ABB 1SDA067452R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067452R1
Quick Summary
ABB 1SDA067452R1 Moulded Case Circuit Breaker provides reliable protection for 690 V industrial power distribution. Engineers often contend with nuisance trips and complex wiring when upgrading switchgear. It complies with IEC 60947-2, carries a CE Declaration of Conformity, and respects RoHS and REACH requirements. Built for the SACE Tmax XT family with front-terminal installation and a Thermomagnetic release, it reduces wiring effort and improves service life, delivering safer, more maintainable panels for critical manufacturing, data centers, or process facilities. With a 3-pole design and a 70–100 A setting range, it supports modular protection without overdesign, helping facilities improve uptime and reduce total cost of ownership.
Product Information
Extended Description
1SDA067452R1 ABB: C.BREAKER TMAX XT1H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HE3100AFF000XXX
E-Number (Norway)
4379220
EAN
8015644013462
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.16 kg
Package Level 1 EAN
8015644013462
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 7 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 52.5 kA | (415 V AC) 37.5 kA | (440 V AC) 32.5 kA | (500 V AC) 25 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 52.5 kA | (500 V DC) 3 Poles in Series 52.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 35 kA | (690 V AC) 10 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P XT1 fixed front-terminal design → Business Impact: Simplifies wiring and speeds up panel assembly, reducing installation labor and risk of loose connections. Application: Ideal for distribution boards in factories and data centers. Feature: Front terminal bolt connections with 6 N·m tightening torque → Business Impact: Ensures robust, vibration-resistant terminations in harsh environments, lowering maintenance needs. Application: Motor control centers and switchgear upgrades. Feature: 70–100 A setting range with 100 A rated current → Business Impact: Flexible protection that adapts to load variations without replacing devices, cutting spare parts and downtime costs. Application: Feeder circuits and transformer protection. Feature: Rated voltage 690 V AC and Ui 800 V → Business Impact: Safe operation across standard industrial networks, supporting higher fault tolerance. Application: Large-scale control panels and distribution systems. Feature: Ics up to 52.5 kA and Icu up to 10 kA at 690 V AC → Business Impact: High fault-current protection with selective tripping, reducing equipment damage risk. Application: Systems with heavy inrush or short-circuit scenarios. Feature: 1.1 kg weight and compact dimensions (76.2 mm W x 130 mm H x 70 mm D) → Business Impact: Easier retrofit in confined spaces and more efficient panel layouts. Application: retrofit projects and modular installations. Feature: RoHS/REACH compliance, EPDs, and DoC → Business Impact: Streamlined procurement with full regulatory assurance, supporting sustainable supply chains. Application: Global manufacturing and facilities requiring regulatory alignment. Feature: 3P front-terminals with clear wiring diagram and CB release TMD → Business Impact: Clear maintenance path and quick fault isolation, improving service response times. Application: Control cabinets and protective switching in critical processes.
Get a Quick Quote for a ABB 1SDA067452R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067452R1?
Enquire Now
FAQs
Install the ABB 1SDA067452R1 using its front-terminal bolts on a 3P device rated for 690V. Connect with busbars 45.5–80 mm², tighten to 6 N·m, and use a M6 screwdriver. It supports a 70–100 A setting range and should be wired per the XT1 wiring diagram for reliable panel protection.
Key specs include 100 A rated current, 690 V rated operational voltage (AC) with 500 V DC capability, Ui 800 V, Ics up to 52.5 kA, Icu up to 10 kA at 690 V, 3 poles, front terminal connections, and a tightening torque of 6 N·m. Busbar connection supports 45.5–80 mm².
Yes, the device supports DC operation up to 500 V DC as part of its rated operational range alongside 690 V AC. When designing for DC transmission or DC control circuits, verify continuous current demands and ensure compatibility with the CM wiring diagram and short-circuit requirements.
The product complies with IEC 60947-2 and carries a CE Declaration of Conformity. It aligns with RoHS and REACH requirements, and associated environmental declarations (EPD Tmax XT XT1 IT/CN) and related supplier certifications are available for procurement and regulatory audits.
Maintenance is streamlined by robust front-terminal connections, reducing wiring faults and commissioning time. The unit offers 7 W per pole power loss under rated conditions and a long mechanical/electrical durability profile (up to tens of thousands of cycles), contributing to improved uptime and a lower total cost of ownership over time.