ABB 1SDA067626R1 Moulded Case Circuit Breaker - XT2 IEC60947-2

Part Number: 1SDA067626R1
Manufacturer
ABB
Part number
1SDA067626R1

Quick Summary

Moulded Case Circuit Breaker protection for industrial power distribution safeguards equipment and personnel. Customers often struggle to select devices that deliver reliable protection across demanding 690 V systems while keeping wiring and maintenance simple. This ABB XT2 product aligns with IEC 60947-2 and CE declarations, and carries GL and LR certifications for global compliance, helping you meet regulatory requirements without compromising on performance. With a 4-pole front-terminal design, a 125 A rated current, and a selectable instantaneous trip (I_i 625–1250 A) the solution supports compact, scalable protection for motor feeders and distribution panels. By combining robust protection with easy installation and proven sustainability credentials, this MCCB delivers value across engineering, procurement, and maintenance teams.

Product Information

Extended Description

1SDA067626R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A FULLY RATED NEUTRAL
Country of Origin
China (CN)
Lead Time
28 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4125BFF000XXX
E-Number (Norway)
4379617
EAN
8015644015220
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644015220
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
625…1250 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature 4-pole XT2 with front terminals provides a compact and accessible wiring path. Business Impact Simplified installation reduces wiring complexity and minimizes panel assembly time, lowering labor costs. Application Ideal for main feeders and distribution panels in factories and process lines. Feature Adjustable setting range 87.5–125 A with TMA release enables precise overcurrent protection. Business Impact Enables tailored protection for varied loads, improving uptime and reducing nuisance trips. Application Motor feeders and control circuits in automation rooms benefit from reliable, configurable protection. Feature Short-circuit performance up to 100 kA rated ultimate breaking capacity (Icu) for multiple voltages ensures fast fault interruption. Business Impact Limits damage and cascade faults, supporting safer shutdowns and lower repair costs. Application Critical power circuits in machinery and transformers. Feature Front-terminal mounting and 6 N·m tightening torque for secure, service-friendly wiring. Business Impact Facilitates consistent installation quality and repeatable connections, reducing maintenance time. Application Panel assemblies and switchgear with accessible front access. Feature RoHS/REACH compliance and ABB EcoSolutions framework support sustainable design. Business Impact Helps meet corporate sustainability targets while maintaining compliance obligations. Application Design reviews, product recycling programs, and end-of-life planning. Feature 125 A rated current and 690 V operation with 8 kV impulse withstand supports industrial power protection across modern manufacturing lines. Business Impact Delivers reliable protection for high-demand equipment with scalable performance. Application 690 V distribution networks, motor control centers, and substations.

Get a Quick Quote for a ABB 1SDA067626R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067626R1? Enquire Now

FAQs

The unit uses front-terminal connections designed for secure bolt-type wiring. Use busbar sizes from 32.5 to 100 mm² for main circuit connections, tighten each terminal to 6 N·m, and follow the included installation instructions XT2. Ensure correct phase alignment and verify clearances around the device to maintain proper heat dissipation.
Rated current I_n is 125 A, rated insulation voltage U_i is 1000 V, rated operational voltage is 690 V AC / 500 V DC, and the instantaneous short-circuit current setting I_i is 625–1250 A. The device is designed to meet IEC 60947-2 with a short-circuit breaking capacity up to 100 kA depending on system voltage.
Yes. The 4P XT2 MCCB with adjustable I_i provides reliable motor feeder protection, allowing precise coordination with upstream protection. Its front-terminal design simplifies wiring for motor control centers, making it suitable for machine bays, conveyors, and pumps in 690 V networks.
The product features a CE Declaration of Conformity and is supported by GL and LR certificates. It follows IEC 60947-2 standards for low-voltage MCCBs. Additional declarations include ROHS/REACH compliance and ABB EcoSolutions data where applicable.
Plan for routine terminal checks and periodic torque verification (6 N·m). The device supports front-access maintenance, reduces wiring time, and includes disassembly guidance for end-of-life recycling. With robust durability and standardized dimensions, you can expect lower downtime and improved return on investment over a long service life.