ABB 1SDA067899R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067899R1
Quick Summary
ABB 1SDA067899R1 is a 4-pole moulded case circuit breaker designed for main power distribution in industrial facilities. The challenge is delivering reliable protection in compact enclosures while simplifying installation and maintenance. Certified to IEC 60947-2, the product carries a CE Declaration of Conformity, along with LR and GL certifications that support global deployments. This unit is aligned with ABB EcoSolutions and the SACE Tmax XT family, offering front-terminal wiring, compatible busbar connections, and 690 V system suitability. By combining robust protective performance with straightforward wiring and recycling considerations, it helps engineers meet safety, efficiency, and sustainability targets in modern power distribution gear.
Product Information
Extended Description
1SDA067899R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-I R 100 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4100JFF000XXX
E-Number (Norway)
4379701
EAN
8015644017958
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017958
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.2 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal, fixed XT2 design. Business Impact: Facilitates faster wiring and cleaner panel layouts, reducing installation time and wiring errors. Application: Ideal for space-constrained control panels in manufacturing lines where quick commissioning is critical. Feature: 4P, 100 A rated current at 690 V. Business Impact: Supports high-power distribution with reliable protection while minimizing busbar congestion. Application: Main distribution boards and transformer protection in process industries. Feature: High short-circuit capability. Business Impact: Delivers reliable interruption for fault conditions across a range of voltages, reducing downtime and component damage. Application: Protection for motors, feeders, and transformer circuits in medium-voltage environments. Feature: Ekip I solid-state release and UL/IEC compatibility. Business Impact: Enhances selectivity and fast tripping with proven reliability, while meeting global standards. Application: Systems requiring precise tripping curves and regulatory compliance in multi-national facilities. Feature: Environmental and life-cycle considerations. Business Impact: Provides documented EPD, RoHS/REACH compliance, and a 55.70% recyclability rate, supporting sustainability goals. Application: Design-for-disassembly planning and responsible end-of-life management for plant-wide upgrades.
Get a Quick Quote for a ABB 1SDA067899R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067899R1?
Enquire Now
FAQs
The XT2 4P fixed front-terminal design simplifies wiring by allowing direct busbar connections and front-access wiring. Use 32.5–100 mm² busbar sizes and torque the terminals to 6 N·m to ensure reliable contact and vibration resistance in panel-mounted assemblies.
Rated current is 100 A, rated operating voltage is 690 V, insulation voltage is 1000 V, and the unit provides short-circuit protection up to 100 kA depending on voltage. It supports 50/60 Hz operation with a 4-pole configuration for robust distribution protection.
Yes. It is designed to IEC 60947-2 standards and carries a CE Declaration of Conformity, with LR and GL certifications backing global deployment and compliance across regional markets.
It belongs to the Tmax XT family with the Ekip I release, offering reliable tripping performance, front-terminal wiring, and compatibility with XT2 disassembly and installation practices, ensuring smooth integration into existing Tmax XT-based protection schemes.
The unit supports RoHS and REACH declarations, provides an Environmental Product Declaration (EPD) for Tmax XT XT2 ELT, and has a recyclability rate of 55.70% per EN 45555, with disassembly instructions to aid end-of-life planning.