ABB 1SDA067647R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067647R1
Quick Summary
ABB 1SDA067647R1 Moulded Case Circuit Breaker provides overcurrent protection for 3-pole, 690 V distribution in industrial facilities. Engineers need compact protection that installs quickly at front terminals while offering reliable trip settings. This device aligns with IEC 60947-2 standards, carries CE conformity via the EC Declaration of Conformity, and supports RoHS/REACH declarations for compliant assemblies. With front-access XT2 design and a 125 A rating, it simplifies panel design, reduces wiring labor, and speeds maintenance. Designed for reliable protection of power circuits in manufacturing, process, and infrastructure panels. The combination of CE/RoHS/REACH compliance and comprehensive documentation supports easy procurement and risk mitigation across global sites. The XT2L 160 TMA variant suits both new builds and retrofit projects, delivering practical protection for critical loads.
Product Information
Extended Description
1SDA067647R1 ABB: C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2LE3125BFF000XXX
E-Number (Norway)
4379321
EAN
8015644695514
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.64 kg
Package Level 1 EAN
8015644695514
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
60…1250 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
8.4...12 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3-pole XT2 fixed-front-terminal design enables fast, secure wiring, reducing installation time and minimizing panel depth constraints, which translates to faster project timelines in new builds and retrofits. This directly improves line uptime and wiring reliability in motor control centers and distribution panels. Feature → Business Impact → Application: Front terminals and the recommended M6 main circuit screwdriver compatibility simplify assembly and maintenance workflows, delivering robust connections with consistent torque and fewer inspection calls. This is ideal for compact switchgear where space is at a premium and service windows are tight. Feature → Business Impact → Application: The adjustable release (TM, setting range 8.4–12 A) supports selective coordination with upstream protections, reducing nuisance trips and enabling safer, more predictable operation in h-traffic data centers and manufacturing lines. Feature → Business Impact → Application: High short-circuit performance ratings (Icu up to 150 kA, Ics up to 150 kA at common voltages) provide reliable shutdown during faults, protecting transformers, feeders, and critical equipment while meeting IEC60947-2 standards. Feature → Business Impact → Application: Low energy loss (11.4 W per pole) combined with RoHS/REACH compliance supports energy efficiency goals and sustainable procurement, suitable for green-building projects and long-term operating cost reductions. Feature → Business Impact → Application: Compact dimensions (90 mm W × 130 mm H × 82.5 mm D) and 1.4 kg weight simplify panel layout, enable easier retrofits, and reduce shipping and handling costs across global sites. The product’s packaging and EPD/eco-information streamline end-of-life planning and recyclability in line with EN45555 guidelines.
Get a Quick Quote for a ABB 1SDA067647R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067647R1?
Enquire Now
FAQs
Install with the front-terminal configuration using a compatible 6 mm torque driver to achieve the 6 N·m tightening torque. Ensure busbars are within the 32.5 to 100 mm² range and align the 3P mounting with fixed XT2 XT2L frames. Verify terminal integrity after wiring and perform a functional check with the TM release to confirm correct trip characteristic.
Key specs include rated current of 125 A, rated voltage of 690 V, and short-circuit ratings Icu up to 150 kA and Ics up to 150 kA at listed voltages. The device supports a setting range of 8.4–12 A, operates with AC/DC current types, and uses a TM TM release. It complies with IEC 60947-2 and features front-terminal connections for easy wiring.
Yes, its 3P XT2 design with a fixed front-terminal layout suits transformer protection in power distribution schemes. The 690 V operating voltage and 150 kA fault-rupture capabilities provide reliable protection against short circuits, while the 8.4–12 A setting range supports selective coordination with upstream protections, minimizing downtime in critical facilities.
The product aligns with IEC 60947-2 standards and CE conformity via the EC Declaration of Conformity. It is RoHS and REACH compliant, with additional LR and GL certificates for extended verification. UL and VDE certifications are noted as no certification needed in this dataset, while the documented RoHS/REACH declarations support global procurement.
With a mechanical durability rating up to 25,000 cycles and electrical durability up to 8,000 cycles, maintenance intervals can be extended compared with lower-end devices. The design reduces wiring complexity and service time thanks to front-terminal access, and the low per-pole power loss (11.4 W) contributes to lower energy costs over the breaker’s lifecycle.