ABB 1SDA067858R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA067858R1
Quick Summary
Moulded Case Circuit Breaker protects ABB power distributions by interrupting fault currents in industrial power panels. This 3-pole XT2 device is designed for reliable frontline protection in automation and distribution applications, minimizing nuisance trips through precise release settings. If downtime or compatibility concerns arise, front-terminal, fixed-3P configuration simplifies installation and maintenance. The product complies with IEC 60947-2 and bears CE certification, with LR and GL certificates supporting equipment protection and transformer/feed-through protection. By combining robust electrical performance with clear documentation and EcoSolutions support, it helps engineers meet safety standards while reducing total cost of ownership in large-scale switchgear and panel projects. It also supports busbar connections 32.5 to 100 mm² and a tightening torque of 6 N·m for secure assembly.
Product Information
Extended Description
1SDA067858R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 25 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
f1db919e-9a96-4fac-b73a-4076b7e1b2e2 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3025EFF000XXX
E-Number (Norway)
4379429
EAN
8015644017545
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644017545
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.8 W
Rated Current (In)
25 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SDC210100D0206 | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P fixed XT2 design with front terminals reduces wiring complexity and speeds panel assembly. Business Impact: Faster commissioning and lower total cost of ownership through streamlined installation and simpler future upgrades. Application: Power distribution panels in manufacturing lines or utility cabinets benefit from quick, reliable integration. Feature: Ekip Dip LS/I release with UVR option and 30 ms opening time. Business Impact: Precise, predictable tripping improves system safety and minimizes damage to downstream equipment. Application: Critical protection for transformers, generators and feeders in automation schemes. Feature: Busbar connection 32.5..100 mm² with bolt terminals and 6 N·m tightening torque. Business Impact: Secure, low-resistance connections translate to stable current paths and reduced maintenance calls. Application: New builds and retrofits in control rooms and switchgear enclosures. Feature: Low power loss of 0.8 W per pole under rated conditions. Business Impact: Reduced heat generation and cooler panels, increasing reliability and decreasing cooling costs. Application: High-density panels and continuous operation environments. Feature: IEC 60947-2 compliance with CE, LR, GL certifications; EcoSolutions disclosures and end-of-life guidance. Business Impact: Compliance confidence reduces risk in audits and accelerates project approvals. Application: Global installations requiring regulatory alignment and documented sustainability data. Feature: Dimensions and compatibility notes: 90 mm width, 130 mm height, 82.5 mm depth; front-terminal bolt connection supports straightforward mounting. Business Impact: Predictable footprint enables efficient panel layout and spare-part planning. Application: Standalone breakers or modular assemblies in control panels.
Get a Quick Quote for a ABB 1SDA067858R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067858R1?
Enquire Now
FAQs
Yes. The XT2 3P 25A front-terminal configuration is designed for straightforward integration with Tmax XT architecture. It uses compatible bolt terminals and a 6 N·m tightening torque, facilitating retrofit installs without major panel redesigns while maintaining the 690 V operational rating.
Key specs include a rated current of 25 A, rated operational voltage of 690 V, and 50/60 Hz. It provides a rated short-circuit breaking capacity suited to common industrial voltages and a 30 ms opening time with Ekip Dip LS/I release, supporting reliable fault clearance in routine operation.
Ideal for power distribution panels in manufacturing, utilities, and automation environments. Its 3P fixed configuration, front terminals, and compatibility with 32.5–100 mm² busbars make it suitable for transformer and generator protection, main distribution, and equipment protection in spaces demanding reliable, standards-compliant circuit protection.
It complies with IEC 60947-2 and carries CE conformity. Certifications include LR and GL, with DoC and EPD disclosures where applicable, ensuring alignment with global electrical safety and environmental reporting requirements.
The device’s low power loss (0.8 W per pole) reduces heat load and cooling needs, supporting longer panel life and fewer cooling-related outages. Front-terminal design simplifies inspection and replacement, while standardized torque and busbar range streamline spare-part planning and reduce maintenance labor costs over the product life cycle.