ABB 1SDA067593R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA067593R1
Quick Summary
Moulded Case Circuit Breaker from ABB protects industrial electrical distributions against overload and short circuits. With fixed front terminals and a robust 3-pole XT2 design, installation is faster and wiring mistakes are reduced across panel builds. CE conformity and IEC 60947-2 compliance ensure European-market readiness, while EcoSolutions principles support sustainable manufacturing and end-of-life planning. The adjustable setting range of 8.75 to 12.5 A and the TMD thermomagnetic release deliver precise protection for motors, transformers, and feeder circuits. Designed for 690 V systems, its 12.5 A nominal rating provides predictable coordination with downstream protection, helping OEMs and integrators meet reliability targets and reduce maintenance costs.
Product Information
Extended Description
1SDA067593R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 12,5-125 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
6ef02f8d-44d7-4a1d-85c0-bb5509f53cf1 Italy (IT)
Simplified SCIP
3683613d-61ef-4311-bd97-7eeac591c35b Germany (DE) | 940d1827-474e-407d-82ef-d9526848d051 Sweden (SE) | 984ef8a3-ece6-4420-ad3e-936bc479f67e Poland (PL) | 7147f31a-3dd4-4342-a2ab-bb704fffc53d France (FR) | 72b319fd-48e3-4d39-bcae-9e16277d20a7 Sweden (SE) | 211d7250-c198-476b-ba75-e0c9cf4b0040 Poland (PL) | fbb83dae-37fb-46a2-b0f7-1d143814451d Germany (DE) | 6d2894d3-08e1-4f5d-a8a6-df20a66f5e7a France (FR) | 090a44ff-a567-41e4-979f-1f83141daab6 Netherlands (NL) | ff302c37-eb4e-4e05-a8e6-d7318392e68a Spain (ES) | eaf40900-4ad5-4242-8a43-c76a3bfff928 Netherlands (NL) | 4a424d8e-8625-4216-b14c-594d8f212917 Bulgaria (BG) | 5fa9c084-d5d1-4e17-a794-9c7d71470bc6 Norway (NO) | eb0f35df-eb40-48e7-8b80-1e6f82a6018c Finland (FI) | d00d21eb-4bc4-4f0e-9f99-651a21e29eb5 Netherlands (NL) | a6543064-dcd8-42c8-bed2-d14d8feefc67 Germany (DE) | 0b51511e-3e45-41a4-8081-3df847fd42a2 Denmark (DK) | 2fab6abc-dbcc-4da4-a1d2-b0cafaea4832 Netherlands (NL) | 7f7b3c78-b246-4ca1-9ed8-163d895aa242 Netherlands (NL) | 75a9654c-0192-4a7e-9064-d3f5457be6dc Estonia (EE) | 2a77e16b-387e-4d11-9854-5c4bd56d5907 Greece (GR) | a131d7c6-1809-473e-9bce-7a9ba963040f Portugal (PT) | 194c878e-e241-4878-964b-ee7933095491 Germany (DE) | 3d319e43-b151-4a91-ad1e-7c9d39e6eea1 Croatia (HR) | 80e02284-94ce-43e3-9de4-d09d9f891fc0 Czech Republic (CZ) | c43cd84c-b24d-4e73-b307-71d159f63dd5 Poland (PL) | e198ffff-9a2c-402f-93a8-9947c0666c22 Germany (DE)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3013AFF000XXX
E-Number (Norway)
4379290
EAN
8015644014896
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644014896
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.05 W
Rated Current (In)
12.5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
125 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
8.75...12.5 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal fixed 3P XT2 design simplifies panel assembly and wiring verification. The fixed front terminals reduce field wiring errors and speed up commissioning, while 32.5..100 mm² busbar capacity supports a wide range of feeder configurations. This translates to faster installation, reduced labor costs, and improved panel density in control cabinets for manufacturing lines. Thermomagnetic release (TMD) with an adjustable setting range of 8.75 to 12.5 A delivers precise overload protection for motors and transformers; the combination minimizes nuisance trips and enables coordinated protection with downstream devices. The unit offers high fault-handling capability (Ics up to 100 kA, Iu 160 A, U_r 690 V) for robust protection in demanding environments. IEC 60947-2 compliance, CE declarations, and EN45555 recyclability support regulatory and sustainability goals. Tightening torque is 6 N·m, ensuring secure front-terminal connections with Main Circuit M6 drivers. Compatibility with SACE Tmax XT characteristics and front-terminal wiring diagrams simplifies retrofits and new builds alike. The 3P 690 V rating makes it suitable for transformer feeders and motor-distribution panels, while the lightweight 1.1 kg body accelerates shipping and handling. The design also supports disassembly guidance for End Of Life planning, aligning with ABB EcoSolutions objectives.
Get a Quick Quote for a ABB 1SDA067593R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067593R1?
Enquire Now
FAQs
This ABB XT2 device accepts busbars from 32.5 up to 100 mm², aligning with standard control-panel feeders. For best results, ensure the busbar ends are clean, the mounting rails are level, and the front-terminal bolts are torqued to 6 N·m to maintain solid electrical contact and prevent heat buildup during operation.
The unit uses a thermomagnetic release (TMD) with an adjustable setting range of 8.75 to 12.5 A. This provides precise overcurrent protection for small motors and transformers, while enabling coordination with downstream protection devices to minimize nuisance trips in variable-load applications.
Yes. Rated operational voltage is 690 V, and the device supports high short-circuit capability (Ics up to 100 kA depending on voltage). This makes it suitable for transformer feeders and motor circuits in demanding 690 V industrial environments, with IEC 60947-2 shaping the protection strategy.
The product carries the CE Declaration of Conformity and complies with IEC 60947-2. It also aligns with ABB EcoSolutions and EN45555 recyclability targets, and an EPD is available for environmental assessment. For traceability, a unique UL/CE/SCIP footprint is maintained within ABB’s compliance landscape.
Common applications include motor feeders, transformers, and distribution panels in manufacturing and process utilities. Maintenance benefits come from front-terminal accessibility, reliable 3P protection, and a Tightening Torque of 6 N·m. If replacement is needed, the unit’s front-terminal design simplifies wiring changes and reduces downtime during retrofit projects.