ABB 1SDA067624R1 Automatic Circuit Breaker - IEC60947-2

Part Number: 1SDA067624R1
Manufacturer
ABB
Part number
1SDA067624R1

Quick Summary

Automatic Circuit Breaker ABB 1SDA067624R1 protects electrical circuits in distribution boards and motor control centers. Installers often struggle with cramped wiring and time-consuming terminal access, so this XT2H four-pole model with front terminals speeds assembly and reduces fault-prone wiring. Certified to IEC60947-2 with a CE declaration of conformity, it also carries GL and LR safety certifications, underscoring its reliability for critical power protection. Built for transformer and generator protection scenarios, it supports ABB's EcoSolutions approach and delivers measurable business value through reduced downtime, easier disassembly, and responsible end-of-life handling.

Product Information

Extended Description

1SDA067624R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A NEUTRAL = 50% PHASES
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HEN125BFF000XXX
EAN
8015644015206
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015206
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
625…1250 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, four-pole XT2H design simplifies wiring and maintenance, enabling faster panel assembly and safer servicing in tight spaces. The 4P fixed front terminals also support robust busbar connections for 32.5..100 mm² main circuits, reducing contact resistance and heat buildup. Setting range 87.5–125 A with TMA release provides precise overload protection tailored to transformers and distribution feeders. This reduces nuisance tripping while maintaining protective margins, which translates into fewer unplanned outages and improved efficiency. Operating at 690 V with 1000 V insulation, it is compatible with common industrial systems and DC backup arrangements. Its high Ics up to 100 kA and Ii up to 1250 A ensure robust short-circuit performance across voltages. Electrical endurance of 8000 operating cycles and mechanical endurance of 25000 cycles translate into longer service life in demanding environments. This reduces maintenance costs and improves total cost of ownership. Compact dimensions (120 × 130 × 82.5 mm) and weight about 1.45 kg support space-constrained installations, while a 6 N·m tightening torque on front bolts ensures a reliable, vibration-resistant connection. ABB EcoSolutions and end-of-life considerations, including 55.70% recyclability per EN45555 and disassembly instructions, help meet environmental targets and waste reduction programs.

Get a Quick Quote for a ABB 1SDA067624R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067624R1? Enquire Now

FAQs

Installation requires ensuring the main circuit uses a busbar within 32.5 to 100 mm², connecting through the front terminals and tightening to 6 N·m. Use the M6 recommended screwdriver for all terminal screws and follow the XT2 installation instructions. The unit’s front-terminal design reduces wiring depth and speeds commissioning, while the 4P configuration supports reliable motor control center protection.
The device is rated 125 A, with a rated operational voltage of 690 V AC and 500 V DC, insulation voltage of 1000 V, and a setting range of 87.5–125 A. It supports AC/DC current types, a short-circuit setting range of 625–1250 A, Ics up to 100 kA, and Ii up to 1250 A, consistent with IEC 60947-2 requirements.
Yes, it carries the EC Declaration of Conformity Tmax XT2 (CE). Additional safety certifications in the data set include GL and LR certificates, underscoring risk management and reliability. RoHS and REACH declarations are documented for material compliance, and the product aligns with ABB EcoSolutions for sustainability considerations.
ABB provides disassembly instructions for Tmax XT XT2 TM and packaging disposal information. The product supports an End Of Life program with a recyclability rate around 55.70% per EN45555 and environmental data via the EPD. Use the supplied guidance to simplify removal, recycling, and disposal while minimizing environmental impact.
Expected benefits include reduced commissioning time due to front-terminal access, lower maintenance costs from higher electrical and mechanical durability (8000 and 25000 cycles respectively), and improved reliability with precise setting ranges and high short-circuit capacities. The integration with ABB EcoSolutions also supports waste reduction goals and easier compliance reporting, contributing to lower total cost of ownership.