ABB 1SDA067592R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA067592R1
Manufacturer
ABB
Part number
1SDA067592R1

Quick Summary

ABB 1SDA067592R1 moulded case circuit breaker protects low-voltage power distribution in industrial panels. Engineers often struggle with compact space, front-terminal installation, and selecting a reliable trip setting that won’t compromise uptime. This model aligns with IEC 60947-2 and CE conformity within the SACE Tmax XT family, delivering proven safety and regulatory compliance. Its 3-pole XT2 configuration, front terminals, and adjustable 7–10 A setting provide precise protection for distribution boards facing diverse loads. By combining robust electrical performance with straightforward installation, it supports faster commissioning, easier maintenance, and safer operation across industrial applications.

Product Information

Extended Description

1SDA067592R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 10-100 A
Country of Origin
China (CN)
Lead Time
67 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
c22196a0-44f2-434b-9b84-a46b82990e7c Italy (IT)
Simplified SCIP
b8128572-784a-422b-b1ad-08ce878ea792 Germany (DE) | 9d9ec041-1e11-4537-a4a1-57fac441dd18 Poland (PL) | a0f5e33e-67fa-47f6-ae5e-79e0811a5495 Norway (NO) | 2a97fe19-98a9-41fb-a519-dcb14e5ca45d Finland (FI) | 54a51eeb-76b0-4ed9-951d-dbd62e42d812 Netherlands (NL) | 9d675f1e-7b93-4032-b982-8713fa095a72 Germany (DE) | 141d392c-d8b2-4e1a-9c1f-d6f02ea85951 Denmark (DK) | 1783be2d-0c1c-4b7a-bc93-08b6ea185436 Netherlands (NL) | 2f6a1fb8-3be0-44bd-9b25-332a278974d5 Netherlands (NL) | 4f1cde91-7ef3-4cf9-b6fe-f94495c73439 Estonia (EE) | 5af5b789-0f6f-4562-a273-94c8798c12e8 Greece (GR) | 7582d9bf-de04-4f66-974d-7d9b9bd6a387 Portugal (PT) | ba5f248a-53e9-4587-a247-8f22ab8c6f93 Germany (DE) | 0ba068b1-6608-4680-bc9d-429c1eabe785 Croatia (HR) | ca6ad635-5242-4ae4-9431-d272b28c3e65 Czech Republic (CZ) | 052a0e46-58d2-4fb7-a5b6-934e8a8dc6f6 Poland (PL) | f04494fe-8119-4d21-b6ca-07e9c0b625a8 Germany (DE) | 84e157f2-3374-40a5-8c78-717ccf5c7846 Germany (DE) | 44e6a526-b658-4d70-b5db-4867dd9e9a20 France (FR) | 18dec544-d410-4f00-b38d-92b9c0bf3903 Netherlands (NL) | f39691fb-7611-4849-8846-02b8de563d72 Spain (ES) | a502b64f-be66-4bf4-8e80-9ec1c499f3ab Netherlands (NL) | 8510d6a1-f92e-4fd6-81d5-9f8d61095d80 Bulgaria (BG) | a66a5e17-79eb-4e54-b064-2a285af77eb5 Sweden (SE) | 5384096f-1658-431d-ab1e-e2b7a3961154 Poland (PL) | f444016d-f8a6-4613-b9da-2a90df11fd16 France (FR) | 07e7c4ed-1ab7-45d7-a3b9-a4d35ed4af63 Sweden (SE)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3010AFF000XXX
E-Number (Norway)
4379289
EAN
8015644014889
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644014889
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.95 W
Rated Current (In)
10 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
100 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
7...10 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Front-terminal connections enable quicker, safer wiring and reduce assembly time in control panels; this directly lowers commissioning costs and minimizes field wiring errors, especially in compact spaces where door clearance is tight. Application: SACE Tmax XT panel boards in manufacturing lines benefit from faster deployment and improved reliability. Feature → Business Impact → Application: The 7–10 A setting range allows precise coordination with downstream protective devices, reducing nuisance trips while protecting critical loads. Application: Transformer and distribution protection in sub-panels where load variability requires adjustable trip points. Feature → Business Impact → Application: Busbar connection for 32.5–100 mm² supports common LV feeder designs, simplifying material stocking and installation. Application: New installations and retrofits in industrial plants. Feature → Business Impact → Application: 3P XT2 with front terminals provides a compact footprint (90×130×82.5 mm) and 6 N·m tightening torque for consistent, repeatable mounting. Application: Tight panel cavities and modular switchgear; easy maintenance. Feature → Business Impact → Application: IEC60947-2 compliance and RoHS/REACH declarations ensure regulatory alignment across Europe, North America, and beyond. Application: Global sourcing, OEM integration, and sustainable product lifecycles.

Get a Quick Quote for a ABB 1SDA067592R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067592R1? Enquire Now

FAQs

Follow the mount template for XT2 front terminals, connect the busbar to 32.5–100 mm² conductors, torque each terminal to 6 N·m, and verify the correct setting range (7–10 A) before energizing. Ensure the panel has adequate clearance and observes the 90×130×82.5 mm footprint for safe operation.
It protects low-voltage distribution boards and transformer circuits in manufacturing, processing, and aggregate power panels. The 3P XT2 design supports compact installations, and front-terminal wiring simplifies replacement and maintenance in retrofit projects.
This device aligns with IEC 60947-2 and includes a CE declaration of conformity. Additional documentation covers RoHS/REACH compliance, ETIM classification, and SCIP-related disclosures for responsible material use and end-of-life considerations.
Rated current is 10 A with a rated voltage of 690 V. It offers a setting range of 7–10 A, and protective capacities include Ics up to 100 kA at lower voltages (with appropriate configurations) and 15 kA at 690 V. The device supports 3P operation with front-terminal connections.
Its compact XT2 footprint, front-terminal wiring, and adjustable trip settings reduce installation time and field wiring errors. Compliance with IEC 60947-2 and RoHS/REACH minimizes regulatory risk, while robust short-circuit protection lowers downtime and maintenance costs over the product life cycle.