ABB 1SDA067397R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067397R1
Manufacturer
ABB
Part number
1SDA067397R1

Quick Summary

Moulded Case Circuit Breaker ABB 1SDA067397R1 provides reliable overcurrent protection for distribution panels in industrial environments. Engineers often confront wiring complexity and slow fault isolation when expanding power distribution networks, making installation efficiency and rapid fault clearance critical. Key certifications include CE conformity (EC Declaration of Conformity Tmax XT1), GL certificate, and LR certificate, which validate safety and reliability in demanding applications. As part of ABB's SACE Tmax XT family, it supports IEC60947-2 compliance and a robust front-terminal design that speeds commissioning and reduces wiring time. The compact footprint, accompanied by documented environmental and end-of-life data, helps drive lower lifecycle costs. In practice, these attributes translate to less downtime, easier maintenance, and improved system reliability for critical equipment protection.

Product Information

Extended Description

1SDA067397R1 ABB: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
9965ca99-affa-4173-b6ec-86c5b94f7e15 Italy (IT)
Simplified SCIP
0baf7834-5c1e-4ab6-92f8-fe1c0c18d111 Germany (DE) | 690bbaca-e914-49b1-b061-fadc8cb41754 Netherlands (NL) | 1d9c93da-ce2a-496b-963a-5aa10a5952ea Netherlands (NL) | faccd3ac-7bd6-452b-b339-f3e8650b7ed7 Germany (DE) | 3971316a-abb7-4fb7-a3a4-b645aa241259 Denmark (DK) | adf816cc-8afa-408f-b37f-84d38645b9ce Germany (DE) | f57e9c1b-e394-43c6-92b6-24992fec4513 Croatia (HR) | a23327a4-9935-4203-a9d5-741ba39df896 Czech Republic (CZ) | b8b0676f-7b3e-4d5c-aa3c-7b6ebfe5bc3e Netherlands (NL) | 678300f8-ecd0-4b74-8804-18f219da3ae0 Netherlands (NL) | 2d166b04-bfde-406d-ae1b-a2d4f9a45c1f Estonia (EE) | 769c0bf8-bb50-4b05-90d1-f148493e2e93 Greece (GR) | c222885d-c4e3-48f8-aa94-67f29ec03c2e Portugal (PT) | 0fa0c29c-f77e-4742-bd29-9f67a5dd58e7 Bulgaria (BG) | 3a1ec757-f5bc-4fe2-a796-b80d5848b865 Sweden (SE) | 3380a59b-f15a-4f8b-8fe2-54d228c70377 Poland (PL) | 25e84eae-96f0-42ce-9d7d-9dfb5f5ce2a5 France (FR) | dafbc307-d434-4abc-8c03-c64d3fc1c333 Sweden (SE) | 3b414454-d89f-4090-bb59-470a3c7330ea Germany (DE) | 59695450-664d-4372-9510-6f5c4ac5ad03 Germany (DE) | 35ec2353-58cd-472a-b909-85aa064a6204 Spain (ES) | 95a1642c-9a73-4d2e-8a1b-c20ad5fc8a6c Netherlands (NL) | 5ec14cea-f544-4faa-ab16-fd3819a27732 Poland (PL) | ca56bfe2-177d-4ed2-a416-d34db5ca5989 Poland (PL) | 37ce67d3-3a1a-4ca0-b8ae-7bf5eec07bd9 Finland (FI) | 3f937e08-97bb-4c73-ac98-fbbab57d1a84 Norway (NO) | b394e0ce-ed58-41d4-9e52-9fc27c75e4e8 France (FR)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE3100AFF000XXX
E-Number (Finland)
3638777
E-Number (Norway)
4309617
EAN
8015644012915
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.136 kg
Package Level 1 EAN
8015644012915
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 7 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed front terminals with front-entry wiring and a 70-100 A setting range. Impact: Simplified on-site wiring, faster commissioning, and predictable trip behavior, reducing installation time and commissioning costs. Application: Power distribution panels in manufacturing lines and process plants. Feature: TMD release with fast opening time (30 ms SOR / 30 ms UVR) and rated instantaneous setting of 1000 A. Impact: Rapid fault isolation minimizes arc duration and protects downstream equipment, improving overall line reliability. Application: Control cabinets and machine protection where fast response is required. Feature: Rated Current 100 A, Rated Voltage 690 V (Ui 800 V, Ue 690 V), Icu 40 kA, Ics 40 kA across a range of voltages. Impact: High fault current withstand capability ensures safe operation under diverse grid conditions, supporting 50/60 Hz systems. Application: Large motors, transformers, and distribution feeders. Feature: Busbar connection 45.5–80 mm² and tightening torque 6 N·m. Impact: Secure, vibration-resistant connections with easy torque verification, reducing maintenance rework. Application: Main circuits in panelboards and switchgear. Feature: Compact dimensions (130 x 76.2 x 70 mm) and weight 1.1 kg; front terminals for easier wiring and serviceability. Impact: Denser panel layouts and faster field servicing. Application: Enclosures with space constraints; OEM assemblies. Feature: Environmental and lifecycle data (EPD, recyclability 55.9% per EN45555) plus End Of Life disassembly instructions. Impact: Strong sustainability credentials, easier scrap planning, and compliant disposal. Application: Green-rated projects and corporate sustainability reporting.

Get a Quick Quote for a ABB 1SDA067397R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067397R1? Enquire Now

FAQs

The XT1 uses front terminals compatible with busbars in the 45.5–80 mm² range. Tighten all terminals to 6 N·m using a standard M6 screwdriver, ensuring clean, straight connections for reliable current paths and easy maintenance. Verify the front-entry wiring path to minimize bending and ensure accessibility for future servicing.
Rated current is 100 A, rated voltage is 690 V (Ui 800 V, Ue 690 V), Icu and Ics are both 40 kA, and the device supports 50/60 Hz. The setting range is 70–100 A, with instantaneous trip at 1000 A. These specs support reliable protection across a broad range of industrial loads.
Yes. The device is designed to meet IEC 60947-2 requirements as part of the Tmax XT family, with documented installation instructions, wiring diagrams, and conformity documentation (EC Declaration of Conformity). It’s ideal for distribution panels where standard compliance and predictable performance matter.
Certified with CE conformity (EC Declaration of Conformity Tmax XT1), plus third-party validation such as GL and LR certificates. Environmental data includes an EPD for Tmax XT XT1 and a recyclability rate of 55.9% per EN45555, along with end-of-life disassembly instructions to support sustainable disposal.
Front terminals and a compact design simplify initial wiring and future servicing, reducing downtime. With a 7 W per pole power loss and clear torque specs of 6 N·m, routine checks are straightforward. Lifecycle data like EPD and disassembly guidance support responsible end-of-life planning and long-term cost containment.