ABB 1SDA067890R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067890R1
Manufacturer
ABB
Part number
1SDA067890R1

Quick Summary

ABB 1SDA067890R1 Moulded Case Circuit Breaker is a compact protective device for main distribution in 690 V industrial networks. Engineers often face the challenge of delivering reliable overload and short-circuit protection without sacrificing space or increasing maintenance downtime. This XT2 family unit aligns with IEC 60947-2 and carries a CE declaration of conformity, with GL and LR certificates supporting global project deployment. The design prioritizes front-terminal wiring and fast, safe tripping, helping maintenance teams reduce downtime. From a business perspective, it lowers total cost of ownership by combining robust protection with sustainable features such as an End-Of-Life disassembly plan and a documented recyclability rate, while remaining compatible with EcoSolutions initiatives and EPD documentation.

Product Information

Extended Description

1SDA067890R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
51f4ab51-eeea-4df7-9c89-081c6e81b4f7 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4010EFF000XXX
E-Number (Norway)
4379693
EAN
8015644017866
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017866
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SDC210100D0206 | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 4P fixed front-terminal design. Business Impact: Simplifies wiring, speeds installation, and reduces on-site risk during maintenance. Application: Ideal for main distribution panels in 690 V systems where quick access and reliable front connections are required. Long-tail keywords: front-terminal MCCB installation, XT2 4P MCCB, 690 V protection. Feature: Ekip Dip LS/I release with 30 ms opening time. Business Impact: Fast, predictable tripping for damage control during faults, minimizing arc flash exposure and equipment damage. Application: Transformer and feeder protection in switchgear. Long-tail keywords: Ekip Dip LS/I, fast trip MCCB, 30 ms release. Feature: 10 A rated current with high breaking capacity. Business Impact: Protects downstream circuits while tolerating short faults, enabling safe feeder design. Application: Low-current feeders feeding control gear in distribution boards. Long-tail keywords: 10 A MCCB, high Ics, 100 kA at 230/240 V. Feature: Energy efficiency and compact footprint. Business Impact: Power loss of only 0.1 W per pole reduces heat rise and cooling needs, supporting energy-saving strategies. Application: Dense panel assemblies with space constraints. Long-tail keywords: low power loss MCCB, compact MCB, energy-efficient protection. Feature: Compatibility with busbars and installation standards. Business Impact: Speeds integration with 32.5–100 mm² busbars and 6 N·m torque for reliable termination. Application: Industrial control panels and machine building. Long-tail keywords: busbar connection, 32.5–100 mm², tightening torque 6 N·m. Feature: Environmental and compliance documentation. Business Impact: Simplifies regulatory approvals with RoHS, REACH, CMRT, and EN45555 recyclability data. Application: Projects demanding sustainability reporting and end-of-life planning. Long-tail keywords: RoHS compliance, EN45555 recyclability, EPD documentation.

Get a Quick Quote for a ABB 1SDA067890R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067890R1? Enquire Now

FAQs

Ensure the busbar is within 32.5–100 mm², mount the unit in the panel with front-entry terminals, tighten the bolts to 6 N·m using a Main Circuit M6 screwdriver, and verify the Ekip Dip LS/I release is seated correctly. Check that the device weight and dimensions fit your enclosure and that wiring follows the circuit diagram for XT2. This minimizes wiring errors and speeds commissioning.
Rated service short-circuit breaking capacity (Ics) is 100 kA for 220/230/240 V, 70 kA for 380/415/440 V, and 15 kA for 690 V. The rated ultimate short-circuit breaking capacity (Icu) matches these values at corresponding voltages, ensuring robust protection for transformer feeders and main distribution paths in mixed-voltage installations.
Yes. The XT2 4P fixed front-terminal design with 690 V rating and high Ics/Icu makes it suitable for transformer protection within low- to medium-voltage distribution assemblies. Its 10 A nominal current and 8 kV impulse withstand provide reliable protection against surges, while its front-terminal layout supports easy primary wiring to transformers and feeders.
It adheres to IEC 60947-2 and includes a CE Declaration of Conformity for Tmax XT2. Additional documentation includes GL and LR certificates, with RoHS and REACH declarations, CMRT, and documented EPD data. UL and VDE certifications indicate no mandatory labeling for certain markets, but the core compliance remains with IEC 60947-2 and CE documentation.
The unit delivers low energy loss (0.1 W per pole), reducing cooling requirements and operating costs in enclosed panels. Front-terminal access simplifies wiring and maintenance, shortening turnaround in updates or fault repairs. The robust XT2 design, along with ECOsolutions and end-of-life instructions, supports lower total cost of ownership over the device lifecycle while maintaining regulatory alignment.