11 Netherlands (NL) | 56c61503-9112-4d77-9173-d119116e6188 Poland (PL) | 8ee92488-322f-4cc1-b31b-c49e4cd8e124 Hungary (HU)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE3032AFF000XXX
E-Number (Finland)
3638774
E-Number (Norway)
4309612
EAN
8015644695187
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.12 kg
Package Level 1 EAN
8015644695187
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.1 W
Rated Current (In)
32 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
22.4...32 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application:Front-terminal design allows fast wiring and modern installation practices, reducing installation time by minutes per unit and lowering field labor costs in panel upgrades or new builds. This translates to faster project delivery and reduced downtime during commissioning in petrochemical, water treatment, and manufacturing facilities. Feature → Business Impact → Application:3-pole XT1 configuration delivers coordinated protection across three phases, improving system stability when powering motors or transformers and minimizing unplanned outages in continuous-process environments. Feature → Business Impact → Application:Thermomagnetic release (TMD) with setting range 22.4–32 A provides reliable, overcurrent protection with selectable tripping, supporting selective coordination in feeders and sub-panels. Feature → Business Impact → Application:IEC60947-2 compliant design ensures global compatibility and easier audits, reducing design risk and accelerating procurement for international sites. Feature → Business Impact → Application:Front-terminal, bolt-type connections plus 6 N·m tightening torque enable secure, vibration-resistant terminations, improving long-term reliability in harsh industrial environments. Feature → Business Impact → Application:High Icu and Ics ratings (up to 40 kA at multiple voltages) support safe interruption of faults in distribution networks and transformers, reducing arc-flash exposure and equipment damage. Feature → Business Impact → Application:Compact 76.2 mm width and 130 mm height enable efficient panel real estate usage while maintaining robust protection, supporting slimline switchgear designs. Feature → Business Impact → Application:Disassembly and end-of-life guidance (Tmax XTXT1) facilitate sustainable recycling programs and compliant lifecycle management. Feature → Business Impact → Application:RoHS and REACH declarations plus SCIP entries help meet environmental and corporate social responsibility targets across global supply chains.
Get a Quick Quote for a ABB 1SDA067392R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067392R1?
Enquire Now
FAQs
The XT1 3P unit uses front-mounted bolt terminals designed for busbar connections. It requires 6 N·m tightening torque and supports busbar cross-sections from 45.5 mm² to 80 mm². The unit features front-terminal access for easy wiring during installation or panel upgrades, reducing field wiring time and potential assembly errors.
Rated current is 32 A with a rated operational voltage of 690 V (AC) / 500 V (DC). It supports an insulation voltage of 800 V and fault-current performance up to 40 kA Icu, with 40 kA Ics across several voltage points. It includes a 22.4–32 A adjustment range and a release type TM with thermal-magnetic protection.
Yes. It is designed for protection in power distribution and transformer-related applications, offering three-pole protection with adequate breaking capacity and coordination. Its ETC and ETIM references identify it as a power circuit-breaker for trafo/generator protection, making it suitable for transformer circuits in industrial installations.
It conforms to IEC60947-2 and carries CE conformity with an EC Declaration of Conformity. Additional certifications include GL and LR certificates for Tmax XT, along with SCIP entries and environmental declarations, supporting regulatory and sustainability audits in multinational operations.
With 8000 cycles electrical and 25000 cycles mechanical durability, the XT1 unit is designed for longevity in frequent switching environments. Front-terminals simplify replacement or upgrade workflows, and ABB disassembly guidance supports end-of-life recycling, reducing lifecycle cost and improving total cost of ownership for maintenance teams.