ABB 1SDA067616R1 Moulded Case Circuit Breaker - XT2H 160 TMD 4P IEC60947-2
Part Number: 1SDA067616R1
Quick Summary
Moulded Case Circuit Breaker is a protective device that interrupts power in industrial machinery and control panels. Engineers often confront space constraints and the need for rapid maintenance; this XT2H model with front terminals simplifies installation and reduces downtime across panel builds. Key certifications include CE conformity (EC Declaration of Conformity Tmax XT2), IEC 60947-2 compliance, and LR and GL certificates that validate safety and reliability in industrial and marine environments. The solution also aligns with RoHS and REACH declarations, delivering steady protection while enabling efficient serviceability and lifecycle cost reduction. In modern automation projects, the combination of compact form factor, clear wiring access, and robust protection supports faster commissioning and smoother plant operations.
Product Information
Extended Description
1SDA067616R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 20-300 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4020AFF000XXX
E-Number (Norway)
4379609
EAN
8015644015121
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015121
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.62 W
Rated Current (In)
20 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
300 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
14...20 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal, fixed four-pole design with TM release simplifies wiring and service access. Business Impact: Reduces installation time and minimizes fault risk during maintenance. Application: Ideal for control panels and machine protection in automation lines. Feature: Setting range 14…20 A with 20 A nominal rating and 690 V operational voltage. Business Impact: Provides precise tailoring of overload protection for motors and transformers while maintaining system safety. Application: Data centers and process automation where current coordination matters. Feature: High Icu of up to 100 kA and Ics up to 70 kA depending on voltage, along with Ui of 1000 V and Ur of 690 V. Business Impact: Delivers strong short-circuit resilience and robust insulation margins, reducing the risk of cascading faults. Application: Medium-to-large switchgear protecting critical feeders. Feature: Electrical durability rated at 120 cycles/hour and 8000 total cycles; mechanical durability rated 240 cycles/hour and 25000 total cycles. Business Impact: Extends service life in frequent switching applications and minimizes replacement costs. Application: Manufacturing lines with frequent start/stop sequences. Feature: RoHS/REACH compliance, EPDs, and environmental data including close-loop recyclability. Business Impact: Supports sustainability reporting and regulatory compliance while reducing end-of-life costs. Application: Green mandates in industrial facilities and multi-site deployments. Feature: Compact dimensions (120 mm W x 130 mm H x 82.5 mm D) and front-terminal bolt connections with 6 N·m tightening torque. Business Impact: Facilitates retrofit into limited cabinet space and ensures reliable assembly. Application: Modernization projects and panel upgrades where space is at a premium.
Get a Quick Quote for a ABB 1SDA067616R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067616R1?
Enquire Now
FAQs
The ABB 1SDA067616R1 features front-terminal connections with bolt terminals and a four-pole XT2 fixed configuration. It is designed for busbar connections in the 32.5 to 100 mm² range and requires a tightening torque of 6 N·m. This facilitates straightforward panel mounting and rapid servicing without disturbing downstream connections.
Key specs include a rated operating voltage of 690 V, rated insulation voltage of 1000 V, setting range of 14–20 A, and a nominal current rating aligned to 20 A. It provides short-circuit protection with Icu up to 100 kA and Ics up to 70 kA, with a rated frequency of 50/60 Hz. The device also supports front-terminal, bolt-type connections and a 4P configuration.
Yes. The XT2H Tmax XT family is designed for low-voltage protection up to 690 V, with an insulation rating of 1000 V and IEC 60947-2 compliance. Its four-pole front-terminal design and TM release provide coordinated protection for machines, transformers, and feeders in automation environments, while ensuring safe operation under high-voltage conditions.
Key certifications include IEC 60947-2 for low-voltage molded case circuit-breakers, CE conformity via the EC Declaration of Conformity for Tmax XT2, LR and GL certificates, and RoHS/REACH declarations. These ensure safety, interoperability, and environmental compliance across global installations.
The front-terminal design, high durability (up to 25,000 mechanical cycles), and explicit torque specifications simplify installation and servicing, reducing downtime. Certified environmental data (EPD, RoHS/REACH) supports sustainability reporting, while high Icu/Ics ratings improve protection reliability, contributing to lower maintenance costs and faster payback in high-availability automation lines.