ABB 1SDA067774R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067774R1
Manufacturer
ABB
Part number
1SDA067774R1

Quick Summary

ABB 1SDA067774R1 Moulded Case Circuit Breaker protects 690 V distribution networks in industrial plants. In practice, engineers struggle with fault-driven downtime and wiring complexity; this unit delivers reliable overcurrent protection with front-terminal mounting for quick panel upgrades. It complies with IEC 60947-2 and carries CE conformity along with LR and GL certifications, supporting global installations. The 3-pole XT2 design is tailored for motor protection and shared busbar connections, helping reduce wiring errors and installation time. Using this breaker improves uptime, simplifies maintenance, and aligns with SACE Tmax XT family standards, enhancing overall plant reliability. Additionally, its MF magnetic release and 12.5 A nominal rating fit light-to-moderate motor loads, delivering targeted protection without nuisance trips.

Product Information

Extended Description

1SDA067774R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MF Iu 12,5 A I3=175 A
Country of Origin
China (CN)
Lead Time
28 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3013IFF000XXX
E-Number (Norway)
4379386
EAN
8015644016708
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644016708
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.05 W
Rated Current (In)
12.5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
175 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
MF
Release Type
M
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front terminals with bolt connections and MF magnetic release simplify wiring and speed panel assembly, reducing commissioning time and human error. This translates to lower installation costs and faster scalability for growing automation lines. The 3P XT2 fixed design delivers consistent protection across three-phase feeders, ideal for motor protection in manufacturing and process environments. With a rated operating voltage of 690 V and insulation voltage of 1000 V, it supports safe operation in demanding industrial installations, while the 12.5 A nominal current fits smaller motor applications without oversizing protection. High short-circuit ratings (Ics and Icu up to 100 kA) provide robust safeguarding against surges, improving system reliability and reducing outage duration. The device complies with IEC60947-2 and carries CE, LR, and GL certifications, aiding regulatory compliance. Front-terminal accessibility, 6 N·m tightening torque, and a 1.4 kg form factor simplify installation and maintenance. Design for motor protection workflows reduces downtime during servicing and enhances lifecycle performance in automated lines.

Get a Quick Quote for a ABB 1SDA067774R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067774R1? Enquire Now

FAQs

To install, ensure the panel busbar is compatible with 32.5–100 mm² conductors and that the front-terminal bolt connections are accessible. mount the unit as a fixed, 3-pole configuration, tighten to 6 N·m per terminal, and connect per the wiring diagram for XT2. The front-terminal design enables quicker wiring, reduces assembly errors, and should be paired with proper PPE and lockout-tagout procedures during maintenance.
Key specs include rated current In of 12.5 A, rated operational voltage Ur of 690 V, Ui of 1000 V, and Ics/Icu values up to 100 kA depending on voltage. The device supports AC/DC current types, a 3P configuration, and a front-terminal bolt connection. Ensure compatibility with 32.5–100 mm² busbars and confirm the 6 N·m tightening torque for reliable terminations.
Yes. The XT2 family is designed for motor protection with three-pole XT2 construction and MF release, offering fast opening times (~30 ms) and reliable short-circuit performance. Its 12.5 A nominal rating fits light-to-medium motor loads, while high Icu/Ics ratings provide robust protection for motor feeders in automated lines and packaging equipment.
The device carries an EC Declaration of Conformity, CE marking, and LR and GL certifications, aligning with global regulatory expectations. UL and VDE certifications are listed as not required for this product, while RoHS and CMRT declarations are noted for material compliance and responsible sourcing.
The front-terminal design reduces wiring time during installation and service, contributing to a faster commissioning schedule. The 6 N·m torque specification ensures consistent termination integrity, lowering the risk of loose connections and thermal issues. Lifecycle benefits include predictable maintenance intervals, lower downtime, and alignment with ABB EcoSolutions for responsible asset management.