ABB 1SDA067775R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067775R1
Quick Summary
ABB 1SDA067775R1 Moulded Case Circuit Breaker is a reliable overcurrent protector for 690 V electrical installations. Engineers often face downtime caused by nuisance tripping and complex wiring in motor control panels, which drives project delays and maintenance costs. This device aligns with IEC 60947-2 standards, CE conformity, and ABB certifications such as GL and LR, ensuring traceability and end‑of‑life support. By leveraging the XT Tmax XT platform, it delivers compact, front-terminal installation with precise trip performance, translating to reduced panel space, faster commissioning, and lower lifecycle costs for industrial projects.
Product Information
Extended Description
1SDA067775R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MA Iu 20 A I3=120...280 A
Country of Origin
China (CN)
Lead Time
21 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN) | EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3020MFF000XXX
E-Number (Norway)
4379387
EAN
8015644016715
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.2 kg
Package Level 1 EAN
8015644016715
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.62 W
Rated Current (In)
20 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
120…280 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
MA
Release Type
M
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal design enables straightforward wiring and faster panel assembly. Benefit: Reduces installation time and minimizes wiring mistakes, improving overall project timelines for panel builders and integrators. Application: Suitable for 3P motor protection in switchgear and control cabinets. Feature: 3-pole XT2 with MA magnetic release and a rated current of 20 A, with an instantaneous short-circuit setting of 120–280 A. Benefit: Provides selective tripping and robust fault isolation, lowering unplanned downtime in high-duty motors and drives. Application: Industrial motor feeders and transformer protection in 690 V systems. Feature: Front mounting terminals with a tightening torque of 6 N·m and busbar compatibility (32.5–100 mm²). Benefit: Secure, vibration-resistant connections that maintain performance in demanding environments. Application: Large machinery, process lines, and power distribution panels. Feature: IEC 60947-2 compliance, CE declaration, and ABB EcoSolutions alignment. Benefit: Ensures regulatory compliance and sustainable lifecycle management, including end‑of‑life disassembly and recycling guidance. Application: Global projects with strict safety and environmental requirements. Feature: Compact dimensions (90 mm W × 130 mm H × 82.5 mm D) and weight of 1.1 kg. Benefit: Easier enclosure fitment and reduced enclosure footprint, lowering installation costs. Application: Space-constrained control panels and modular switchgear. Feature: Clear technical documentation and wiring diagrams (XT2 family). Benefit: Accelerates commissioning and reduces commissioning errors. Application: New installations and maintenance activities in industrial facilities. Feature: Iu 160 A rated uninterrupted current and 690 V rated operational voltage. Benefit: Supports continuous operation under load with reliable short-time protection. Application: Heavy-load feeders, transformer protection, and motor circuits. Feature: Recyclability and environmental data (55.70% recycling rate; EPD availability). Benefit: Supports sustainability reporting and compliance with environmental targets. Application: Green manufacturing programs and corporate ESG reporting.
Get a Quick Quote for a ABB 1SDA067775R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067775R1?
Enquire Now
FAQs
For installation, use the front-terminal design with a tightening torque of 6 N·m and busbars sized 32.5 to 100 mm². The unit is 3P with front terminal connections, weighs about 1.1 kg, and should be mounted in a suitable enclosure. Follow the XT2 dimensional guidelines to ensure proper clearance and secure wiring, reducing commissioning time and potential faults.
The instantaneous setting enables selective tripping of the circuit breaker during high fault currents, while avoiding nuisance trips during normal motor inrush. This improves system availability, reduces unplanned downtime, and protects downstream equipment. It is particularly beneficial in motor feeders and transformer protection within 690 V networks.
Yes. The product adheres to IEC 60947-2 standards and carries a CE declaration of conformity. Additional certifications include GL and LR certificates associated with the Tmax XT family, supporting safety validation, traceability, and regulatory compliance for global deployments.
This 3P XT2 MCCB is ideal for motor protection, switchgear, and panel boards in industrial facilities. Its front terminals, 690 V operational voltage, and 20 A rated current suit distribution feeders, transformers, and critical motors. Compatibility with busbars and 32.5–100 mm² conductors simplifies integration within existing electrical rooms.
The device features documented disassembly instructions for end-of-life handling and maintenance, along with a durable magnetic release (MA) and reliable trip performance. Warranty terms note that product returns apply under warranty. Overall, the MCCB supports lower maintenance costs through robust protection, extended device life, and easier serviceability in panel assemblies.