ABB 1SDA067589R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA067589R1
Quick Summary
Moulded Case Circuit Breaker protects low-voltage power distribution by interrupting fault currents in panelboards and motor control centers. This ABB XT2 3P solution addresses common wiring and protection challenges in compact spaces, offering precise coordination and fast isolation. The device aligns with IEC 60947-2 and CE requirements, with additional GL and LR certifications supporting robust lifecycle performance. By combining a front-terminal design with a compact footprint and a clear setting range, it enables safer installations, easier maintenance, and improved panel density. For engineers and procurement teams, the XT2 long-term reliability translates to reduced downtime and lower total cost of ownership while maintaining compliance across international sites.
Product Information
Extended Description
1SDA067589R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 5-50 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3005AFF000XXX
E-Number (Norway)
4379286
EAN
8015644014858
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644014858
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.3 W
Rated Current (In)
5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
50 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
3.5...5 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Front-terminal three-pole configuration with bolt terminals and a front entry design simplifies wiring during retrofit or new builds, reducing installation time and error-prone cabling, especially in tight control panels or MCCs. Application: panel boards in industrial facilities where space is at a premium and rapid commissioning is needed. Feature → Business Impact → Application: TMD release and a defined setting range of 3.5–5 A provide precise protection tailored to small-control circuits and transformer protection, improving selectivity and minimizing nuisance trips. Application: control circuits and transformers in low-voltage distribution networks. Feature → Business Impact → Application: High breaking capacity (Icu up to 100 kA at relevant voltages) delivers reliable fault interruption, reducing risk of cascading faults and equipment damage. Application: panels serving motors and power distribution with high fault currents. Feature → Business Impact → Application: Rated insulation voltage up to 1000 V and operational voltage up to 690 V AC / 500 V DC enable compatibility with mixed AC/DC systems, supporting versatile installation across industrial plants. Application: mixed electrical environments and future-proofed panel design. Feature → Business Impact → Application: Compact dimensions (90 mm width × 130 mm height × 82.5 mm depth) and 1.1 kg weight facilitate space-saving layouts and easier replacement in legacy assemblies. Application: retrofit projects and space-constrained switchgear upgrades. Feature → Business Impact → Application: Compliance with IEC 60947-2 and CE alongside documented environmental and product declarations supports regulatory licensing, supplier audits, and sustainability programs. Application: industries with strict certification and environmental reporting requirements.
Get a Quick Quote for a ABB 1SDA067589R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067589R1?
Enquire Now
FAQs
The XT2 device is a three-pole MCCB with front terminals and bolt connections, designed for straightforward wiring in control panels. It supports busbar connections from 32.5 to 100 mm², with a tightening torque of 6 N·m, and a compact footprint measuring 90 mm in width, 130 mm in height, and 82.5 mm in depth to fit dense panels and retrofit projects.
Key specs include rated current 5 A, rated voltage 690 V AC and 500 V DC, rated insulation voltage 1000 V, setting range 3.5–5 A, control release TMD, and 3P configuration. Its short-circuit ratings show Icu and Ics up to 100 kA across various voltages, with Iu rated at 160 A, and standards compliant with IEC 60947-2.
Yes. The 3P XT2 with front terminals is designed for panel boards and motor control centers, offering precise protection for low-voltage circuits, compatibility with 690 V AC/500 V DC systems, and a compact form factor that eases integration into existing MCCs and new panel designs.
This device carries CE conformity (EC Declaration of Conformity), GL and LR certificates, and includes environmental declarations such as EPD for Tmax XT XT2 and design for recycling per EN45555. It also references CMRT and TSCA disclosures, along with RoHS compliance, supporting regulatory audits and sustainability reporting.
Tmax XT XT2 offers high mechanical and electrical durability, with up to 25,000 mechanical cycles and up to 8,000 electrical cycles under rated conditions. This translates to reduced maintenance intervals, lower downtime, and improved system availability, delivering a favorable total cost of ownership in long-term distribution and MCC deployments.