ABB 1SDA067887R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067887R1
Manufacturer
ABB
Part number
1SDA067887R1

Quick Summary

ABB 1SDA067887R1 moulded case circuit breaker protects low-voltage distribution panels in industrial electrical systems. Engineers often struggle to balance reliable protection with compact, easy-to-service devices in crowded panel spaces. This XT2 3-pole unit meets IEC 60947-2 and CE conformity while offering RoHS and REACH compliance, supporting safe, regulation-aligned operation. For maintenance-heavy environments, the front-terminal design and robust Ekip M-I release simplify installation and service, reducing downtime. In practice, it delivers dependable protection for SACE Tmax XT installations with efficient heat management and lifecycle cost advantages, making it a sound choice for panel builders and end users seeking dependable industrial protection with practical installation benefits.

Product Information

Extended Description

1SDA067887R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-M-I R 32 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3032KFF000XXX
E-Number (Norway)
4379444
EAN
8015644017835
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644017835
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.7 W
Rated Current (In)
32 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip M-I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Release Ekip G-LS/I, Ekip N-LS/I, Ekip M-LIU, Ekip M-I XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: XT2 3P fixed front terminals simplify wiring and service access, reducing panel downtime and installation time in control cabinets and switchgear assemblies; this translates to lower maintenance costs and faster circuit commissioning in industrial plants. Feature → Front terminal, bolt connection, 6 N·m tightening torque supports secure connections for 32 mm² to 100 mm² busbars, enabling reliable protection in compact panels and limiting nuisance tripping due to loose contacts; ideal for motor feeders and transformer protection in process lines. Feature → Rated 32 A and 690 V AC operation with Ics up to 100 kA and Icu up to 100 kA at relevant voltages; business impact is higher system availability and safer fault isolation, suitable for power distribution feeders in manufacturing lines. Feature → Ekip M-I release and EL type provide precise tripping control and fast audible feedback, improving operator awareness and reducing fault-clearing time in high-load drives and critical feeders. Feature → Power loss of 0.7 W per pole minimizes heat generation, contributing to cooler panels and energy efficiency during continuous operation in modern switchgear. Feature → Compliance with IEC 60947-2, CE declarations, RoHS and REACH ensures regulatory readiness for global projects, supporting multi-region deployments and simplifying supplier qualification for OEMs and panel builders.

Get a Quick Quote for a ABB 1SDA067887R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067887R1? Enquire Now

FAQs

This device uses fixed front terminals with bolt connections and a tightening torque of 6 N·m, supporting busbars from 32.5 to 100 mm². It is designed for straightforward panel integration, compatible with standard M6 recommended screwdrivers, and fits in common 3P distribution enclosures to streamline wiring, testing, and commissioning.
Key specs include rated current 32 A, rated voltage 690 V AC, and short-circuit breaking capacity Ics up to 100 kA (depending on voltage). The unit uses Ekip M-I release with a 30 ms trip time and offers electrical durability of up to 8000 cycles, ensuring reliable protection for motor feeders and feeders from transformers.
Yes. As a SACE Tmax XT XT2 family member, it provides multi-pole protection with front-terminal access, high Ics/Icu ratings, and IEC60947-2 compliance, making it appropriate for transformer protection and feeder isolation in industrial switchgear and energy distribution networks.
It carries a CE Declaration of Conformity and RoHS/REACH compliance, with additional references to applicable IEC60947-2 standards. While UL/VDE certificates vary by region, the product supports global deployment through standard-compliant design and sustainability information like EPD and recycling guidance.
Low heat generation (0.7 W per pole) reduces cooling requirements, lowering energy use in continuous operation. The robust mechanical durability (up to 25000 cycles) and front-terminal accessibility cut maintenance downtime, while RoHS/REACH compliance mitigates regulatory risk across regions.