ABB 1SDA067618R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067618R1
Quick Summary
ABB 1SDA067618R1 is a four-pole moulded case circuit breaker for protective power distribution. Engineers often face mis-rated devices, difficult front-terminal access, and extended downtime when replacing failed breakers. This XT2 family product supports IEC60947-2 conformity with CE declarations, alongside GL and LR certifications to facilitate global deployments. As part of ABB EcoSolutions, it aligns with RoHS, REACH, and EN45555 recyclability targets to reduce total cost of ownership. Selecting Tmax XT 1SDA067618R1 supports faster installation, improved uptime, and streamlined compliance reporting for critical facilities. This combination of rugged protection, front-terminal access, and detailed environmental data supports procurement teams aiming for safer design audits and lower maintenance costs.
Product Information
Extended Description
1SDA067618R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-320 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4032AFF000XXX
E-Number (Norway)
4379611
EAN
8015644015145
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015145
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.57 W
Rated Current (In)
32 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
320 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
22.4...32 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
The four-pole XT2 Moulded Case Circuit Breaker uses front terminals and a TMD release to deliver fast, predictable fault protection. This reduces arc energy during faults and minimizes downtime, while simplifying wiring in crowded panels. Application: ideal for transformer feeders, main distribution panels, and process lines where space is tight and reliability is mission-critical. A rated current of 32 A with a setting range of 22.4–32 A and a 6 N·m tightening torque for busbars 32.5–100 mm² ensures precise coordination with downstream devices and robust terminal integrity, lowering hotspot risk and rework. Application: AC switchgear and motor protection schemes in 690 V systems. IEC60947-2 conformity and CE declarations, plus RoHS/REACH and EPD data, support regulatory readiness and transparent environmental metrics across global markets. End-of-life support with disassembly instructions, packaging disposal guidance, and front-terminals compatibility reinforce safer retrofit projects and easier maintenance. Compatibility with 32.5–100 mm² busbars, 690 V systems, and a compact footprint aids rapid installation in data centers, manufacturing floors, and power distribution rooms. The XT2’s 120 mm width and 130 mm height with a 82.5 mm depth help preserve cabinet space while delivering reliable protection.
Get a Quick Quote for a ABB 1SDA067618R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067618R1?
Enquire Now
FAQs
For proper installation, ensure the busbar is within 32.5–100 mm² and the wiring uses front-terminal access. Tighten terminals to 6 N·m and secure the device in a compatible enclosure with the 120 mm width, 130 mm height, and 82.5 mm depth. Use M6 screwdriver guidance for Main Circuit connections and verify 690 V operating conditions before energizing.
Key specs include a rated current of 32 A with a 22.4–32 A setting range, rated voltage of 690 V, Ui of 1000 V, and 320 A instantaneous trip setting. It supports Ics and Icu up to 100 kA at common distribution voltages, with 30 ms opening time and 2.57 W per pole power loss. It is a 4P device with front terminals and 6 N·m tightening torque.
Yes. The ABB 1SDA067618R1 carries IEC60947-2 conformity and CE Declaration of Conformity. It also supports RoHS and REACH compliance, with environmental data available via EPDs. UL and VDE certifications are either not required or declared accordingly, depending on regional regulatory needs.
Electrical durability is rated up to 8000 cycles and mechanical durability up to 25,000 cycles, supporting long service life in demanding environments. The unit includes end-of-life information and disassembly instructions to facilitate safe maintenance and recycling, reducing total cost of ownership in retrofit and upgrade projects.
Sustainability data include an Environmental Product Declaration (EPD) for Tmax XT XT2 TM, and a recyclability rate per EN45555 of 55.70%. End-of-life disassembly instructions and packaging disposal guidance are provided to support recycling programs, design-for-closing resource loops, and compliant ESG reporting.