ABB 1SDA067611R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067611R1
Quick Summary
ABB 1SDA067611R1 is a moulded case circuit breaker used for main power distribution and transformer protection. Engineers frequently struggle with nuisance trips and maintenance in compact switchgear, this breaker helps reduce both. CE conformity with IEC 60947-2 and GL/LR approvals support global installations, while ABB EcoSolutions guides responsible end-of-life. Its 4P, front-terminal design and 690 V rating deliver reliable performance for power distribution with lower installation risk and lifecycle costs. This aligns with ABB Site Meeting Group waste targets and supports sustainable, recyclable packaging. By combining high switching capacity and a compact XT2H family form, it enables scalable protection across evolving industrial layouts.
Product Information
Extended Description
1SDA067611R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 6,3-63 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4006AFF000XXX
E-Number (Norway)
4379604
EAN
8015644015077
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015077
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.33 W
Rated Current (In)
6.3 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
63 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
4.41...6.3 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Front-terminal, 4-pole XT2 design simplifies wiring and reduces panel space, accelerating installation while lowering mounting complexity in control cabinets and switchgear. This translates to shorter project timelines and reduced labor costs during commissioning, especially in confinedMessage areas where space is a premium. Application: main distribution panels and transformer protection where reliable 4P protection is required. Feature → Business Impact → Application: Adjustable setting range 4.41–6.3 A with a fixed In of 6.3 A provides selective coordination and precise overcurrent protection, helping prevent nuisance trips and unnecessary power outages. Application: sensitive loads and critical feeders within industrial plants requiring tight current regulation. Feature → Business Impact → Application: IEC 60947-2 compliance and CE declaration ensure regulatory alignment across global sites, simplifying procurement and reducing compliance risk. Application: multinational manufacturing facilities with diverse regulatory requirements. Feature → Business Impact → Application: Ics up to 70 kA and Icu up to 100 kA at various voltages offer robust short-circuit protection, supporting high-energy events without compromising equipment safety. Application: transformer-connected feeders and main distribution where fault currents are a design consideration. Feature → Business Impact → Application: Low power loss per pole (3.33 W) and mechanical durability up to 25k cycles decrease energy costs and extend service life in continuous operation environments. Application: continuous process industries with demanding duty cycles. Feature → Business Impact → Application: Front connection Type Bolt terminal and 6 N·m tightening torque enable secure, vibration-resistant wiring in harsh environments, improving long-term reliability. Application: outdoor or industrial inside installations where vibration is a concern. Feature → Business Impact → Application: ABB EcoSolutions data including 55.70% recyclability and End of Life disassembly guidance support sustainable asset management and compliant waste handling. Application: plants pursuing circular economy targets. Feature → Business Impact → Application: Compatible with busbar ranges 32.5–100 mm² and main circuit M6 screwdriver recommendations streamline installation planning and reduce hardware variation. Application: retrofit projects and new builds seeking standardized, time-saving assembly.
Get a Quick Quote for a ABB 1SDA067611R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067611R1?
Enquire Now
FAQs
The ABB 1SDA067611R1 is designed for main power distribution and transformer protection in switchgear and control panels. Its 4P front-terminal design and 690 V rating make it ideal for compact installations where space is at a premium, while maintaining reliable protection for critical feeders.
Key specs include 690 V rated insulation and 690 V rated operational voltage, 6.3 A rated current, a setting range of 4.41–6.3 A, 4 poles, front terminal connections, and a power loss of 3.33 W per pole. Short-circuit ratings reach up to 70–100 kA depending on voltage, with Iu of 160 A.
Yes. The product is designed to IEC 60947-2 standards and carries CE conformity documentation, along with GL and LR certifications, ensuring global installation eligibility and regulatory alignment.
Front terminals simplify wiring access, reduce panel depth requirements, and enable faster commissioning. Bolt-style terminals with a 6 N·m tightening torque improve vibration resistance and long-term reliability in harsh industrial environments.
The unit offers mechanical durability up to 25,000 cycles and electrical durability of up to 8,000 cycles, along with documented End of Life disassembly instructions and recyclability data. This supports reduced maintenance intervals and lower total cost of ownership in steady-state and peak-load applications.