ABB 1SDA067393R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067393R1
Quick Summary
Moulded case circuit breaker ABB 1SDA067393R1 protects industrial power distribution by interrupting fault currents in MCC installations. In busy facilities, nuisance trips and poor coordination drive downtime, maintenance costs, and risk to downstream equipment. This unit carries CE conformity under the EC Declaration of Conformity for Tmax XT1, adheres to IEC 60947-2, and is supported by environmental declarations (EPD) for Tmax XT XT1 IT and CN. Designed for seamless integration with SACE Tmax XT systems, featuring front terminals and a fixed 3P XT1 format, enabling faster wiring, safer maintenance, and lifecycle-cost advantages for electrical distribution. By aligning with RoHS and REACH, it supports sustainable, compliant plant operation and easier end-of-life planning.
Product Information
Extended Description
1SDA067393R1 ABB: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 40-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
8a91ff6a-ad35-4fb5-a92a-df6404a582cb Italy (IT)
Simplified SCIP
ff22bf26-0f34-41ea-99ef-86eed6814bc5 Germany (DE) | 52ef1d57-7ac3-4b6f-a7e4-e82a028ffb83 Netherlands (NL) | 74d485f3-103e-4d7a-8443-1f7ad4022261 Netherlands (NL) | f4830c59-0293-41c0-b6c6-bbc224ef389e Germany (DE) | 75045930-dcf8-4bdf-a8a6-b1d7536722b0 Denmark (DK) | 00d5e05b-73de-4ffd-ada4-75fe59753d1b Germany (DE) | a3bb56c5-c825-461f-b74a-af460f0a46b3 Croatia (HR) | 511b521b-ee85-4c5d-bc0a-7a79e53ee659 Czech Republic (CZ) | 6c056f27-91fa-4473-854f-037e49936562 Netherlands (NL) | 4019c24c-8691-4202-9180-e5d03adce627 Netherlands (NL) | 48db9e10-b526-4ac0-aae6-d10ceea229d1 Estonia (EE) | ba95b5e4-99d5-4eea-b2c9-cb155dd74fa9 Greece (GR) | c445fb07-7d15-41b6-a68d-cdb076abe0f1 Portugal (PT) | 2bbe0591-3502-4ecc-b98b-6a391f7c3659 Bulgaria (BG) | eb299f83-c903-4a3c-b98c-1d1fc6bbcadb Sweden (SE) | 6abe2cd0-f062-4d83-9004-c331378e8e51 Poland (PL) | e62cb378-2733-4350-aa9c-3b6ed41c578f France (FR) | 30e1b010-9328-4a58-8902-080379a87c23 Sweden (SE) | be0d0faf-5974-449f-b370-495cba09cb01 Germany (DE) | 9140d5d7-7c67-405b-bf7e-5475de634beb Germany (DE) | 23f70161-83b5-42b7-b046-4553eb6db904 Spain (ES) | 7cce477e-45c8-445e-9a44-47829e0653e7 Netherlands (NL) | d5142b24-b2c5-442e-92f1-34be6bf004b6 Poland (PL) | 0da3aafb-d5a7-44a0-866d-3774ab59123e Poland (PL) | 9d65d086-3f78-4165-b15a-c20f5c9a033b Finland (FI) | 167b4a8a-f6f6-4ac1-b303-632a0bd3431b Norway (NO) | 3b58e72f-8f59-4998-b549-8ee112e84c38 France (FR)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE3040AFF000XXX
E-Number (Finland)
3638775
E-Number (Norway)
4309613
EAN
8015644012175
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.12 kg
Package Level 1 EAN
8015644012175
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.6 W
Rated Current (In)
40 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
28...40 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal, 3P XT1 fixed design; Business Impact: Simplifies wiring, reduces installation time, and enhances safety during maintenance; Application: Ideal for compact MCC feeds and switchgear panels. Feature: Thermomagnetic release (TMD) with setting range 28–40 A; Business Impact: Improves selective protection and reduces nuisance trips, lowering downtime and service costs; Application: Coordinated protection for motor loads and feeders. Feature: Rated current 40 A at 690 V with Icu up to 40 kA; Business Impact: Strong fault-current interruption supports downstream equipment protection and system reliability; Application: Industrial power distribution with high fault levels. Feature: Mechanical durability up to 25,000 cycles and electrical durability up to 8,000 cycles; Business Impact: Longer service life and reduced maintenance intervals; Application: Frequent operation environments such as manufacturing lines. Feature: Front connection terminals with 6 N·m tightening torque; Business Impact: Easier installation and secure terminations, reducing reworks; Application: Quick-wiring in new builds or retrofit projects. Feature: RoHS/REACH compliance and EPD availability; Business Impact: Ensures regulatory alignment and sustainability reporting; Application: Plant-wide compliance programs and green procurement.
Get a Quick Quote for a ABB 1SDA067393R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067393R1?
Enquire Now
FAQs
This unit uses front terminals for convenient wiring and requires a tightening torque of 6 N·m on bolt terminals. It supports 76.2 mm width, 130 mm height, and 70 mm depth, with a weight of 1.1 kg. Minimum order is 1 piece, and the recommended screwdriver is M6 for main circuit connections. Plan for a 3P configuration and ensure adequate clearance per panel standards.
Rated current is 40 A, rated voltage 690 V, insulation voltage 800 V, and operating voltage 690 V. Short-circuit capabilities include Icu up to 40 kA and Ics up to 25–40 kA depending on voltage. Release is TMD with a setting range of 28–40 A, and the device conforms to IEC 60947-2 standards for low-voltage power circuit-breakers.
Yes. It carries CE conformity via EC Declaration of Conformity for Tmax XT1 and adheres to IEC 60947-2. Additional compliance is supported by RoHS/REACH declarations and EPD documentation, reinforcing material and environmental performance for modern electrical installations.
Best suited for MCC protection in switchgear and power distribution panels, especially where 3P feeds, front-terminal wiring, and 690 V systems are used. It integrates with SACE Tmax XT ecosystems, enabling reliable protection for motors and feeders while supporting fast commissioning and straightforward maintenance in manufacturing, process plants, and utility spaces.
Electrical durability is rated at 8,000 cycles and mechanical durability at 25,000 cycles, indicating long service life under typical load conditions. End-of-life considerations follow disassembly guidance and packaging disposal information. RoHS/REACH compliance and EPD data assist in regulatory reporting and support sustainable maintenance planning.