ABB 1SDA067396R1 Moulded Case Breaker - IEC60947-2
Part Number: 1SDA067396R1
Quick Summary
Moulded Case Circuit Breaker protects industrial power distribution and equipment in control panels and switchgear. Engineers often grapple with unexpected trips and downtime on high-demand manufacturing lines. This model meets IEC 60947-2, CE conformity, and UL recognition for safe, compliant integration. With 690 V rating and 80 A nominal current, it delivers reliable protection while minimizing maintenance. Environmental benefits include a design for closing resource loops with a 55.9% recyclability rate and documented EPDs. Installation is straightforward thanks to front-terminal access and universal busbar compatibility. Users gain lifecycle cost savings through longer service intervals and reduced downtime. Rated at 80 A and 3P configuration, it aligns with Tmax XT family for modular protection schemes.
Product Information
Extended Description
1SDA067396R1 ABB: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 80-800 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
62bbce4d-080f-4d86-9d81-b900472c629b Italy (IT)
Simplified SCIP
479f51fc-294e-4dd6-895e-e829ac0b81e1 Poland (PL) | 55b895cf-afa9-4baa-9ab8-1a4e51392550 France (FR) | 2ff5a69b-4b7b-4aa0-aaca-580fc33c244a Sweden (SE) | c6d4ab2c-2876-4862-a074-95b19ec7a5db Germany (DE) | 0564b919-5fdc-4fac-83de-b868b1cf479a Hungary (HU) | 30e03275-97e9-43fd-950a-c41477e4f724 Hungary (HU) | 3f2635c8-8b68-4411-83d9-38c9ab429218 Germany (DE) | b059d5cc-c10c-470b-b91a-8c5fba296910 Poland (PL) | 352d50a8-6362-4006-aab7-149019f3a151 Netherlands (NL) | ddd923fd-da41-4ae8-91dc-fc97e42eee32 Bulgaria (BG) | 9afe4ace-6b6c-49ee-9880-5a365d758903 Belgium (BE) | 752d4914-a434-422a-bf45-6467cc38fa93 Spain (ES) | a1bdc34a-9ba6-4c5a-8124-e25737c8623e Sweden (SE) | 59c45024-6b55-426e-939d-feef3baa0f33 Poland (PL) | 76b7bfaf-8556-461f-9862-8cef9d327ecc Norway (NO) | 99ecf823-5fdb-4e14-abf2-810261830484 Finland (FI) | 7385ef91-2bd9-48a2-8c37-7dd4b14991c9 Belgium (BE) | d34e8069-d92d-4d9f-bce5-dfbd55f31e6d Germany (DE) | f93d3bb5-6874-4bfb-bc53-7426f177f77d Greece (GR) | 264b5eaa-e9ff-4830-b97e-bc7991ec2f8c Portugal (PT) | abf903d0-ee30-4afb-bf25-aff4181635e9 Germany (DE) | 6ac49de9-8f8e-476d-816d-1483a6ffa760 Croatia (HR) | 0acc9fa6-ca0e-4ffb-b2ca-63b2beae6d3f Czech Republic (CZ) | 3e3ac273-7275-4ca1-b62e-88cce695e24b Germany (DE) | 34880d7b-26c8-439a-b0c3-541a658baddc Estonia (EE) | eb832ab9-ab8e-4a4f-8384-e601ee2473be Denmark (DK)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE3080AFF000XXX
E-Number (Finland)
3638627
E-Number (Norway)
4309616
EAN
8015644695200
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.133 kg
Package Level 1 EAN
8015644695200
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.8 W
Rated Current (In)
80 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
800 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
56...80 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Three-pole XT1 design provides robust protection for 690 V networks, enabling selective interruption during faults and reducing collateral downtime in heavy machinery. This translates to improved line uptime and safer maintenance windows for machine builders and plant engineers. Application: ideal for switchgear and control panels in manufacturing lines needing reliable 3P protection. Feature → Business Impact → Application: Front-terminal, bolt-type connections and 6 N·m tightening torque simplify installation and ensure secure busbar contact, cutting commissioning time and minimizing initialization errors. Application: quick retrofit into existing Tmax XT and similar ecosystem equipment. Feature → Business Impact → Application: Adjustable setting range of 56–80 A supports precise coordination with downstream protection devices, improving selectivity and reducing nuisance trips. Application: configurable protection in evolving line layouts and new equipment integrations. Feature → Business Impact → Application: High short-circuit performance with Ics up to 40 kA and Icu up to 40 kA (depending on voltage) delivers dependable fault clearance for critical loads. Application: protection of motors, transformers, and power distribution networks. Feature → Business Impact → Application: Front-terminal accessibility and compatibility with 45.5–80 mm² conductors streamline installation and maintenance. Application: service in confined spaces, retrofit projects, and modular panel builders. Feature → Business Impact → Application: Environmental and compliance features including EPDs, EN45555 recyclability rating (55.9%), RoHS/REACH, and SCIP CMRT support sustainable procurement and regulatory alignment. Application: data-driven sustainability programs and responsible supply chain decisions.
Get a Quick Quote for a ABB 1SDA067396R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067396R1?
Enquire Now
FAQs
Ensure supply is de‑energized, verify conductor cross‑section supports 45.5–80 mm², and use a main circuit screwdriver (M6) to tighten the front terminal bolts to 6 N·m. Align the unit with the panel cutout, secure mounting, and connect the busbar per the included wiring diagram. Front terminals simplify replacement and future upgrades, reducing commissioning time.
The XT1 model provides high short-circuit capacity with Ics up to 40 kA and Icu up to 40 kA, depending on voltage. This supports demanding load profiles found in motors and transformers, ensuring rapid fault clearance without sacrificing system stability. Always verify the exact ratings for your voltage point in the datasheet to confirm coordination with downstream protections.
Yes. The product carries CE conformity with an EC Declaration of Conformity for Tmax XT1 and complies with IEC 60947‑2 standards. RoHS/REACH declarations and a valid environmental profile (EPD) further support regulatory compliance and responsible sourcing in European projects and energy‑efficient design programs.
The XT1 sub‑type uses standardized three‑pole front‑terminal construction, same mounting footprint, and wiring diagrams that align with Tmax XT products. This enables straightforward upgrades, modular protection schemes, and consistent maintenance practices across the Tmax XT family, reducing spare parts inventory and training needs.
Electrical durability is rated for up to 8000 cycles per hour at 120 cycles/hour, with mechanical durability up to 25,000 cycles. The unit supports straightforward inspection and front-terminal replacement, reducing downtime during service. Recyclability is designed into the product (55.9% per EN45555), supporting sustainability goals and long‑term lifecycle cost reductions.