ABB 1SDA067867R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067867R1
Manufacturer
ABB
Part number
1SDA067867R1

Quick Summary

ABB Moulded Case Circuit Breaker protects electrical panels by delivering fast fault interruption for industrial distribution. Engineers often struggle with space constraints and wiring complexity when upgrading protection gear, making front-terminal, easily serviceable devices essential. This model aligns with key standards and sustainability programs, including IEC 60947-2 conformity with CE declarations and ABB’s EPD support, while RoHS compliance is documented. As part of the SACE Tmax XT family, it delivers robust low-voltage protection with a clear path to modular deployment in modern automation, panel optimization, and transformer protection schemes. The result is safer commissioning, reduced downtime, and lower lifecycle costs for panel builders and maintenance teams.

Product Information

Extended Description

1SDA067867R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 10 A
Country of Origin
China (CN)
Lead Time
52 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
2900d2df-4a08-412a-a938-7185a46461d8 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3010FFF000XXX
E-Number (Norway)
4379438
EAN
8015644017637
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644017637
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: 3P fixed-front-terminal design simplifies wiring and reduces field wiring errors, enabling faster panel assembly and safer maintenance in dense control cabinets; Leading to lower commissioning time and improved reliability in production lines. Feature → Ekip LSI release provides precise, selective tripping and enhanced protection coordination, minimizing nuisance trips and protecting critical loads in distribution boards and motor control centers. Feature → 690 V AC rated insulation and 10 A nominal current ensures compatibility with standard low-voltage distributions while maintaining safety margins across industrial environments, reducing retrofit risk during plant modernization. Feature → Front terminal connections with 6 N·m tightening torque and busbar compatibility from 32.5 to 100 mm² deliver flexible installation and solid mechanical performance, supporting various incoming conductors and simplifying upgrades. Feature → 3 poles in XT2 configuration delivers coordinated protection for multi-line feeders, enabling safer, space-efficient protection schemes in switchboards and MCCs. Feature → IEC 60947-2 compliance, CE declaration, and RoHS/EPD documentation provide regulatory confidence and sustainability alignment for procurement and compliance teams. In practice, these specifications translate into measurable efficiency gains, safer maintenance intervals, and a clear ROI path for standardizing on ABB Tmax XT components across global plants.

Get a Quick Quote for a ABB 1SDA067867R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067867R1? Enquire Now

FAQs

This model supports front-terminal connections and busbar ranges from 32.5 to 100 mm², enabling straightforward integration into common switchgear. It ships with a 6 N·m tightening torque specification and main-circuit M6 tooling guidance, reducing field rework. It is designed for 690 V AC systems and 3P configurations, making it suitable for panel-integration in new builds or retrofits.
Key specs include a rated current of 10 A, rated voltage of 690 V AC, and a service short-circuit breaking capacity Ics of up to 100 kA. The device delivers an uninterrupted current of 160 A (Iu) and a 3P XT2 configuration with Ekip LSI release. These values support safe protection of low-voltage distribution circuits and motors within typical industrial plants.
Yes, the unit is designed for panel protection in industrial distribution contexts, with 690 V AC rating and XT2 family characteristics that support rigorous protection coordination. It features Ekip LSI for reliable tripping and front-terminal access, making it practical for spaces with tight layouts and frequent maintenance in IT-friendly mechanical rooms or control panels.
The product carries a CE declaration of conformity for Tmax XT2 and IEC 60947-2 compliance. ABB provides Environmental Product Declarations (EPD) and RoHS declarations, supporting sustainability and regulatory requirements. There is no UL or VDE certification needed for this model, as indicated by related certificates in the supplier data.
Lead time is listed at 52 days, reflecting Make-To-Order considerations for this ABB XT2 variant. Packaging follows standard single-unit Level 1 packaging with a 130 mm width and 208 mm height footprint, and the unit is identified by EAN 8015644017637. Minimum order quantity is 1 piece, with packaging designed for safe transport to panel builders and installers.