ABB 1SDA067463R1 Moulded Case Circuit Breaker - XT1 4P

Part Number: 1SDA067463R1
Manufacturer
ABB
Part number
1SDA067463R1

Quick Summary

ABB 1SDA067463R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for 690 V distribution panels in industrial power circuits. Front-terminal mounting and a precise 87.5–125 A setting range simplify wiring and commissioning in compact switchgear, reducing startup time and field adjustments. It delivers robust electrical durability with rated current 125 A, Ui 800 V, Ui 690 V, and Icu up to 70 kA, aligning with IEC 60947-2 and CE conformity. ABB EcoSolutions data, environmental declarations (EPD, RoHS), and recycle-ready packaging support sustainable procurement and compliant end-of-life management across global projects. This combination of performance, installation convenience, and eco-credentials makes it a practical choice for power distribution, transformer protection, and switchgear retrofits.

Product Information

Extended Description

1SDA067463R1 ABB: C.BREAKER TMAX XT1H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 125-1250 A FULLY RATED NEUTRAL
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HE4125AFF000XXX
E-Number (Norway)
4379250
EAN
8015644013578
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644013578
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 52.5 kA | (415 V AC) 37.5 kA | (440 V AC) 32.5 kA | (500 V AC) 25 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 52.5 kA | (500 V DC) 3 Poles in Series 52.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 35 kA | (690 V AC) 10 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
GL Certificate
1SDL000163R0103
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature and benefit are presented in a practical, business-focused sequence: The front-terminal bolt connections enable secure, vibration-resistant busbar contacts, reducing field rework and tightening torque concerns (6 N·m) and enabling faster panel assembly for 45.5 to 80 mm² conductor sizes. Business impact: increased installation efficiency and long-term reliability in critical power paths. Application: suitable for 4-pole XT1 configurations in industrial switchgear where front access improves servicing and diagnostics. Feature: Adjustable setting range of 87.5–125 A; Business impact: precise coordination with motor and load profiles, enabling optimized discrimination and reduced nuisance trips. Application: ideal for distribution panels with varying load growth. Feature: High short-circuit and interrupting capability (Icu up to 70 kA at 690 V; Ics up to multi-kA ranges per line); Business impact: enhanced system protection for transformers and feeders, meeting IEC 60947-2 standards. Application: protective devices in transformer protection schemes and critical power paths. Feature: 4P XT1 design with front terminals and TMD release; Business impact: simplified installation and dependable release behavior with fast opening times. Application: essential in rugged industrial environments where quick disconnections are required. Feature: Comprehensive compliance and environmental data (CE, IEC 60947-2, EPD, RoHS, CMRT, TSCA); Business impact: supports compliant procurement, regulatory reporting, and sustainable sourcing. Application: appropriate for global projects with strict environmental and certification requirements. Feature: Durable construction and documented maintenance guidance (Disassembly instructions Tmax XT XT1); Business impact: facilitates safe end-of-life management and predictable lifecycle planning. Application: aligns with ABB EcoSolutions objectives for circularity and responsible disposal.

Get a Quick Quote for a ABB 1SDA067463R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067463R1? Enquire Now

FAQs

For XT1 4P with front terminals, use bolt terminals and ensure busbar sizes between 45.5 and 80 mm². Tighten to 6 N·m and follow the recommended installation drawings (XT1 3p-4p fixed front terminals) to maintain performance and enable quick servicing.
Set within 87.5–125 A to tailor protection to the load profile. The TMD release provides coordinated tripping; expected opening times are around 30 ms, ensuring fast interruption during fault conditions and minimizing arc duration in feeders.
Yes. It is rated for 690 V operating voltage with Ui 800 V and Icu up to 70 kA, making it appropriate for transformer protection and feeder protection in industrial switchgear assemblies.
The device carries IEC 60947-2 compliance and CE conformity, plus environmental declarations (EPD, RoHS) and CMRT/TSCA information. Additional certificates (GL, LR) and WEEE packaging data support global regulatory and sustainability reporting.
Disassembly instructions for Tmax XT XT1 are provided to aid safe recycling. The unit’s electrical durability and mechanical durability support long lifecycles, while ABB EcoSolutions data guide sustainable disposal and recycling practices to reduce total cost of ownership.