ABB 1SDA067897R1 Moulded Case Circuit Breaker - XT2 4P
Part Number: 1SDA067897R1
Quick Summary
ABB 1SDA067897R1 Moulded Case Circuit Breaker protects industrial power distribution networks. Downtime from nuisance trips and difficult maintenance is a common pain point in busy electrical rooms, slowing production and increasing costs. This device aligns with IEC 60947-2 standards, carries CE conformity, and supports RoHS/REACH environmental compliance, enabling easier audits. As part of ABB's SACE Tmax XT family, it offers front-terminal installation, modular protection, and scalable control for motor control centers and distribution panels, helping engineers meet safety, reliability, and energy-management goals.
Product Information
Extended Description
1SDA067897R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-I R 25 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4025JFF000XXX
E-Number (Norway)
4379699
EAN
8015644017934
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017934
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.8 W
Rated Current (In)
25 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole, fixed-front-terminal design of the Tmax XT2 MCCB. Business Impact: simplifies installation, reduces wiring errors, and accelerates maintenance in crowded panels. Application: motor-control centers and feeder circuits in manufacturing lines. Feature: 25 A rated current and 690 V operating voltage with a robust short-circuit rating up to 100 kA. Business Impact: dependable overload and fault protection, supporting IEC60947-2 compliance and safe coordination with upstream devices. Application: medium-size loads in process plants and power distribution panels. Feature: Ekip I release with fast opening times (~30 ms in SOR/UVR modes). Business Impact: rapid fault isolation minimizes arc energy and downtime. Application: critical loads such as CNC machines and conveyors. Feature: Front-terminal, bolt-type connections with busbar compatibility (32.5–100 mm²) and 6 N·m tightening torque. Business Impact: secure terminations, reduced maintenance intervals, and vibration resistance. Application: retrofit or new-build switchgear installations. Feature: Environmental and compliance data including RoHS/REACH declarations, EPDs, disassembly guidance, and recyclability metrics. Business Impact: supports sustainability reporting and end-of-life planning. Application: global deployments with ESG targets. Feature: Compact footprint (120 mm W x 130 mm H x 82.5 mm D) and weight 1.6 kg plus packaging data; 1 piece MOQ. Business Impact: minimizes enclosure space and logistics costs. Application: panel builders and space-constrained electrical rooms.
Get a Quick Quote for a ABB 1SDA067897R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067897R1?
Enquire Now
FAQs
Install as a four-pole, fixed-front-terminal device with bolt terminals. Use a main circuit screwdriver of size M6 and tighten to 6 N·m. Compatible with busbars 32.5–100 mm² and suitable for front-entry panel mounting in MCCs and switchgear.
Yes. It features a rated operational voltage of 690 V AC, 50/60 Hz, and a high impulse withstand capacity (8 kV), making it appropriate for industrial power distribution and motor protection.
Rated service short-circuit breaking capacity (Ics) up to 100 kA across several voltages (e.g., 220–240 V variants) and 70–65 kA for higher voltage ranges, ensuring robust protection for feeders and motors.
It adheres to IEC 60947-2, with CE Declaration of Conformity. Compliance also covers RoHS and REACH, TSCA where applicable, and provides EPDs for environmental reporting.
Product net dimensions are 120 mm W × 130 mm H × 82.5 mm D with a net weight of 1.6 kg. Packaging level is one piece per box, with each unit sharing the same EAN 8015644017934 for traceability.