ABB 1SDA067614R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA067614R1
Manufacturer
ABB
Part number
1SDA067614R1

Quick Summary

ABB 1SDA067614R1 Moulded Case Circuit Breaker delivers reliable overcurrent protection for modular power distribution panels. Engineers often struggle to select devices that combine fast protection with straightforward field maintenance in harsh plant environments. This XT2 family member complies with IEC 60947-2 and carries CE conformity, supported by LR and GL certifications for global electrical equipment, along with explicit disassembly guidance for end-of-life. With ABB EcoSolutions framing and a 12.5 A setting range, it supports efficient asset management, regulatory compliance, and lower total cost of ownership. Its front-terminal design and robust short‑circuit ratings help minimize downtime during maintenance.

Product Information

Extended Description

1SDA067614R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 12,5-125 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4013AFF000XXX
E-Number (Norway)
4379607
EAN
8015644015107
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015107
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.05 W
Rated Current (In)
12.5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
125 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
8.75...12.5 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
4P fixed front-terminal design with a TM release streamlines installation and servicing, while the 8.75–12.5 A setting range lets you tailor protection to motor and feeder loads. In practice, technicians save time on wiring checks and field adjustments, reducing commissioning cycles and misconfiguration risk. It is well suited for modular panels in manufacturing lines and distribution boards. With a rated current of 12.5 A and rated insulation voltage of 1000 V, the XT2 device handles high fault currents while protecting connected equipment. The Icu and Ics ratings—up to 100 kA across standard voltages—provide robust short-circuit protection, limiting damage to downstream gear and improving plant uptime. Front terminals use a 6 N·m tightening torque and support busbars from 32.5 to 100 mm², enabling reliable wiring in tight panels. The XT2 4P footprint aligns with common DIN-rail installations, facilitating retrofits and spare-part compatibility across the SACE Tmax XT family. Compliance and environmental data underpin risk management: IEC60947-2 protection, CE conformity, RoHS/REACH declarations, CMRT, TSCA, and WEEE guidance, plus an environmental product declaration (EPD) for Tmax XT XT2 TM. Lifecycle and recycling advantages include a 55.70% recyclability rate aligned to EN45555, end-of-life disassembly instructions, and packaging disposal guidance, helping meet sustainability targets while maintaining a low total cost of ownership.

Get a Quick Quote for a ABB 1SDA067614R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067614R1? Enquire Now

FAQs

Install with front terminals, connect busbars sized 32.5 to 100 mm², and tighten to 6 N·m. Use an M6 screwdriver and follow the XT2 installation instructions to ensure proper alignment, secure mounting, and proper clearance for access and future maintenance.
Rated current is 12.5 A, rated voltage 690 V, insulation voltage 1000 V, and Ics/Icu ratings up to 100 kA depending on voltage. Setting range is 8.75 to 12.5 A, with a 30 ms opening time for SOR/UVR configurations, ensuring fast, selective protection.
Yes. The 4P XT2 device supports high fault currents, 690 V operation, and front-terminal wiring ideal for MCCs and transformer feeders. Its precise setting range and robust short-circuit protection help minimize downtime and prevent downstream equipment damage.
Key references include IEC 60947-2, CE conformity, LR and GL certificates, and documentation for RoHS/REACH, CMRT, TSCA, and WEEE. An EPD is available for Tmax XT XT2 TM, supporting sustainability and regulatory compliance across global deployments.
The device offers a recyclability rate of 55.70% per EN45555, disassembly instructions for end-of-life, and packaging disposal guidance. These factors support sustainable procurement and align with ABB EcoSolutions targets while preserving low total cost of ownership.