ABB 1SDA067609R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067609R1
Manufacturer
ABB
Part number
1SDA067609R1

Quick Summary

ABB 1SDA067609R1 is a 4-pole molded case circuit breaker for industrial power distribution protection. Engineers face nuisance trips and downtime from aging devices; this model's precise thermal-magnetic release reduces false trips. It aligns with IEC60947-2, carries CE EC declarations, and holds GL and LR certificates for global compliance. Designed to integrate with ABB SACE Tmax XT XT2 families, it supports front-terminal wiring on 690 V systems. With compact dimensions and easy installation, it lowers total cost of ownership in control panels and distribution boards. This combination of reliability, safety features, and lifecycle efficiency makes it a strong fit for data centers, manufacturing lines, and critical infrastructure.

Product Information

Extended Description

1SDA067609R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 4-40 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4004AFF000XXX
E-Number (Norway)
4379602
EAN
8015644015053
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015053
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.47 W
Rated Current (In)
4 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
40 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
2.8...4 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The 4P XT2 molded case design uses fixed front terminals and a TM release. This enables faster, safer wiring and simplifies on-site installations, reducing commissioning time in panel assemblies. In practice, it supports motor protection and feeder protection in space-constrained switchgear with robust, reliable performance. The 4 A rated current with a setting range of 2.8 to 4 A provides precise overload protection and selective tripping for small control circuits in factory automation, minimizing unnecessary outages while protecting sensitive equipment. High short-circuit capacity (Ics up to 100 kA and Icu up to 100 kA depending on voltage) offers strong protection for transformers and feeders in demanding power networks, increasing uptime and safety. The device supports 690 V operation with Ui of 1000 V, broadening its applicability across plant sections and MCCs. Front-terminal, bolt-type connections with 6 N·m torque ensure a secure, vibration-resistant fit on busbars from 32.5 to 100 mm², enabling reliable long-term performance in cabinets and switchgear. The XT2 design also emphasizes energy efficiency with power losses around 2.47 W per pole, contributing to lower operating costs. Environmentally, the unit aligns with RoHS and REACH expectations and provides recyclability data via EN45555 pathways, supporting sustainability programs without compromising protection. Overall, the product harmonizes ease of installation, robust electrical performance, and regulatory compliance for modern industrial automation environments.

Get a Quick Quote for a ABB 1SDA067609R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067609R1? Enquire Now

FAQs

This MCCB uses fixed front terminals designed for bolt connections and supports busbar ranges from 32.5 to 100 mm². It fits standard ABB SACE Tmax XT XT2 configurations and is suitable for new installs or panel refurbishments where front-terminal wiring simplifies assembly and maintenance.
Key specs include a rated current of 4 A with a setting range of 2.8–4 A, rated voltage of 690 V, Ui of 1000 V, and a short-circuit current rating (Ics) up to 100 kA with instantaneous rating (Ii) of 40 A. It uses a thermal-magnetic release (TMD) and is IEC60947-2 compliant.
Yes. It is designed for 690 V systems, features front-terminal bolt connections, and has a high insulation voltage rating, making it appropriate for medium-voltage sections of control panels, MCCs, and transformer protection schemes in industrial settings.
The product carries a CE EC Declaration of Conformity and GL and LR certificates. IEC60947-2 is the core standard, with RoHS and REACH declarations. It also aligns with recycling and lifecycle targets such as EN45555, supporting sustainability-focused procurement.
The device offers reliable protection with low power loss (about 2.47 W per pole) and durable electrical/mechanical life spans. Reduced nuisance trips, easier installation, and robust front-terminal connections lower maintenance time, minimize downtime, and contribute to lower total cost of ownership in manufacturing lines and critical distribution panels.