ABB 1SDA067585R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067585R1
Manufacturer
ABB
Part number
1SDA067585R1

Quick Summary

ABB Tmax XT Moulded Case Circuit Breaker is a rugged, front-terminal protection solution for low-voltage power distribution in industrial automation. Engineers upgrading panels often face space constraints, wiring challenges, and lengthy commissioning cycles. This 1SDA067585R1 XT2H 160 model meets IEC 60947-2 with CE conformity and RoHS compliance, while offering an environmental profile that supports sustainable manufacturing. The device’s 3-pole XT2 design with front terminals, 690 V rated operation, and adjustable release delivers reliable protection with straightforward installation. By combining lifecycle durability data with a compact footprint, it helps panel builders reduce downtime, simplify maintenance, and lower total cost of ownership while maintaining safety and compliance.

Product Information

Extended Description

1SDA067585R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 2-20 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3002AFF000XXX
E-Number (Norway)
4379282
EAN
8015644014810
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644014810
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.38 W
Rated Current (In)
2 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
20 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.4...2 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal design offers safer, faster wiring and easier field maintenance, reducing panel assembly time and wiring errors in dense switchgear spaces. This translates to lower commissioning costs and quicker uptime in automated production lines. The compact XT2 footprint, with a net width of 90 mm and height of 130 mm, and a weight around 1.1 kg, enables tighter panel layouts and easier shipping, delivering tangible space and logistics savings for panel builders. Electrical durability of 120 cycles per hour up to 8000 cycles combined with 240 mechanical cycles per hour up to 25000 cycles extends service life and lowers maintenance frequency in harsh industrial environments. The 690 V operating voltage, 2 A rated current, and front-bolt terminal connection support robust protection without compromising accessibility or installation speed. RoHS and CE conformity, along with EPD availability for Tmax XT, reinforce regulatory compliance and environmental stewardship for modern factories. These features work together to deliver predictable protection, faster deployment, and reduced total cost of ownership for control panels and machine builders.

Get a Quick Quote for a ABB 1SDA067585R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067585R1? Enquire Now

FAQs

To install, mount the 3P XT2H unit using front bolt terminals and tighten to 6 N·m. Connect busbars within the 32.5–100 mm² range and ensure correct alignment with the panel’s DIN rail or mounting frame. Check that the installation adheres to IEC 60947-2 guidelines and verify that the rated voltage (690 V) and current (2 A) match the panel requirements before energizing.
The device supports a rated insulation voltage Ui of 1000 V and a rated operational voltage Ur of 690 V (AC) / 500 V (DC). Short-circuit performance includes Ics values up to 100 kA depending on voltage, with Icu (ultimate short-circuit breaking capacity) around 70–100 kA per voltage class, ensuring strong protection for LV distributions in industrial settings.
Yes. With 3P front-terminal design, 690 V operation, 2 A nominal current, and rugged mechanical/electrical durability, it is well-suited for machine builders and automation panels requiring reliable fault protection, fast maintenance access, and compact footprint in tight spaces.
The device carries CE conformity (EC Declaration of Conformity for Tmax XT2) and RoHS compliance. It is part of ABB’s SACE Tmax XT family with published environmental declarations (EPD) and various certifications (e.g., GL, LR, UL references as applicable), ensuring safety and regulatory alignment across global projects.
Electrical durability is rated at up to 8000 cycles with 120 cycles per hour, while mechanical durability reaches up to 25,000 cycles (240 cycles per hour). This translates into longer service intervals, reduced maintenance downtime, and lower lifecycle costs for high-demand automation installations.