ABB 1SDA067621R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067601R1
Quick Summary
ABB 1SDA067621R1 Moulded Case Circuit Breaker protects motor circuits and power distribution in industrial plants. In dense switchgear, selecting the right current setting and a reliable trip curve is critical to avoiding downtime and warranty risk. This XT2H device complies with IEC 60947-2 and CE conformity, with RoHS and REACH declarations and an Environmental Product Declaration (EPD) available. With front-terminal installation and a 4-pole design rated to 690 V and 63 A, it supports scalable protection for motor feeders and distribution panels. Leverage ABB's Tmax XT family for compatibility with busbars 32.5–100 mm² and a compact footprint that reduces panel depth and assembly time.
Product Information
Extended Description
1SDA067601R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 80 I3=400...800 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3080BFF000XXX
E-Number (Finland)
3638189
E-Number (Norway)
4379298
EAN
8015644014971
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.65 kg
Package Level 1 EAN
8015644014971
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 5.8 W
Rated Current (In)
80 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
400…800 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
56...80 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal connection and bolt terminals enable quick wiring and secure torque during panel assembly. Business Impact: Reduces installation time, minimizes wiring errors, and improves repeatable torque across assemblies. Application: Ideal for control panels and MCCs where fast field wiring is essential. Feature: Thermal-magnetic release (TMA) provides precise overload protection and fast short-circuit interruption. Business Impact: Protects motors and transformers from thermal damage and reduces arc energy exposure. Application: Suitable for high-startup current loads in manufacturing lines. Feature: Setting range of 44.1–63 A with a fixed 63 A rated current supports selective coordination in mixed-load feeders. Business Impact: Optimizes protection zones, improves fault isolation, and reduces nuisance trips. Application: Motor feeders and distribution circuits with variable load profiles. Feature: 4P XT2 design and front-terminal type enhances mounting stability and servicing access. Business Impact: Facilitates space-saving panel layouts and simpler maintenance routines. Application: Large switchgear assemblies and transformer protection apps. Feature: Rated voltage of 690 V and Ui of 1000 V enables safe operation in modern LV networks. Business Impact: Broad compatibility with industrial systems while preserving safety margins. Application: Electrical distribution in manufacturing plants and processing lines. Feature: RoHS, REACH compliance and EPD availability support sustainability and regulatory readiness. Business Impact: Minimizes compliance risk and supports green procurement programs. Application: Global supply chains with corporate ESG targets.
Get a Quick Quote for a ABB 1SDA067601R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067601R1?
Enquire Now
FAQs
Installers should ensure front-terminal bolts are tightened to 6 N·m, verify busbar connection within 32.5–100 mm², and follow installation instructions XT2 for front-terminal mounting. This reduces wiring errors, improves accessibility for maintenance, and supports reliable fault isolation in compact switchgear.
The device is rated for 63 A with a setting range of 44.1–63 A and a rated voltage of 690 V (Ui 1000 V). It offers Ics up to 100 kA at lower voltages and up to 15 kA at 690 V, with a 8 kV impulse withstand. These specs support precise coordination and robust protection for motor feeders.
Yes, it supports 690 V AC systems. Short-circuit ratings include Icu up to 70–100 kA depending on voltage and configuration, with Ics values reaching up to 100 kA at 230–240 V and 15 kA at 690 V AC, plus high-performance DC ratings for series configurations as specified.
The product complies with IEC 60947-2, with a CE Declaration of Conformity, RoHS and REACH declarations, and an available EPD. Additional certifications include GL and LR certificates, supporting global regulatory and sustainability requirements.
ROI comes from reduced downtime due to precise thermal-magnetic protection, faster installation from front-terminal wiring, and extended maintenance intervals thanks to robust construction. The XT family also supports compact layouts, saving cabinet space and enabling scalable protection for growing motor and feeder networks.