ABB 1SDA067896R1 Moulded Case Breaker - IEC60947-2

Part Number: 1SDA067896R1
Manufacturer
ABB
Part number
1SDA067896R1

Quick Summary

ABB XT2H 160 overcurrent protection device for distribution boards and switchgear. Engineers seek dependable protection with easy wiring and minimal downtime; this model delivers with front-terminal access, a solid-state release, and a robust design that reduces maintenance cycles. The product aligns with CE conformity and IEC 60947-2 standards, with LR and GL certifications within the Tmax XT family to support global installations. By leveraging the SACE Tmax XT platform, this breaker integrates into compact, highly coordinated power-distribution schemes, delivering predictable protection while lowering total cost of ownership through efficient installation and durable performance.

Product Information

Extended Description

1SDA067896R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-I R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4010JFF000XXX
E-Number (Norway)
4379698
EAN
8015644017927
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017927
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, 4-pole XT2H 160 with Ekip I release provides faster, safer wiring and straightforward service access, improving panel build times and minimizing field faults. The 10 A rated current paired with up to 100 kA Ics (depending on voltage) ensures reliable fault clearance without unnecessary tripping, safeguarding downstream equipment and reducing unplanned downtime. Busbar compatibility (32.5 to 100 mm²) and a 6 N·m tightening torque support durable, vibration-resistant connections in challenging environments, while the 690 V rated operational voltage and 8 kV impulse withstand enable safe operation in modern industrial plants. Compact dimensions (120 mm W, 130 mm H, 82.5 mm D) and a 1.6 kg weight enable dense installation in control cabinets, saving space and material costs. The design also emphasizes sustainability with end-of-life disassembly guidance and a design-for-closure resource loop approach (55.70% recyclability per EN 45555) and comprehensive RoHS/REACH compliance, aligning with enterprise sustainability goals. Global approvals, including CE Declarations of Conformity, LR and GL certificates, support regulatory readiness and service continuity across regions. In short, this XT2H 160 offers reliable protection, installation efficiency, and lifecycle cost savings for power distribution and switchgear applications.

Get a Quick Quote for a ABB 1SDA067896R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067896R1? Enquire Now

FAQs

Install using front-terminal connections designed for bolt-type terminals. Use busbars between 32.5 and 100 mm² and tighten to 6 N·m. The 120 mm width and 130 mm height enable compact mounting; ensure correct positioning for 4P operation and verify IEC 60947-2 compliance in accordance with the installation instructions.
Rated service short-circuit breaking capacity (Ics) at 690 V is 15 kA, with higher Ics values at lower voltages (e.g., 100 kA at 220–240 V and 380–415 V variants). This supports coordination with upstream devices while maintaining safety margins under fault conditions.
Yes. It is rated for 690 V AC operation with a 1000 V insulation rating, designed for motor control centers and distribution panels. The 4P configuration and Ekip I release provide precise motor protection and reliable shutdown in industrial settings.
This device supports CE conformity with Declaration of Conformity for Tmax XT, IEC 60947-2 compliance, and LR/ GL certifications included in the Tmax XT family, ensuring regulatory readiness and global acceptance across processes and facilities.
Front-terminal access reduces wiring time and field fault potential, while modular 4P design and solid-state Ekip I release improve reliability. Documentation for end-of-life disassembly and recycling supports sustainability goals and can lower total cost of ownership through easier maintenance and replacement planning.