ABB 1SDA067612R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067612R1
Manufacturer
ABB
Part number
1SDA067612R1

Quick Summary

ABB 1SDA067612R1 moulded case circuit breaker is a four-pole XT2 device engineered for 690 V distribution in high-demand panels. Engineers often struggle with compact space, difficult wiring access, and ensuring regulatory compliance without sacrificing protection reliability. This device carries CE conformity (EC Declaration of Conformity) and third‑party approvals (GL and LR certificates), aligned with IEC60947-2 standards for safety and performance. With front-terminal accessibility and a robust 8 A rating, it simplifies installation and ongoing maintenance in industrial plants. The Tmax XT lineage supports sustainable maintenance strategies and EcoSolutions integration, delivering predictable protection, reduced downtime, and lower total cost of ownership for the power distribution network.

Product Information

Extended Description

1SDA067612R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 8-80 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4008AFF000XXX
E-Number (Norway)
4379605
EAN
8015644015084
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015084
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.57 W
Rated Current (In)
8 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
80 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
5.6...8 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P XT2 fixed-front-terminal design enables rapid wiring and straightforward panel integration, reducing installation time and fault-prone connections in switchgear. This improves reliability in power distribution and motor control applications where space is limited and accessibility matters. Long-tail keywords such as front-terminal MCB and 4-pole molded case circuit breaker describe the architecture used in compact switchboards and transformer feeders. Feature → Business Impact → Application: The adjustable setting range of 5.6–8 A allows precise coordination for small-load circuits, minimizing nuisance tripping and improving process uptime in automation panels and control cabinets. This aligns with automation experts seeking predictable trip performance while meeting energy-management requirements. Feature → Business Impact → Application: TMD release with a 30 ms opening time delivers fast fault interruption, critical for protecting downstream equipment and reducing arc-flash exposure, suitable for transformer protection and generator interfaces in critical infrastructure. Feature → Business Impact → Application: High Ics/Icu capacity across voltage bands (up to 100 kA at lower voltages, down to 15–70 kA at higher voltages) provides robust short-circuit protection for industrial feeders, ensuring compliance with IEC60947-2 and minimizing electrical stress on feeders and busbars. Feature → Business Impact → Application: Front-terminal bolt connections with a 6 N·m tightening torque support reliable, vibration-resistant wiring in heavy-duty environments, ideal for switchgear in chemical plants, metal facilities, and energy distribution centers. Feature → Business Impact → Application: ABB EcoSolutions and recyclability data (55.70% closing resource loops) enable responsible end-of-life handling, reducing environmental impact and aligning with corporate sustainability goals across manufacturing facilities. Feature → Business Impact → Application: Comprehensive dimensional and weight data (120 mm W × 130 mm H × 82.5 mm D; 1.45 kg) ensures accurate fitment in existing enclosures and straightforward replacement in legacy Tmax XT-based installations, minimizing retrofit costs in retrofits and upgrades.

Get a Quick Quote for a ABB 1SDA067612R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067612R1? Enquire Now

FAQs

This unit uses front-terminal bolt connections and a tightening torque of 6 N·m, designed for straightforward panel mounting. Ensure enclosure space accommodates 120 mm width, 130 mm height, and 82.5 mm depth, and verify busbar connections within 32.5 to 100 mm². The front-access design speeds wiring and simplifies future maintenance.
Rated service short-circuit breaking capacity (Ics) ranges by voltage, with up to 100 kA at lower voltages (e.g., 230–240 V) and up to 70 kA at higher voltages (e.g., 380–415 V). Rated ultimate short-circuit capacity (Icu) similarly scales, providing robust protection across typical industrial feeders and transformers in this XT2 family.
Yes. It is a Tmax XT 4P molded case breaker designed for distribution and transformer protection with front-terminals, IEC60947-2 compliance, and a 690 V operating rating. Its TMD release and fixed front terminals support reliable transformer protection schemes in substations and plant-level power distribution.
The unit carries CE conformity (EC Declaration of Conformity) and third-party approvals such as GL and LR certificates. It also complies with IEC60947-2. While UL/VDE are listed as not required for this model, you should verify regional requirements and any site-specific standards before procurement.
The XT2 4P with front-terminal access simplifies wiring, reduces maintenance time, and supports easier disassembly for end-of-life recycling (EcoSolutions). Its reliable protection reduces unplanned outages, improving overall equipment effectiveness (OEE) and lowering total cost of ownership in manufacturing environments.