ABB 1SDA067584R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067584R1
Manufacturer
ABB
Part number
1SDA067584R1

Quick Summary

ABB 1SDA067584R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for industrial power distribution. For engineers, misconfigured protection and extended maintenance downtime are common pains, and this device offers a precise 1.12 to 1.6 A setting with front-terminal wiring for quick servicing. It supports CE conformity via the EC Declaration of Conformity and adheres to IEC 60947-2 requirements, with GL and LR certificates validating traceability. In practice, the solution aligns with ABB EcoSolutions, delivering space-efficient panel layouts, predictable coordination, and a clear path to compliance. This reduces downtime, enhances safety, and supports procurement with documented environmental and lifecycle information.

Product Information

Extended Description

1SDA067584R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 1,6-16 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3001AFF000XXX
E-Number (Norway)
4379281
EAN
8015644014803
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644014803
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
1.6 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
16 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.12...1.6 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The 3-pole XT2 housing with fixed front terminals streamlines wiring and serviceability. This configuration reduces field installation time and minimizes terminal mis-connections, yielding safer assembly and lower labor costs. In control panels and distribution boards, the front-access terminals speed commissioning and simplify future maintenance, supporting shorter downtime windows and easier retrofit projects. The thermomagnetic release (TMD) with a 1.12–1.6 A setting range delivers precise protection coordination. The business impact is reduced nuisance trips and better selectivity, improving equipment uptime. In transformer and motor feeder applications, this lets operators tune trips to actual fault current, while maintaining compliance with IEC 60947-2 and regional safety standards. With an operational voltage up to 690 V and insulation up to 1000 V, this MCCB balances safety margins with compact sizing. The device supports high short-circuit withstand capacities (Ics up to 100 kA and Icu up to 70 kA across key voltages), enabling reliable protection for feeders and transformers in industrial plants. Compact dimensions and modest weight help save space in tight panels and reduce transport costs: 90 mm width, 130 mm height, 82.5 mm depth, about 1.1 kg. The unit also offers robust mechanical durability (up to 25,000 cycles) and electrical durability (up to 8,000 cycles at rated conditions), ensuring long service intervals. Extensive environmental and compliance data add value for procurement: EPDs for Tmax XT XT2 TM, EN45555 recyclability estimate around 55.7%, RoHS and REACH declarations, CMRT, and EOL disassembly guidance. With comprehensive installation instructions, wiring diagrams, and data sheets, engineers can confidently specify, install, and maintain within standards and corporate sustainability targets.

Get a Quick Quote for a ABB 1SDA067584R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067584R1? Enquire Now

FAQs

The ABB XT2 front-terminal design simplifies wiring by providing bolt-type terminals accessible from the front. Ensure busbar connection is within 32.5–100 mm² and torque each terminal to 6 N·m. Use the 3P configuration for balanced protection and follow the included installation instructions for safe, code-compliant commissioning.
Setting range is 1.12–1.6 A (TMD release), with a rated service current of 1.6 A. Short-circuit capabilities vary by voltage, but the unit is designed to deliver high Ics ratings up to 100 kA and Icu up to 70 kA across standard industrial voltages, aligning with IEC 60947-2 requirements.
Yes. With 690 V operation, Ui 1000 V insulation, and robust Ics/Icu performance, the XT2 3P MCCB provides selective protection and fast clearing for transformer feeders, reducing fault impact and improving overall system reliability in distribution networks.
The device includes a CE declaration of conformity and IEC 60947-2 compliance. Additional certifications such as GL and LR certificates are listed in the data sheet, supporting traceability and regulatory awareness for global deployments.
Front-terminal access simplifies inspection and replacement, while durable mechanical and electrical cycles (up to 25,000 and 8,000 respectively) extend service intervals. Combined with environment and disposal data, the solution supports predictable maintenance, reduced downtime, and stronger total cost of ownership in manufacturing environments.