ABB SACE Tmax XT is a moulded case circuit breaker for three‑phase power distribution in industrial installations. Engineers often face downtime and maintenance hassles when protection devices are hard to access or misconfigured; the XT1N variant with front terminals and a fixed setting range helps reduce wiring errors and service time. This family carries strong certifications: IEC60947-2 compliant, CE declaration of conformity, and credible third‑party approvals such as GL and LR certificates, along with environmental declarations (EPD) and recyclability data. By pairing precise thermal magnetic release with a compact, front‑terminal footprint, the XT1 supports safe, fast installation, easier testing, and lower total cost of ownership across panel builders, machine builders, and data centers.

Product Information

Extended Description

1SDA067413R1 ABB: C.BREAKER TMAX XT1N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 50-500 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1NE3050AFF000XXX
E-Number (Finland)
3640529
E-Number (Norway)
4379205
E-Number (Sweden)
3182432
EAN
8015644013073
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.134 kg
Package Level 1 EAN
8015644013073
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.7 W
Rated Current (In)
50 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA | (230 V AC) 50 kA | (240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 18 kA | (500 V AC) 15 kA | (525 V AC) 11 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA | (230 V AC) 65 kA | (240 V AC) 65 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 36 kA | (500 V AC) 30 kA | (525 V AC) 22 kA | (690 V AC) 6 kA | (250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
35...50 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → ApplicationThe XT1 model uses a 3P configuration with front terminals and bolt terminals, enabling straightforward, secure wiring and faster panel assembly, reducing commissioning time for motor control centers and distribution boards. This translates to lower labor costs and improved reliability in machine shops and processing plants.Feature → High short-circuit protection ratings (Ics up to 50 kA, Icu up to 65 kA at multiple voltages) → Enhanced safety and uptime by delivering robust fault interruption without nuisance trips in high-demand environments. Application spans transformers, UPS rooms, and data centers where fault levels vary.Feature → Adjustable setting range 35–50 A and fixed current rating of 50 A → Operators can tailor protection to load profiles, improving selectivity and safeguarding critical equipment, from assembly lines to cooling systems.Feature → Front-access design and 6 N·m tightening torque with bolt terminals → Safer maintenance and easier retrofits in tight enclosures; applicable to upgrade projects in legacy panels and retrofit programs.Feature → Comprehensive compliance and environmental data (IEC60947-2, CE, EPD, EN45555 recyclability) → Confidence for specifiers and procurement teams seeking sustainable, regulation‑driven solutions for Medical/industrial, robotics, and energy infrastructure.

Get a Quick Quote for a ABB 1SDA067413R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067413R1? Enquire Now

FAQs

The XT1 3P fronts terminals design provides bolt-type connections on the front, enabling quick, accessible wiring and secure mounting within standard panel spaces. This simplifies installation in control panels, machine enclosures, and distribution boards while reducing wiring congestion and maintenance time.
Rated current is 50 A with a setting range of 35–50 A. Rated voltage is 690 V, with standalone and series short-circuit performance: Ics up to 50 kA and Icu up to 65 kA depending on voltage, ensuring robust fault interruption across common industrial voltages.
Yes. It adheres to IEC 60947-2, provides thermal-magnetic release (TMD) protections, and offers reliable short-circuit protection for low-voltage circuits. It is CE certified and carries GL/LR approvals, supporting compliance in global manufacturing and installation projects.
Plan for front-access wiring, ensure correct busbar sizing (45.5–80 mm²), and tighten terminals to 6 N·m. The front-terminal design enables safer servicing in tight enclosures and simplifies retrofits in existing panels, reducing downtime during upgrades.
The product includes a CE Declaration of Conformity, GL and LR certificates, and environmental data, including EPDs and recyclability calculations per EN45555. Additional information includes CMRT for conflict minerals and RoHS declarations, supporting responsible procurement and regulatory compliance.