ABB 1SDA067902R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for industrial switchgear and control panels. In busy plants, nuisance trips and wiring complexity can drive costly downtime and lengthy commissioning. This device aligns with IEC60947-2 and CE conformity, with GL and LR certifications supporting safe, regulator-complaint deployment. Designed to complement SACE Tmax XT systems and ABB EcoSolutions programs, it helps engineers meet evolving safety and environmental requirements while simplifying procurement. With 690 V AC operation, a 10 A rating, and front-terminal access, the XT2H 160 fixed 4P model delivers scalable protection for modern automation architectures and OEM panel builds.

Product Information

Extended Description

1SDA067902R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4010FFF000XXX
E-Number (Norway)
4379703
EAN
8015644017989
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644017989
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Ekip LSI solid-state release → Business Impact: Fast, selective tripping with reduced nuisance trips → Application: Machine control panels and process lines where quick fault clearance is essential. Feature: 4P front-terminal design → Business Impact: Simplified wiring and dependable busbar connections → Application: New switchgear assemblies and retrofit installations requiring robust front-access terminals. Feature: 10 A rated current and 690 V AC rating → Business Impact: Safe handling of typical industrial loads while maintaining high voltage protection margin → Application: Power distribution in machinery and process controls. Feature: Front terminal, bolt connection, tightening torque 6 N·m → Business Impact: Secure, vibration-resistant connections reducing maintenance and warranty claims → Application: Industrial installations subject to mechanical stress. Feature: Compliance with IEC60947-2 and RoHS/REACH/CMRT eco-stewardship → Business Impact: Regulator-ready deployments with lower environmental impact and easier end-of-life handling → Application: Global projects seeking sustainable, standards-aligned protection. Feature: Power loss 0.10 W per pole → Business Impact: Lower energy waste in idle states and extended panel efficiency → Application: Energy-conscious data centers and continuous process lines. Feature: Busbar connection range 32.5–100 mm² → Business Impact: Flexible wiring options supporting various panel configurations → Application: Retrofit and new builds using common busbar sizes. Feature: 8 kV rated impulse withstand and 1000 V insulation → Business Impact: Higher electrical robustness against surges and transient events → Application: Critical process lines with stringent surge requirements. Feature: ABB EcoSolutions and recyclability 55.70% EN45555 → Business Impact: Improved environmental performance and potential end-of-life cost savings → Application: Projects prioritizing sustainability and regulatory compliance.

Get a Quick Quote for a ABB 1SDA067902R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067902R1? Enquire Now

FAQs

This 4P device uses front terminals for straightforward wiring and quick access during commissioning. It supports busbar connections from 32.5 to 100 mm² and requires a tightening torque of 6 N·m. In panel layouts, plan for space to accommodate the 120 mm width and 130 mm height while ensuring clearance for front-terminal wiring and wiring ducts.
Yes. The breaker is designed to IEC60947-2 compliant, with a CE Declaration of Conformity documented for Tmax XT products. Additional third-party certifications from GL and LR support global deployment. For procurement, reference the CE declaration and the listed certificates to confirm regulatory alignment across target markets.
Rated service short-circuit breaking capacity (Ics) is listed as 100 kA at 220/230/240 V and 70 kA at 380/415/440 V, 50 kA at 500 V, 30 kA at 525 V, and 15 kA at 690 V. Rated ultimate breaking capacity (Icu) follows the same voltage-dependent pattern. These values ensure suitable protection for distribution boards and machine feeders under diverse supply conditions.
The 1SDA067902R1 is a Tmax XT family device featuring Ekip LSI release for reliable protection and coordination within XT switchgear. It supports front-terminal configuration, 690 V AC rating, and 10 A nominal current, enabling seamless replacement or expansion in XT-based installations and OEM panel builds while preserving electrical performance and safety margins.
The product carries RoHS and REACH declarations, CMRT for conflict minerals reporting, and an EPD option under ABB EcoSolutions. Recyclability is targeted at 55.70% per EN45555, with end-of-life disassembly guidance provided for Tmax XT XT2 ELT. These details help customers meet sustainability goals and regulatory requirements across regions.