ABB 1SDA067401R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067401R1
Quick Summary
ABB 1SDA067401R1 Moulded Case Circuit Breaker provides four-pole electrical protection for power distribution in industrial facilities. This model helps mitigate downtime caused by undersized or poorly coordinated protection devices, delivering reliable disconnection during faults. It complies with IEC 60947-2 and CE declarations, and carries GL and LR certifications for traceability and safety. By combining front-terminal accessibility with a compact XT1 footprint, it simplifies installation and maintenance while supporting scalable protection within SACE Tmax XT ecosystems. The result is improved panel reliability, easier field servicing, and a clear path to regulatory compliance in demanding environments.
Product Information
Extended Description
1SDA067401R1 ABB: C.BREAKER TMAX XT1C 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1CE4032AFF000XXX
E-Number (Finland)
3640515
E-Number (Norway)
4309712
EAN
8015644012953
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.426 kg
Package Level 1 EAN
8015644012953
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.1 W
Rated Current (In)
32 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
22.4...32 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 4P fixed front-terminal design. Business Impact: Streamlines wiring and reduces installation time, cutting labor costs and panel footprint. Application: Ideal for compact distribution boards and machine complete power feeds. Feature: 32 A rated current and 690 V rated operational voltage with Ui 800 V. Business Impact: Provides robust protection for motor feeders and transformers while sustaining high-performance insulation margins. Application: Suitable for industrial control panels and transformer feeders. Feature: Release type TMD with setting range 22.4–32 A. Business Impact: Enables precise coordination and selective tripping, minimizing disruption. Application: System protection in multi-device cascades where selective discrimination is critical. Feature: High short-circuit ratings (Ics up to 40 kA at low voltages; 25 kA at mid-voltage; 4 kA at 690 V). Business Impact: Enhances safety margins and reduces repair costs after faults. Application: Protection in networks with varying fault currents across voltage levels. Feature: Front terminal connection and tightening torque of 6 N·m with busbar compatibility (45.5–80 mm²). Business Impact: Delivers secure, vibration-resistant connections and quick field installation. Application: Power distribution panels and equipment with heavy-duty conductor runs. Feature: Compact dimensions and weight (101.6 mm W, 130 mm H, 70 mm D; 1.4 kg). Business Impact: Easier rack integration and reduced enclosure space, enabling tighter layouts. Application: Modern control cabinets and panel builders seeking efficiency and space optimization. Feature: Compatibility with SACE Tmax XT family and availability of manufacturer documentation (installation instructions, drawings, and wiring diagrams). Business Impact: Ensures streamlined engineering workflows, faster commissioning, and consistent spare-part strategy. Application: OEM machines, energy installations, and retrofits requiring integrated protection.
Get a Quick Quote for a ABB 1SDA067401R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067401R1?
Enquire Now
FAQs
This unit uses front-terminal connections and requires a 6 N·m tightening torque. Plan for a conductor range of 45.5–80 mm² per pole and ensure the space for a 101.6 mm wide, 130 mm high, 70 mm deep module. It’s designed for easy slide-in mounting in standard 4P MCCB slots and accepts M6 screwdriver for main circuit connections.
Key ratings include 32 A rated current, 690 V rated voltage, Ui 800 V insulation, and Ii 450 A instantaneous setting. Ics up to 40 kA at low voltages (230–240 V), 25 kA at 380–440 V, and 4 kA at 690 V, enabling reliable protection across common industrial scenarios while maintaining selective coordination.
Yes. The XT1C 4P design with front terminals and 32 A rating is appropriate for transformer feeder protection. It aligns with IEC 60947-2 requirements, supports high short-circuit withstand, and integrates with SACE Tmax XT ecosystems for consistent coordination and lifecycle management.
The product carries a CE Declaration of Conformity for regulatory alignment. Additional traceability is supported by GL Certificate 1SDL000163R0103 and LR Certificate for Tmax XT. These credentials aid in audit readiness and supplier qualification within regulated environments.
Front-terminal design simplifies wiring and reduces commissioning time, while the robust 4P XT1C construction supports long service life in demanding environments. Its compact size helps save panel space, and its high Ics/Icu ratings minimize replacement frequency, contributing to lower downtime and total cost of ownership.