ABB 1SDA067644R1 Moulded Case Circuit Breaker - IEC 60947-2 XT2

Part Number: 1SDA067644R1
Manufacturer
ABB
Part number
1SDA067644R1

Quick Summary

ABB 1SDA067644R1 Moulded Case Circuit Breaker protects industrial power distributions by providing reliable overload and short-circuit protection in a compact XT2 3P front-terminal package. Engineers often struggle with space constraints, front-access maintenance, and lifecycle waste, making a compact, serviceable breaker essential. This device aligns with IEC 60947-2 and carries CE conformity along with LR certification, supporting traceability and safety in regulated environments. Designed for ABB SACE Tmax XT families, it enables easy system upgrades and scalable protection in data centers, manufacturing lines, and transformer feed applications. In short, it delivers dependable protection while reducing installation time and total cost of ownership through standardized specs and robust environmental compliance.

Product Information

Extended Description

1SDA067644R1 ABB: C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 63 I3=315...630 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2LE3063BFF000XXX
E-Number (Norway)
4379318
EAN
8015644015404
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644015404
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.85 W
Rated Current (In)
63 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
300…630 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
44.1...63 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The XT2 3P fixed front-terminal design enables straightforward field mounting and front-access servicing, reducing commissioning time and enabling faster fault isolation in control panels. This translates to lower downtime and improved maintenance productivity for critical power distribution applications such as motor feeders and transformer protection in manufacturing plants. Feature → Business Impact → Application: Rated current of 63 A and a rated voltage of 690 V with a setting range of 44.1–63 A provides precise coordination with downstream protection schemes, improving selectivity and limiting collateral outages in complex distribution networks. Feature → Business Impact → Application: High Icu and Ics ratings (up to 150 kA) support reliable fault current interruption in high-energy environments, delivering safer, more selective tripping in substations and panel boards. Feature → Business Impact → Application: Front bolt terminal connections with a tightening torque of 6 N·m simplify installation and vibration resistance, making retrofits and upgrades quicker and more reproducible in existing switchgear. Feature → Business Impact → Application: IEC60947-2 compliance with DoC CE and LR certification along with end-of-life documentation and EPD support regulatory alignment and sustainability goals, reducing compliance risk for audits and customer requirements. Feature → Business Impact → Application: Compact dimensions (90 mm W × 130 mm H × 82.5 mm D) and a weight of 1.1 kg offer space-saving deployment in dense electrical enclosures, enabling scalable protection in tight control panels and distributed busbar systems. Feature → Business Impact → Application: Front-terminal design supports reliable busbar connections (32.5–100 mm²) and a clear maintenance path, improving reliability and reducing commissioning variances in data centers, process lines, and transformer rooms.

Get a Quick Quote for a ABB 1SDA067644R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067644R1? Enquire Now

FAQs

This device uses front bolt terminals with a 6 N·m tightening torque, and it supports busbar connections from 32.5 to 100 mm². With dimensions of 90 mm width, 130 mm height, and 82.5 mm depth, it fits standard XT2 enclosures and permits straightforward retrofits and panel upgrades while maintaining reliable fault isolation and serviceability.
The breaker is rated for 63 A and 690 V, with Ics up to 150 kA, Icu ratings across multiple voltages, and a setting range of 44.1–63 A. It also provides 8 kV rated impulse withstand. Together, these specs enable precise coordination with downstream devices, fast disconnection under fault conditions, and robust transformer or motor protection in medium to high-energy installations.
Yes. The XT2 is compliant with IEC 60947-2, and the product carries a CE declaration of conformity. It also has LR certification, reinforcing safety and traceability for marine and power distribution applications. End-of-life documentation and environmental declarations are available, supporting sustainable procurement and audits.
Yes, it’s designed for protection on transformer feeds within ABB SACE Tmax XT families. Its front-terminal arrangement, 3P configuration, 63 A rating, and high Icu/Ics values enable reliable transformer protection with fast fault clearing, while its compact XT2 form factor simplifies integration into compact switchgear and substations.
The product supports end-of-life disassembly instructions and has an Environmental Product Declaration (EPD) for Tmax XT XT2 TM. Recyclability is specified at 55.70% per EN45555, and there are packaging disposal guidelines. These elements help reduce total cost of ownership and support sustainability reporting and compliance across EHS programs.