ABB 1SDA067444R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067444R1
Quick Summary
Moulded Case Circuit Breaker is a protective device that interrupts fault currents and overloads in industrial power distribution. Engineers face space constraints, complex wiring, and challenging maintenance scheduling; this XT1S unit minimizes panel footprint with front terminals. Key certifications include CE conformity with the EC Declaration of Conformity, IEC 60947-2 compliance, and third‑party approvals such as GL and LR. Designed for reliability and lifecycle efficiency, it supports sustainability goals through recyclability (55.9% per EN45555) and an Environmental Product Declaration (EPD). For integrators, the product aligns with ABB EcoSolutions, offering documented end‑of‑life guidance, RoHS/REACH compliance, and straightforward installation that reduces downtime and total cost of ownership.
Product Information
Extended Description
1SDA067444R1 ABB: C.BREAKER TMAX XT1S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A NEUTRAL = 50% PHASES
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
faa8fc84-a76f-46a6-8b1f-d1e2dcfe417d Italy (IT)
Simplified SCIP
be0f0c2a-5718-4b2b-8d1c-1e3e63ee561d Belgium (BE) | 9865a77f-d19b-426a-b9e5-1987fef7e4a9 Spain (ES) | 6739099c-6886-499d-9327-a4fa93994027 France (FR) | 08892a03-c565-4d2c-bacc-a65c6fb1ad76 Sweden (SE) | 15ccdd6b-d01c-48d0-a49a-6acf9d82a492 Germany (DE) | 154a4afd-4544-45ec-90e2-d0a9676c86af Croatia (HR) | 992eb9be-d2f7-43e2-b7da-749e086d8c99 Germany (DE) | 0d0bd1ef-5056-45a3-bded-6513be937dc1 Germany (DE) | b03637f7-375e-47f0-a7a9-20ca05730c6d Czech Republic (CZ) | ab64c997-15ec-4cec-843d-bf66b65ddaf3 Germany (DE) | 53cab9cb-019b-4279-9b10-800bccc1e5e0 Hungary (HU) | 00ed01a4-6ae5-4350-81f8-f2770ab0d70b Poland (PL) | 276605bb-6771-4fea-a265-fb705db785df Portugal (PT) | 16e4e4ce-063f-4984-9af8-f370d3d7acdf Norway (NO) | 7fb3392d-b0a4-4d6f-ad52-ed50ca895630 Bulgaria (BG) | 59ae4440-55e2-4865-9ed1-8690c55474d2 Poland (PL) | 7d484c39-1e90-48cf-aaab-bb748da5c3aa Greece (GR) | e209ab92-227a-483b-b30e-3dbba0a87d57 France (FR) | ad275b77-02ca-4fd9-89cb-7fb209ebe42d Germany (DE) | 89b262a1-e4b9-4ffb-8471-65edaf702881 Estonia (EE) | 6a7a2b71-172b-4e7f-8660-1a5077eb1990 Belgium (BE) | 3a18bbbc-e724-4973-a1df-558e16edff28 Hungary (HU) | 7b773c72-3dd3-47df-b983-50cdd60c4da0 Poland (PL) | b74f71c4-eb58-4d9c-b6ae-d913d8e8f099 Finland (FI) | f7aaa7f7-0823-409f-9fc4-c12094d442c2 Netherlands (NL) | 597a31a8-ce53-45fb-a55b-7de96382fb68 Sweden (SE) | 2fd60748-3800-4579-b7ba-fa247360a931 Denmark (DK)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SEN160AFF000XXX
EAN
8015644013387
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644013387
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1600 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
112...160 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal 4P construction enables safe, compact installation in control panels. Business Impact: Reduces wiring complexity and panel depth while speeding assembly and serviceability in tight spaces. Application: Machine controls and panel boards where space is at a premium. Feature: Rated current 160 A with a 112–160 A setting range and TM release. Business Impact: Provides tuned protection with fast interruption for overloads and short circuits, improving uptime and system reliability. Application: Power distribution in manufacturing lines and transformer protection scenarios. Feature: High short‑circuit performance (Ics up to 80 kA, Ii up to 1600 A) and rated voltage of 690 V. Business Impact: Enhanced safety margins and selectivity for critical loads, reducing catastrophic outages and equipment damage. Application: Medium‑to‑high power distribution networks and critical plant feeders. Feature: Compliance and sustainability features including IEC 60947‑2, CE conformity, RoHS/REACH, and an EPD with recyclability information. Business Impact: Eases regulatory approval, supports green procurement goals, and simplifies end‑of‑life planning. Application: Global rollouts and green‑focused projects in factories and data centers. Feature: Dimensions, weight, and robust front‑terminal bolt connections (Unit: 101.6 mm width, 130 mm height, 70 mm depth; 1.4 kg). Business Impact: Predictable enclosure fit and straightforward logistics, lowering shipping and handling costs. Application: New installs and retrofit projects requiring exact form‑factor compatibility.
Get a Quick Quote for a ABB 1SDA067444R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067444R1?
Enquire Now
FAQs
Install the unit using the front-terminal bolt connections and tighten to 6 N·m for each terminal. Ensure the busbar cross-section is within 45.5 to 80 mm² and verify the 4P arrangement aligns with the mounting footprint (XT1). Use the recommended Main Circuit M6 screwdriver and observe safe‑switching procedures during energization.
The breaker is rated for 160 A (I_n), with a Rated Operational Voltage of 690 V AC / 500 V DC and a Rated Insulation Voltage of 800 V. It supports Ii up to 1600 A and Ics up to 80 kA, enabling protection of medium‑to‑high power circuits in industrial applications and transformer protection scenarios.
Yes. It complies with IEC 60947-2 and carries CE conformity (EC Declaration of Conformity). Additional certifications such as GL and LR are documented, aiding regulatory approvals in multiple regions and simplifying cross‑border deployment.
ABB provides End‑Of‑Life disassembly instructions for Tmax XT XT1 units, an Environmental Product Declaration (EPD) for Tmax XT XT1 (IT/CN), and a recyclability metric of 55.9% per EN45555. These resources support waste‑minimization goals and compliant disposal/recycling programs.
Product net dimensions are 101.6 mm wide, 130 mm high, and 70 mm deep, with a net weight of 1.4 kg. Packaging is a single unit per box, with box dimensions roughly 128 × 135 × 143 mm and the same EAN 8015644013387 for logistics and inventory control.