Moulded Case Circuit Breaker ABB 1SDA067860R1 provides protective switching for 690 V distribution panels. Engineers face space constraints and complex wiring when upgrading protection, and this unit simplifies installation while delivering reliable fault interruption. The device aligns with IEC 60947-2, CE conformity, and GL certification, reinforcing safety and regulatory compliance for industrial installations. From sustainable packaging to recyclability metrics, this model supports responsible procurement and lifecycle cost reductions. Designed for ABB EcoSolutions, it integrates with Tmax XT family components to streamline maintenance, spare parts, and technician training. This combination reduces downtime by enabling faster diagnostics and compliant upgrade paths in electrical rooms.

Product Information

Extended Description

1SDA067860R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 100 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
9512b584-8a0b-4802-9d07-3cef32550cce China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3100EFF000XXX
E-Number (Norway)
4379431
EAN
8015644017569
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.712 kg
Package Level 1 EAN
8015644017569
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.2 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SDC210100D0206 | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal design with three fixed poles and a solid-state EKIP Dip LS/I release enables straightforward front-access wiring and fast, reliable tripping. This reduces commissioning time and minimizes wiring errors in switchgear installations. It is well suited for MCCs and distribution panels where accessibility and rapid fault clearance are critical. Rated at 100 A and 690 V with 100 kA service withstand (Ics) and 100 kA ultimate breaking capacity (Icu) across applicable voltages, this breaker provides robust protection for demanding loads and transformer feeders. It supports safe interruption at high fault currents, reducing equipment damage and downtime in critical processes. Busbar connections 32.5 to 100 mm² offer flexible feeder configurations and easier retrofit in existing switchgear. Combined with front terminals, standard bolt connections, and a recommended M6 screwdriver, installation is faster and less error-prone. Tightening torque of 6 N·m ensures secure, vibration-resistant terminations, while a front-connection design simplifies field maintenance. The bolt terminal arrangement supports reliable, serviceable terminations in compact layouts, minimizing rework during upgrades. Environmental and regulatory compliance is built in with REACH and RoHS declarations, plus an EPD for Tmax XT XT2 ELT. A recyclability rate of 55.70% per EN45555 and end-of-life disassembly guidance support sustainable procurement and ESG reporting. Product dimensions and weight help with panel planning: 90 mm width, 130 mm height, 82.5 mm depth, and a net weight of 1.4 kg. Packaging includes a Level 1 unit box with 130x208x145 mm footprint and a gross weight of 1.712 kg, aiding logistics and stocking. Standards and compatibility are ensured by IEC 60947-2 compliance, CE declaration, and GL/LR certificates. The product is designed for front-terminal connections in 3P fixed configurations and supports Tmax XT ecosystems for streamlined maintenance, spare parts, and technician training.

Get a Quick Quote for a ABB 1SDA067860R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067860R1? Enquire Now

FAQs

Install the 1SDA067860R1 as a fixed 3P unit using front terminals for accessibility during maintenance. Tighten all connections to 6 N·m with a Main Circuit M6 screwdriver, and connect busbars in the 32.5 to 100 mm² range. This configuration minimizes wiring errors and speeds commissioning in modern switchgear.
The breaker offers 100 A current rating, 690 V voltage, and Ics/Icu up to 100 kA, enabling safe interruption of high fault currents typical in MCCs and transformer feeders. The EKIP Dip LS/I solid-state release provides reliable tripping, while front terminals facilitate fast servicing and reduced downtime.
Key certifications include IEC 60947-2 compliance and CE declaration of conformity for Tmax XT2. Additional certifications noted are GL and LR, with RoHS and REACH declarations. An EPD is available, and recyclability is indicated per EN45555, supporting sustainability and regulatory requirements in global deployments.
High reliability and rapid Ekip Dip LS/I operation reduce unplanned downtime and maintenance time. Front-access terminals simplify servicing, and a robust 6 N·m torque ensures durable terminations. End-of-life documentation and recyclability data support ESG reporting, contributing to lower lifecycle costs and improved procurement value over time.
Documentation includes installation instructions for XT2, wiring diagrams for XT1–XT4, and the SDC210100D0206 technical characteristics sheet. The EC CE DoC, GL LR certificates, and end-of-life disassembly guidance provide comprehensive references for commissioning, maintenance, and compliant disposal.