ABB 1SDA067600R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067600R1
Quick Summary
ABB 1SDA067600R1 is a three-pole moulded case circuit breaker designed for reliable protection in low-voltage distribution and transformer feeder panels. In busy plants, incorrect protection settings and difficult wiring can drive downtime and maintenance costs. The unit aligns with IEC 60947-2 and CE requirements, and carries LR certificate for reliability and traceability. Rated 63 A and 690 V, it belongs to the SACE Tmax XT family with front-terminal design, delivering straightforward wiring and predictable protection in compact switchboards. This combination of robust standard compliance and practical installation helps engineers meet safety and uptime targets while keeping total cost of ownership in check.
Product Information
Extended Description
1SDA067600R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 63 I3=315...630 A
Country of Origin
China (CN)
Lead Time
21 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3063BFF000XXX
E-Number (Finland)
3602499
E-Number (Norway)
4379297
EAN
8015644014964
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.666 kg
Package Level 1 EAN
8015644014964
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.85 W
Rated Current (In)
63 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
300…630 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
44.1...63 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The fixed front-terminal XT2H design reduces wiring time and improves connection reliability, enabling faster panel assembly and fewer loose connections in control and distribution panels. This directly translates to reduced commissioning time and lower field fault risk. The thermomagnetic release with an adjustable setting range of 44.1 to 63 A and an instantaneous trip window of 300 to 630 A provides selective protection, minimizing nuisance trips and preserving downstream equipment during faults. With a rated service short-circuit breaking capacity up to 100 kA and up to 70 kA ultimate ratings across common low-voltage voltages, this MCCB delivers robust fault energy handling for transformers and motor feeders while meeting IEC 60947-2 requirements. The 32.5–100 mm² busbar compatibility and front-terminal connection streamline installation in tight panels, reducing wiring complexity and panel depth. The device supports lifecycle efficiency with RoHS/REACH compliance and eco-focused features like an EPD, and offers predictable maintenance intervals thanks to a mechanical durability of up to 25,000 cycles and electrical durability up to 8,000 cycles per hour, supporting long-term operational reliability in industrial environments. Finally, the 6 N·m tightening torque and M6 screwdriver recommendation foster consistent, vibration-resilient installations in harsh environments, while the XT2H 3P format is well-suited for power distribution and transformer protection within ABB SACE Tmax XT ecosystems.
Get a Quick Quote for a ABB 1SDA067600R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067600R1?
Enquire Now
FAQs
This unit uses front-terminal connections and is designed for XT-series layouts. It supports busbars from 32.5 to 100 mm², requires 6 N·m tightening torque with a Main Circuit M6 screwdriver, and fits three-pole XT2 housings for conventional Tmax XT installations.
The device features an adjustable setting range of 44.1 to 63 A, with an instantaneous trip current setting Ii of 300 to 630 A, enabling selective protection for transformer feeders and motor circuits.
Yes. The product carries ROHS/REACH declarations and a CE Declaration of Conformity for Tmax XT2, with supporting certifications such as LR and GL where applicable, ensuring regulatory compliance across major markets.
Electrical durability is up to 8,000 cycles per hour, while mechanical durability reaches up to 25,000 cycles, supporting long service life in demanding industrial duty cycles.
With a 690 V rating, 63 A current, and high short-circuit capacities (Ics up to 100 kA, Icu up to 70 kA), it provides reliable transformer protection and distribution-board safeguarding, reduces nuisance trips, and simplifies installation in compact ABB SACE Tmax XT systems.