ABB 1SDA067607R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA067607R1
Quick Summary
ABB 1SDA067607R1 is a moulded case circuit breaker for protecting 690 V distribution in industrial electrical systems. It addresses downtime and maintenance hassles through front-terminal access and reliable thermal-magnetic release. Key certifications include CE conformity (EC Declaration of Conformity Tmax XT2), GL and LR approvals to support global installations, with UL and VDE certifications available per market. This compact 4-pole device from the SACE Tmax XT family offers dependable protection, front-terminal accessibility, and a design that integrates with ABB EcoSolutions for sustainable end-of-life handling. For businesses seeking consistent safety compliance and easier maintenance across facilities, this MCCB provides value with scalable protection and field-proven performance.
Product Information
Extended Description
1SDA067607R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 2,5-25 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4002BFF000XXX
E-Number (Norway)
4379600
EAN
8015644015039
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015039
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.47 W
Rated Current (In)
2.5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
25 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.75...2.5 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The 4-pole 690 V MCCB delivers robust distribution protection, reducing the risk of cascading faults and downtime in heavy electrical environments. By combining a front-terminal design with a bolted connection and a tight 6 N·m torque, installation is faster and more reliable, saving commissioning time and minimizing connection faults. The built‑in thermal-magnetic release (TM) with an adjustable setting range of 1.75–2.5 A provides precise overcurrent protection for feeders and transformers, improving system uptime and protecting costly equipment. Busbar compatibility from 32.5 to 100 mm² expands retrofit options without rewiring, while the 2.5 A rated current enables compact, energy-efficient protection on low-load feeders. IEC 60947-2 compliance ensures global acceptance in industrial switchgear assemblies, and the XT design supports easy maintenance and future upgrades. The unit’s 690 V AC / 500 V DC ratings, front-terminals, and clear wiring diagram simplify on-site servicing and spare-part planning.
Get a Quick Quote for a ABB 1SDA067607R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067607R1?
Enquire Now
FAQs
This MCCB uses front bolt terminals and supports busbar connections ranging from 32.5 mm² to 100 mm². The front-terminal configuration simplifies wiring, enables quick installation, and reduces space requirements in panel layouts while maintaining secure, vibration-resistant connections for industrial environments.
The device is a 4P MCCB with 690 V rated voltage (AC) and 1000 V rated insulation, a rated current of 2.5 A, and a setting range of 1.75–2.5 A. It provides thermal-magnetic release (TM) protection with an instantaneous setting up to 25 A and a short-circuit breaking capacity up to 100 kA depending on voltage, suitable for medium-power feeders.
Yes. The XT Tmax family is designed for transformer and generator protection within industrial switchgear. The 4P XT2 model with front terminals and TM release is well-suited for protection of 690 V distribution circuits, meeting IEC 60947-2 requirements and supporting reliable operation in transformer-fed feeds and network protection schemes.
Key certifications include CE conformity (EC Declaration of Conformity Tmax XT2), GL and LR approvals for global installation. UL and VDE certifications are market-dependent, and the product adheres to IEC 60947-2 standards. These certifications help ensure regulatory compliance, safety, and risk management across international projects.
Follow the 6 N·m tightening torque for front-terminal bolts and use M6 screwdriver bits as recommended. Ensure the busbar is within 32.5–100 mm² and align the unit for front-termination access. The device weighs about 1.45 kg and occupies a compact footprint of 120 mm width by 130 mm height, suitable for panel-mounted DIN rail or fixed busbar assemblies according to enclosure design.