ABB 1SDA067907R1 Moulded Case Breaker - IEC60947-2
Part Number: 1SDA067907R1
Quick Summary
ABB 1SDA067907R1 Moulded Case Breaker is a fixed four-pole circuit breaker for distribution panels. Engineers often struggle with space, front-terminal access, and precise tripping coordination in control cabinets; this device addresses those needs. It complies with IEC 60947-2 and features a CE Declaration of Conformity, with ETIM EC000228 classification to support global procurement. By aligning with SACE Tmax XT families and offering reliable front-terminal installation, it delivers business value through safer protection and faster commissioning. Customers benefit from reduced wiring errors, easier maintenance, and consistent performance under 50/60 Hz operation. With 4P, front-terminal access, and a 160 A rating, this MCCB supports scalable protection schemes in industrial estates.
Product Information
Extended Description
1SDA067907R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 160 A FULLY RATED NEUTRAL
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
8cf77dc3-f516-4aef-b76c-6b40f513e7e9 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4160FFF000XXX
E-Number (Norway)
4379707
EAN
8015644018030
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644018030
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole XT2 fixed breaker with front terminals and Ekip LSI release. Business Impact: Enhanced multi‑phase protection with fast, reliable tripping to minimize downtime in power distribution. Application: Panelboards and MCC assemblies in manufacturing facilities. The front-terminal design simplifies wiring and maintenance, reducing installation time and error rates. Feature: 160 A rated current and 690 V AC nominal voltage. Business Impact: Robust protection for medium-scale industrial feeders, enabling safe operation of motors and transformers. Application: Distribution networks across process plants. Feature: Busbar connection capacity 32.5 to 100 mm². Business Impact: Flexible wiring and modular layout, supporting scalable layouts in retrofit projects and upgrades. Application: New builds and modernization programs. Feature: Ics up to 100 kA and Icu up to 100 kA rated against specified voltages. Business Impact: High fault-handling capability delivers dependable protection for critical loads and transformers, reducing collateral damage. Application: Transformer or generator protection in sub-distribution panels. Feature: Front-terminal, bolt-type connections with 6 N·m tightening torque. Business Impact: Secure, vibration-resistant terminations that maintain integrity over life cycles. Application: Harsh industrial environments with frequent thermal cycling. Feature: RoHS, REACH, and CMRT/EPD certifications and disclosures. Business Impact: Ensures regulatory compliance and sustainable procurement across global supply chains. Application: Automotive, chemical, and electronics manufacturing facilities. Feature: Compact dimensions and weight of 120 mm x 130 mm x 82.5 mm and 1.6 kg. Business Impact: Space-efficient installation in compact control cabinets and particle-free enclosures. Application: Industrial control panels and machine housings. Feature: 50/60 Hz rated operation and a 30 ms opening time. Business Impact: Fast response for short-circuit protection with minimal mechanical wear. Application: Continuous operation environments requiring reliable protection.
Get a Quick Quote for a ABB 1SDA067907R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067907R1?
Enquire Now
FAQs
It is designed for front-terminal connections on four-pole MCCBs and supports busbars from 32.5 to 100 mm². Suitable for distribution boards, MCCs, transformers, and control panels in industrial facilities.
It complies with IEC 60947-2, includes a CE Declaration of Conformity, and aligns with ETIM EC000228 classification. It also references REACH, RoHS, and CMRT disclosures for global procurement.
Rated service short-circuit capacity (Ics) is up to 100 kA across 220–240 V, and rated ultimate short-circuit capacity (Icu) can reach 100 kA at the same ranges, with reduced values at higher voltages (e.g., 70–15 kA at 380–690 V).
Tightening torque is 6 N·m for bolt terminals. The product uses front terminal connections, enabling straightforward extraction and maintenance during servicing.
Net dimensions are 120 mm wide, 130 mm high, and 82.5 mm deep with a net weight of 1.6 kg, making it suitable for compact control cabinets and space-constrained installations.