ABB 1SDA067625R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067625R1
Manufacturer
ABB
Part number
1SDA067625R1

Quick Summary

ABB 1SDA067625R1 is a 4-pole moulded case circuit breaker designed for motor protection and distribution panels. In demanding electrical environments, nuisance trips and wiring complexity can erode uptime and raise maintenance costs. It aligns with IEC 60947-2 and CE declarations of conformity, with GL and LR certificates providing regulatory traceability. With front-terminal mounting, a 160 A rating, and a 690 V operating voltage, it delivers reliable safety and installation efficiency, especially for OEMs and panel builders. This device is well suited for motor feeders, switchgear, and power-distribution panels, offering predictable performance in rugged industrial settings while supporting efficient project timelines.

Product Information

Extended Description

1SDA067625R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A NEUTRAL = 50% PHASES
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HEN160BFF000XXX
EAN
8015644015213
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015213
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.15 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
800…1600 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
112...160 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal 4P XT2 design enables compact, safer panel layouts and simpler wiring, reducing assembly time and wiring errors. Business Impact: Faster commissioning and lower labor costs in control panels and switchgear assemblies. Application: Motor control centers and electric distribution boards benefit from easier maintenance and clearer terminals. Feature: Adjustable instantaneous settingIi from 800 to 1600 A and a setting range of 112–160 A improves selectivity and fault containment. Business Impact: Minimizes downtime and collateral damage during faults, protecting motors and transformers. Application: Large installations with mixed loads and transformer feeders gain targeted protection. Feature: High Icu up to 100 kA and Ui of 1000 V enable robust short-circuit and insulation performance. Business Impact: Enhanced safety margins and reduced risk of arc-flash events in 690 V networks. Application: High-power distribution and switchgear environments. Feature: 690 V rated operational voltage and 160 A rated current support reliable operation across industrial facilities. Business Impact: Consistent protection for critical loads with predictable maintenance. Application: Plant-wide protection schemes and machine protection. Feature: Front-bolt terminals with 6 N·m tightening torque and busbar connection 32.5–100 mm² simplify installation and ensure stable connections. Business Impact: Reduced torque variability and improved reliability in field wiring. Application: New panel builds and retrofit projects. Feature: Lifecycle and environmental information, including End Of Life disassembly instructions, EPDs, and recyclability data, support sustainable design decisions. Business Impact: Lower end-of-life costs and better compliance with circular economy targets. Application: OEMs and system integrators pursuing green procurement and responsible disposal.

Get a Quick Quote for a ABB 1SDA067625R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067625R1? Enquire Now

FAQs

It uses front terminal mounting with bolt terminals and a tightening torque of 6 N·m, designed for 32.5–100 mm² busbars and 120 mm wide by 130 mm high by 82.5 mm deep enclosures, simplifying panel integration.
Rated current In is 160 A;Rated Ultimate Short-Circuit Breaking Capacity Icu is up to 100 kA;Rated Insulation Voltage Ui is 1000 V;Rated Operational Voltage Ur is 690 V (AC) / 500 V (DC).
Yes. Its 4P XT2 design, 690 V rating, adjustable setting range (112–160 A), and 100 kA short-circuit capability make it well suited for motor feeders and distribution boards in industrial switchgear.
It complies with IEC 60947-2; CE Declaration of Conformity; GL and LR certificates; and is supported by end-of-life and recyclability documentation, aligning with modern regulatory and sustainability requirements.
Front-terminal wiring simplifies installation and maintenance; disassembly instructions aid recycling; robust electrical and mechanical durability reduce replacement cycles; and packaging and EPD data support compliant procurement decisions.