Quick Summary

ABB 1SDA067876R1 is a moulded case circuit breaker for three‑phase protection in industrial switchgear. This solution addresses the common challenge of sourcing a reliable, front‑terminal MCCB that fits limited panel spaces without compromising protection. It aligns with CE conformity and IEC 60947‑2 standards, and sits within the Tmax XT family for consistent lifecycle support. With a 160 A rating and 690 V operating voltage, it delivers robust short‑circuit protection in demanding environments. The design emphasizes installation efficiency, lifecycle transparency, and ease of procurement for OEMs and maintenance teams. In applications such as data centers, manufacturing lines, and power distribution cabinets, this model delivers durable, standards‑driven protection with clear value in uptime and safety.

Product Information

Extended Description

1SDA067876R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 160 A
Country of Origin
China (CN)
Lead Time
28 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
ba908fa0-b2f4-4c27-944c-d5a9a5b87f68 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3160GFF000XXX
EAN
8015644017729
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644017729
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3‑pole XT2H architecture with 160 A rated current provides predictable protection for 3‑phase loads, reducing unplanned downtime and equipment damage in distribution panels. This translates to improved line uptime and lower maintenance costs in manufacturing plants and process facilities. Feature → Business Impact → Application: Front terminal connections and bolt terminals enable straightforward wiring and reliable termination, cutting installation time and reducing wiring faults in new builds and panel upgrades. Feature → Business Impact → Application: Busbar connection range from 32.5 to 100 mm² accommodates common European and global busbar sizes, supporting quick retrofits and flexible panel design across various OEM platforms. Feature → Business Impact → Application: Ics up to 100 kA across multiple voltages delivers strong fault‑current protection for transformers, motors, and feeders, minimizing damage and improving safety margins in critical infrastructure. Feature → Business Impact → Application: IEC 60947‑2 compliance, CE documentation, RoHS/CMRT/EPD data, and end‑of‑life instructions ensure regulatory alignment and sustainable lifecycle management for OEMs and integrators. Feature → Business Impact → Application: Tightening torque of 6 N·m and a compact 1.2 kg weight support consistent, vibration‑resistant installations in cabinets subject to mechanical stress, with reliable servicing and spare parts availability for the Tmax XT family. Feature → Business Impact → Application: Release type Ekip LSIG and a 30 ms opening time enable rapid, controlled disconnection during fault conditions, improving protection performance for motors, transformers, and critical loads in industrial plants.

Get a Quick Quote for a ABB 1SDA067876R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067876R1? Enquire Now

FAQs

The unit uses front terminal, bolt connections compatible with 32.5–100 mm² busbars. Use a 6 N·m tightening torque per terminal and ensure busbar corners are clean and square for secure termination. This setup supports quick panel upgrades and reliable wire terminations in 3P distributions.
Rated current is 160 A with rated operational voltage 690 V AC. It provides a rated insulation voltage of 1000 V AC and a rated impulse withstand of 8 kV. Short-circuit capability (Ics) is up to 100 kA across applicable voltages, with a 50/60 Hz supply.
Yes. The device carries CE declarations of conformity for Tmax XT2 and complies with IEC 60947-2 standards. It also aligns with RoHS declarations and provides end‑of‑life disassembly instructions as part of ABB EcoSolutions packaging and lifecycle data.
This model is part of the SACE Tmax XT family and uses front‑terminal mounting suitable for XT2 configurations. Ensure compatibility with your panel’s busbar layout, cage design, and torque specs. Disassembly and replacement follow ABB’s XT installation instructions for consistent performance.
Origin is China (CN) with a lead time of 28 days. The product is not sold as a standard stocked item and is typically quoted as availability and delivery based on current manufacturing schedules.