ABB 1SDA067859R1 Moulded Breaker - 63A, 690V IEC60947-2

Part Number: 1SDA067859R1
Manufacturer
ABB
Part number
1SDA067859R1

Quick Summary

Moulded Case Circuit Breaker ABB XT2H 160 protects 3‑phase industrial power distribution in panels. Engineers often confront limited space, complex wiring, and the need for fast, reliable trip behavior; this model addresses those pain points with front terminals and a robust trip mechanism. The device complies with IEC 60947-2 and features CE conformity, plus environmental declarations (EPD) that support green procurement. As a member of the SACE Tmax XT family, it offers consistent performance under varying loads while simplifying maintenance. For buyers, this translates into lower downtime, easier field installation, and improved compliance across regional standards, with a clear path to scalable protection in growing electrical infrastructure.

Product Information

Extended Description

1SDA067859R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 63 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
11164a43-b119-4677-9283-572494d8ba28 Italy (IT)
Simplified SCIP
b74862b9-c03d-4d0f-9a99-dc49c4fb3f34 Germany (DE) | b73ae5a0-3698-4b9d-9984-96f1c13f7aea France (FR) | dd04f114-b467-4cb4-be9a-cec9f91ee010 Sweden (SE) | 391b3c00-69cf-48d1-b29f-61a136cc6492 Poland (PL) | ab4608a7-bf91-4c98-9988-07cddaef470f Norway (NO) | 07256526-45e5-4870-88ac-fa2fc33d221b Finland (FI) | 7dc9bd17-fc56-429b-9f98-9d1296e57848 Netherlands (NL) | 5f39a986-9789-42fc-bb57-4a628bdcd5a7 Germany (DE) | 4a4da4c3-ec2d-4206-ad9d-b8e3fca4244a Denmark (DK) | cf3aca86-9235-4d37-88eb-60316eb00fa4 Netherlands (NL) | 084f66b4-6662-4c45-85e8-0c9533f28f00 Estonia (EE) | acce6e6e-d116-4727-a886-ed1619436f67 Greece (GR) | 118f7b51-d7c9-44dc-9e1b-c1d6a95614f7 Portugal (PT) | 10d7dc16-8f27-4f8f-af40-682e193d3efc Germany (DE) | cec58a95-b7d5-4841-a7ca-c8ef31fb5876 Croatia (HR) | de829ca0-f6a7-4c18-adb4-bc7ab5476479 Czech Republic (CZ) | 7912686b-2080-4ec2-9914-83be697e1f35 Poland (PL) | 194546f9-f305-4115-8b66-c7762fa5fa94 Netherlands (NL) | 9572a023-59e4-479d-9892-74edf91df2ce Germany (DE) | aeec9433-585f-4c26-bea4-da2d6772d615 Germany (DE) | c9832520-2368-4713-aab8-4943a23d0def France (FR) | fcb18477-25ba-4740-9c6f-8a95ab422316 Netherlands (NL) | 6159f85e-9c96-4cea-837b-ed4119bcd9ee Spain (ES) | d5bd8e2f-aa3b-4c8d-bfac-73a426c5ccf4 Netherlands (NL) | dbbaaa22-92bc-485c-b378-1a37e3a77d6d Bulgaria (BG) | 2e63445f-a6af-4490-82d7-a2b48d48b1c3 Sweden (SE) | 16f6c309-f229-4a6a-9693-13320a364ec7 Poland (PL)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3063EFF000XXX
E-Number (Norway)
4379430
EAN
8015644017552
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.702 kg
Package Level 1 EAN
8015644017552
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.7 W
Rated Current (In)
63 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SDC210100D0206 | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal, fixed 3-pole configuration with solid-state EKIP Dip LS/I release. Business Impact: Reduces wiring complexity and simplifies serviceability, accelerating installation and maintenance. Application: Ideal for standard distribution panels and transformer feeders in industrial plants. Feature: 63 A rated current with 690 V rated operational voltage. Business Impact: Provides reliable protection for medium-load circuits while supporting common European power systems. Application: Protective device for 3P electrical networks in manufacturing lines and distributing panels. Feature: 8 kV rated impulse withstand and IEC 60947-2 conformity. Business Impact: Enhances safety margins and ensures regulatory compliance in harsh industrial environments. Application: Critical for life-safety and process-critical protection schemes. Feature: Front-terminal copper-bolted connections, tightening torque 6 N·m, recommended screwdriver M6. Business Impact: Fast, secure terminations minimize installation errors and improve vibration resistance. Application: Suitable for dense switchgear assemblies where space and reliability matter. Feature: 160 cycles/hour electrical durability, 25,000 cycles mechanical durability. Business Impact: Extends service life and reduces replacement risk in high-cycle applications. Application: High-usage motor control centers and automated lines. Feature: 3P XT2 sub-type with Ekip Dip LS/I release, 30 ms opening time. Business Impact: Quick, predictable fault clearance reduces arc flash exposure and equipment damage. Application: Critical protection for transformers and feeder circuits in manufacturing facilities. Feature: Compliance and environmental data (EPD, CMRT, RoHS, REACH). Business Impact: Supports sustainability reporting and regulatory adherence while maintaining performance. Application: Procurement-ready for green projects and global supply chains.

Get a Quick Quote for a ABB 1SDA067859R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067859R1? Enquire Now

FAQs

This unit uses front bolt terminals designed for busbar connections and supports 32.5 to 100 mm² conductors. Tightening torque is 6 N·m, and the recommended screwdriver is M6 for main circuit terminations. The front-terminal design simplifies wiring inside panels and enables faster commissioning with consistent connection quality.
Key specifications include a rated current of 63 A, rated operational voltage of 690 V, and a rated impulse withstand voltage of 8 kV. It meets IEC 60947-2 standards and delivers a rated service short-circuit breaking capacity appropriate for multi-voltage configurations, ensuring reliable protection across typical industrial feeders.
Yes. With 3P configuration, front terminals, and 63 A at 690 V, it suits transformer protection and motor feeder applications. The EKIP Dip LS/I release provides fast, deterministic tripping, while the device’s durability (up to 25,000 mechanical cycles) supports frequent switching in automated lines.
The breaker carries CE conformity with DoC for Tmax XT2, IEC 60947-2 compliance, and environmental declarations (EPD). These certifications help with regulatory approvals, sustainability reporting, and enterprise-grade procurement requirements.
The front-terminal design reduces wiring time and field errors, while 6 N·m tightening torque ensures reliable terminations over time. Electrical durability of 120 cycles per hour and mechanical durability of 240 cycles per hour translate to longer service life in demanding environments, lowering downtime and replacement costs.