ABB 1SDA067891R1 Moulded Case Breaker - IEC60947-2

Part Number: 1SDA067891R1
Manufacturer
ABB
Part number
1SDA067891R1

Quick Summary

ABB 1SDA067891R1 Moulded Case Circuit Breaker protects power distribution by interrupting faults. Engineers often face nuisance trips, maintenance challenges, and limited space in compact switchgear. This XT2 family device complies with IEC 60947-2 and CE declarations, and carries LR and GL certificates to support global approvals. With front terminals, 4-pole design, and a 690 V rating, it enables safe, scalable protection across industrial panels. Designed for ABB EcoSolutions and retrofit projects, it helps minimize downtime, simplify procurement, and improve overall reliability in power distribution architectures.

Product Information

Extended Description

1SDA067891R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 25 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
d2c1e28e-063d-4d21-91f0-6327cc7025fe China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4025EFF000XXX
E-Number (Norway)
4379694
EAN
8015644017873
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017873
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.8 W
Rated Current (In)
25 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SDC210100D0206 | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 4-pole front-terminal construction enables straightforward wiring and reliable mechanical integrity. Benefit: Reduces installation time and potential miswiring, improving site safety and enabling faster panel commissioning in factories and data centers. Application: New panel builds and retrofit projects where fast, dependable protection is required. Feature: 690 V rated operational voltage and 25 A rated current provide robust protection for medium voltage distribution. Benefit: Enables safe protection of transformers, feeders, and MCCs while meeting common industrial drive and automation loads. Application: Transformer protection in switchgear, motor control centers, and distribution panels. Feature: High fault-current capability with Ics up to 100 kA and Icu down to 15–100 kA depending on voltage. Benefit: Improves selectivity and fault tolerance, reducing arc flash risk and equipment damage. Application: Industrial plants with high short-circuit incidence, including metalworking and process lines. Feature: Front-accessible lever/Release (Ekip Dip LS/I) and standardized tightening torque of 6 N·m. Benefit: Simplifies commissioning and maintenance, ensuring consistent performance and easier field servicing. Application: Routine preventive maintenance in manufacturing lines and facilities with tight space constraints. Feature: Embodied in the XT2 series with IEC 60947-2 compliance, RoHS/REACH declarations, and environmental data (EPD and recyclability). Benefit: Supports sustainable procurement, regulatory alignment, and responsible end-of-life management. Application: Projects targeting green building certifications and compliant lifecycle management.

Get a Quick Quote for a ABB 1SDA067891R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067891R1? Enquire Now

FAQs

For installation, use the front-terminal design with busbars sized 32.5 to 100 mm². Tighten connections to 6 N·m and use an M6 screwdriver. The 4P configuration fits standard MCCBs and switchgear footprints, simplifying retrofit and new panel builds while maintaining safe, accessible wiring and straightforward maintenance.
The device supports Rated Service Short-Circuit Breaking Capacity up to 100 kA and Rated Ultimate Short-Circuit Breaking Capacity up to 100 kA at common voltages. It operates at 690 V and 50/60 Hz, with a rated current of 25 A and 160 A uninterrupted current. These ratings ensure robust protection in high-energy electrical environments.
Yes. The XT2 family is designed for transformer and distribution protection, offering 4P front-terminal mounting, 690 V operation, and high short-circuit withstand. Its 25 A nominal current and 8 kV impulse withstand support reliable transformer protection within standard industrial switchgear and power distribution schemes.
This device carries the EC Declaration of Conformity for Tmax XT2, plus LR and GL certificates, along with RoHS and REACH compliance declarations. It aligns with IEC 60947-2 standards and CE marking, enabling use in global markets and helping meet internal procurement and sustainability requirements.
Electrical durability is rated at up to 8000 cycles and mechanical durability up to 25,000 cycles, supporting long service life in continuous production. The front-terminal design simplifies wiring and maintenance, reducing downtime during replacements. With eco-friendly packaging and disclosed recyclability data, this breaker contributes to lower lifecycle costs and improved total cost of ownership.